Difference between revisions of "Galaxy"
Jump to navigation
Jump to search
(Created page with "The Honeywell Galaxy Dimension panels are multi-area intrusion detection systems. The integration with HSYCO can be accomplished via RS-232 serial communication. Category:I...") |
|||
Line 48: | Line 48: | ||
|- | |- | ||
− | |rowspan="2"| | + | |pin |
+ | | | ||
+ | |<code> | ||
+ | |PIN code assigned to the “remote” user. This option is mandatory | ||
+ | |||
+ | |- | ||
+ | |||
+ | |maxzone | ||
+ | |4158 | ||
+ | |0 ≤ n ≤ 4158 | ||
+ | |highest zone number among the zones used on the panel. This option is recommended to improve the driver’s performances | ||
+ | |||
+ | |- | ||
+ | |||
+ | |maxgroup | ||
+ | |32 | ||
+ | |0 ≤ n ≤ 32 | ||
+ | |highest index among the groups used on the panel. This option is recommended to improve the driver’s performances | ||
+ | |||
+ | |- | ||
+ | |||
+ | |maxoutput | ||
+ | |256 | ||
+ | |0 ≤ n ≤ 256 | ||
+ | |highest index among the outputs used on the panel. This option is recommended to improve the driver’s performances | ||
+ | |- | ||
+ | |||
+ | |rowspan="2"|guiobject | ||
|rowspan="2"|true | |rowspan="2"|true | ||
|true | |true | ||
− | |enable | + | |enable support for the galaxy UI object |
|- | |- | ||
|false | |false | ||
− | |disable support for the UI | + | |disable support for the galaxy UI object |
|- | |- | ||
− | |rowspan="2"| | + | |rowspan="2"|guizones |
− | |rowspan="2"| | + | |rowspan="2"|true |
|true | |true | ||
− | | | + | |enable support for the zones-related UI objects |
|- | |- | ||
|false | |false | ||
− | | | + | |disable support for the zones-related UI objects |
+ | |||
|- | |- | ||
− | |rowspan="2"| | + | |rowspan="2"|guioutputs |
|rowspan="2"|true | |rowspan="2"|true | ||
+ | |true | ||
+ | |enable support for the outputs-related UI objects | ||
+ | |- | ||
|false | |false | ||
− | | | + | |disable support for the outputs-related UI objects |
+ | |- | ||
+ | |||
+ | |rowspan="2"|startupevents | ||
+ | |rowspan="2"|false | ||
+ | |true | ||
+ | |generate IO events also during the driver’s start-up phase | ||
|- | |- | ||
|false | |false | ||
− | | | + | |start generating events only after HSYCO is aligned with the current status of the system |
|- | |- | ||
|pollinterval | |pollinterval | ||
− | | | + | |5 |
|n > 0 | |n > 0 | ||
|the data acquisition interval, in seconds | |the data acquisition interval, in seconds |
Revision as of 10:48, 20 December 2013
The Honeywell Galaxy Dimension panels are multi-area intrusion detection systems. The integration with HSYCO can be accomplished via RS-232 serial communication.
Communication
Employ a RS-232 straight cable to connect the panel directly to HSYCO or to an Ethernet/RS-232 gateway.
RS-232 parameters:
Baud rate | 9600 |
Data bits | 8 |
Stop bit | 1 |
Parity | none |
Flow control | none |
Configuration
It is required to configure the panel for HSYCO to be able to communicate with it. Follow these instructions:
- Enable the engineer access
- Menu 48.1.1 - set to 1 (Enabled)
- Enable engineer mode
- Enter engineer PIN, followed by ENT
- Enable remote access and events reporting
- Menu 56.6.2 - set to 1 (SIA)
- Set SIA level to 4
- Enable (set to ON) all the events to be sent to HSYCO
- Menu 56.6.3 - set an account number (e.g. “0001”)
Options
ID | Default | Values | Description |
---|---|---|---|
pin |
|
PIN code assigned to the “remote” user. This option is mandatory | |
maxzone | 4158 | 0 ≤ n ≤ 4158 | highest zone number among the zones used on the panel. This option is recommended to improve the driver’s performances |
maxgroup | 32 | 0 ≤ n ≤ 32 | highest index among the groups used on the panel. This option is recommended to improve the driver’s performances |
maxoutput | 256 | 0 ≤ n ≤ 256 | highest index among the outputs used on the panel. This option is recommended to improve the driver’s performances |
guiobject | true | true | enable support for the galaxy UI object |
false | disable support for the galaxy UI object | ||
guizones | true | true | enable support for the zones-related UI objects |
false | disable support for the zones-related UI objects
| ||
guioutputs | true | true | enable support for the outputs-related UI objects |
false | disable support for the outputs-related UI objects | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
pollinterval | 5 | n > 0 | the data acquisition interval, in seconds |
logsize | 20 | n ≥ 0 | the number of log lines to display in the UI object |