The Bentel KYO320 is an advanced, multi-area security system integrated HSYCO.
 
The Bentel KYO320 is an advanced, multi-area security system integrated HSYCO.
 +
 
The KYO320 driver in HSYCO supports the integration of more than one KYO320 unit on the same HSYCO SERVER.
 
The KYO320 driver in HSYCO supports the integration of more than one KYO320 unit on the same HSYCO SERVER.
 +
 
The integration with HSYCO can be accomplished through the standard RS-232 port on the KYO320’s motherboard.
 
The integration with HSYCO can be accomplished through the standard RS-232 port on the KYO320’s motherboard.
  
Line 31: Line 33:
 
|}
 
|}
  
 +
== HSYCO Configuration ==
 +
Add a BENTEL I/O Server in the [[Settings#I/O Servers|I/O Servers section of the Settings]] and set its parameters:
 +
 +
=== Communication ===
 +
*'''Comm ID''': select the comm port connected to the panel.
  
== HSYCO Configuration ==
+
=== High Availability ===
 +
*'''Shutdown when inactive''': defaults to true.
  
 
=== Options ===
 
=== Options ===
Line 67: Line 75:
 
|false
 
|false
 
|disable zone status log
 
|disable zone status log
 +
|-
 +
 +
|rowspan="2"|userlogs
 +
|rowspan="2"|false
 +
|true
 +
|generates logs that can be viewed with the userlist object, and can be selected to generate user events
 +
|-
 +
|false
 +
|logs for userlist objects disabled. Normal text logs are generated even when this option is false
 
|-
 
|-
  
Line 388: Line 405:
 
|turn on output <n> using code <c>
 
|turn on output <n> using code <c>
 
|-
 
|-
 +
 +
|}
 +
 +
== User Interface ==
 +
 +
=== Bentel Object ===
 +
 +
{{:Bentel_(UI Object)}}
 +
 +
=== UISET Actions ===
 +
 +
{| class="wikitable"
 +
!ID
 +
!Attribute
 +
!colspan="2"|Set to
 +
|-
 +
 +
|areas
 +
|value
 +
|the status of all partitions
 +
|-
 +
 +
|log0
 +
|value
 +
|the latest entry of the security log for a short period
 +
|-
 +
 +
|logs
 +
|value
 +
|the latest entries of the security log (as many as specified in hsyco.ini)
 +
|-
 +
 +
|zones
 +
|value
 +
|the status of all known zones (zones are added to this list as soon as an event is detected on a zone)
 +
|-
 +
 +
|connection.label.online
 +
|visible
 +
|true when the panel is connected to HSYCO, false otherwise
 +
|-
 +
 +
|connection.label.offline
 +
|visible
 +
|true when the panel is not connected to HSYCO, false otherwise
 +
|-
 +
 +
|partition.<n>.label.alarm
 +
|visible
 +
|true when partition <n> alarm is active, false otherwise
 +
|-
 +
 +
|partition.<n>.label.armed
 +
|visible
 +
|true when partition <n> is armed, false otherwise
 +
|-
 +
 +
|partition.<n>.label.disarmed
 +
|visible
 +
|true when partition <n> is disarmed, false otherwise
 +
|-
 +
 +
|partition.<n>.label.away
 +
|visible
 +
|true when partition <n> is armed in away mode, false otherwise
 +
|-
 +
 +
|partition.<n>.label.stay
 +
|visible
 +
|true when partition <n> is armed in stay mode, false otherwise
 +
|-
 +
 +
|partition.<n>.label.staynodelay
 +
|visible
 +
|true when partition <n> is armed in stay no delay mode, false otherwise
 +
|-
 +
 +
|zone.<n>.label.alarm
 +
|visible
 +
|true when zone <n> alarm is active
 +
|-
 +
 +
|zone.<n>.label.tamper
 +
|visible
 +
|true when zone <n> tamper alarm is active
 +
|-
 +
 +
|zone.<n>.label.disabled
 +
|visible
 +
|true when zone <n> is disabled
 +
|-
 +
|}
 +
 +
== Log Files ==
 +
 +
A permanent record of all the events shown in the log page is saved in a file called security.log in the logs/YYYY directory for the current year.
 +
 +
This file is never overwritten or deleted by HSYCO.
 +
<pre>
 +
2014.07.30 20:09:21.760 - SECOND FLOOR - ARMED
 +
2014.07.30 20:09:21.763 - SECOND FLOOR - AWAY
 +
2014.07.30 20:10:02.364 - [2] GARAGE - OPEN
 +
2014.07.30 20:10:04.779 - [2] GARAGE - OK
 +
2014.07.30 20:10:06.167 - BASEMENT - ALARM
 +
2014.07.30 20:10:48.477 - BASEMENT - DISARMED
 +
2014.07.30 20:10:48.481 - SECOND FLOOR - DISARMED
 +
2014.07.30 20:39:31.326 - ZONE 281 - OPEN
 +
2014.07.30 20:39:36.708 - ZONE 281 - OK
 +
2014.07.30 20:40:41.571 - AC POWER - FAULT
 +
2014.07.30 20:49:58.945 - ZONE 281 - OPEN
 +
2014.07.30 20:50:04.181 - ZONE 281 - OK
 +
2014.07.30 20:50:11.559 - AC POWER - OK
 +
</pre>
 +
 +
Other information related to the Bentel KYO driver are saved in the daily message.log files.
 +
 +
== Release Notes ==
 +
=== 3.3.0 ===
 +
*Bentel KYO driver converted to I/O Server
 +
*Java API write command methods are now obsolete and deprecated, replaced by IO write commands
 +
*new (bentel) object
 +
*new option userlogs. Used to create (userlist) clickable logs
 +
 +
=== 2.0.0 ===
 +
*full integration within HSYCO 2.9.0
 +
=== 1.1.0 ===
 +
*change to the status polling thread to improve recovery time after transient communication problems
 +
 +
----
 +
 +
 +
''Bentel, KYO and KYO320 are registered trademarks of BENTEL SECURITY SRL.''

Latest revision as of 14:30, 24 February 2015

The Bentel KYO320 is an advanced, multi-area security system integrated HSYCO.

The KYO320 driver in HSYCO supports the integration of more than one KYO320 unit on the same HSYCO SERVER.

The integration with HSYCO can be accomplished through the standard RS-232 port on the KYO320’s motherboard.

Communication

Employ a DE-9 (often called DB-9) female-female RS-232 crossed cable to connect the RS-232 KYO port to the serial port on HSYCO SERVER. The cable must follow this pinout diagram:

2 ↔ 3
3 ↔ 2
5 ↔ 5

RS-232 parameters:

Baud rate same as defined on the KYO320 (usually 9600, 38400 or 57600)
Data bits 8
Stop bit 1
Parity even
Flow control none

HSYCO Configuration

Add a BENTEL I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • Comm ID: select the comm port connected to the panel.

High Availability

  • Shutdown when inactive: defaults to true.

Options

ID Default Values Description
gui true true enable support for the UI object, UISET actions and USER commands
false disable UI support
language system language en language of log and display messages. Supported values are it and en
it
zoneactivitylog false true logs the open/close status of zones in the log page and security.log files
false disable zone status log
userlogs false true generates logs that can be viewed with the userlist object, and can be selected to generate user events
false logs for userlist objects disabled. Normal text logs are generated even when this option is false
code the user code to be used when sending IO commands to the KYO, if code is not explicitly set in the command
logsize 50 n ≥ 0 the number of log lines to display in the UI object
polltime 1000 n ≥ 0 the data polling interval, in milliseconds. Shorter time improve the response of the system, but increase the load on the CPU of both HSYCO and the KYO system

bentel.ini

The bentel.ini file is an optional configuration file located in the main directory (same directory as hsyco.ini or hsyco.jar) and used to define zones and partitions names. If defined, these names will be used instead of the original numbers in the log files and the bentel GUI object.

The bentel.ini is automatically detected at start-up. Changes to this file become effective when the I/O Server is restarted.

For each zone or partition, enter a line formatted as:

<io_server_id>.zone.<n> = <name>
<io_server_id>.area.<n> = <name>

For instance:

kyo.zone.1 = kitchen
kyo.zone.2 = garage
kyo.area.1 = basement
kyo.area.2 = second floor

Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
system.fault 1 R general system fault
0 R reset
system.batteryfault 1 R general battery fault
0 R reset
system.lowbattery 1 R low battery
0 R reset
system.nobattery 1 R low battery
0 R reset
system.nopower 1 R general no AC power fault
0 R reset
system.tamper 1 R general tamper condition (central unit, zones, modules)
0 R reset
system.radiofault 1 R general radio modules fault
0 R reset
system.radiolowbattery 1 R radio modules low battery
0 R reset
system.duress 1 R duress status
0 R reset
system.maintenance 1 R maintenance mode
0 R reset
zone.<n>.disabled 1 R zone <n> disabled
0 R zone <n> enabled
zone.<n>.alarm 1 R zone <n> alarm
0 R reset
zone.<n>.tamper 1 R zone <n> tamper alarm
0 R reset
zone.<n> enable W enable zone <n> using default code
disable W disable zone <n> using default code
enable.<c> W enable zone <n> using code <c>
disable.<c> W disable zone <n> using code <c>
partition.<n>.armed 1 R area <n> is armed (any mode)
0 R reset
partition.<n>.disarmed 1 R area <n> is not armed
0 R reset
partition.<n>.away 1 R area <n> away mode
0 R reset
partition.<n>.stay 1 R area <n> stay mode
0 R reset
partition.<n>.staynodelay 1 R area <n> stay no delay mode
0 R reset
partition.<n>.alarm 1 R area <n> alarm memory
0 R reset
partition.<n> away W arm area <n> using default code
disarm W disarm area <n> using default code
stay W stay arm area <n> using default code
staynodelay W instant stay arm area <n> using default code
away.<c> W arm area <n> using code <c>
disarm.<c> W disarm area <n> using code <c>
stay.<c> W stay arm area <n> using code <c>
staynodelay.<c> W instant stay arm area <n> using code <c>
out.<n> off W turn off output <n> using default code
on W turn on output <n> using default code
off.<c> W turn off output <n> using code <c>
on.<c> W turn on output <n> using code <c>

User Interface

Bentel Object

The user interface for the Bentel KYO320 multi-area intrusion detection system:

UI Object bentel1.png UI Object bentel2.png UI Object bentel3.png UI Object bentel4.png

The Bentel object is listed in the Project Editor’s new object list only when at least one Bentel I/O Server is defined.

Parameters

  • server id: the server ID
  • position: the object's position. Use the pixels or rows and columns coordinates format

Syntax

(bentel <server id>; <position>)

E.g.

(bentel serverid; x10y20)

UISET Actions

ID Attribute Set to
areas value the status of all partitions
log0 value the latest entry of the security log for a short period
logs value the latest entries of the security log (as many as specified in hsyco.ini)
zones value the status of all known zones (zones are added to this list as soon as an event is detected on a zone)
connection.label.online visible true when the panel is connected to HSYCO, false otherwise
connection.label.offline visible true when the panel is not connected to HSYCO, false otherwise
partition.<n>.label.alarm visible true when partition <n> alarm is active, false otherwise
partition.<n>.label.armed visible true when partition <n> is armed, false otherwise
partition.<n>.label.disarmed visible true when partition <n> is disarmed, false otherwise
partition.<n>.label.away visible true when partition <n> is armed in away mode, false otherwise
partition.<n>.label.stay visible true when partition <n> is armed in stay mode, false otherwise
partition.<n>.label.staynodelay visible true when partition <n> is armed in stay no delay mode, false otherwise
zone.<n>.label.alarm visible true when zone <n> alarm is active
zone.<n>.label.tamper visible true when zone <n> tamper alarm is active
zone.<n>.label.disabled visible true when zone <n> is disabled

Log Files

A permanent record of all the events shown in the log page is saved in a file called security.log in the logs/YYYY directory for the current year.

This file is never overwritten or deleted by HSYCO.

2014.07.30 20:09:21.760 - SECOND FLOOR - ARMED
2014.07.30 20:09:21.763 - SECOND FLOOR - AWAY
2014.07.30 20:10:02.364 - [2] GARAGE - OPEN
2014.07.30 20:10:04.779 - [2] GARAGE - OK
2014.07.30 20:10:06.167 - BASEMENT - ALARM
2014.07.30 20:10:48.477 - BASEMENT - DISARMED
2014.07.30 20:10:48.481 - SECOND FLOOR - DISARMED
2014.07.30 20:39:31.326 - ZONE 281 - OPEN
2014.07.30 20:39:36.708 - ZONE 281 - OK
2014.07.30 20:40:41.571 - AC POWER - FAULT
2014.07.30 20:49:58.945 - ZONE 281 - OPEN
2014.07.30 20:50:04.181 - ZONE 281 - OK
2014.07.30 20:50:11.559 - AC POWER - OK

Other information related to the Bentel KYO driver are saved in the daily message.log files.

Release Notes

3.3.0

  • Bentel KYO driver converted to I/O Server
  • Java API write command methods are now obsolete and deprecated, replaced by IO write commands
  • new (bentel) object
  • new option userlogs. Used to create (userlist) clickable logs

2.0.0

  • full integration within HSYCO 2.9.0

1.1.0

  • change to the status polling thread to improve recovery time after transient communication problems