Line 324: | Line 324: | ||
|W | |W | ||
|enabled the minimum air damper control on all the zones | |enabled the minimum air damper control on all the zones | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="3" |config.probe | ||
+ | |off | ||
+ | |W | ||
+ | |set the local probe to off on all zones | ||
+ | |- | ||
+ | |remote | ||
+ | |W | ||
+ | |set the remote probe as input on all zones | ||
+ | |- | ||
+ | |floor | ||
+ | |W | ||
+ | |set the probe as electrical heating floor protection on all zones | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="3" |config.ecoinput | ||
+ | |disabled | ||
+ | |W | ||
+ | |disable the Eco-Sleep activation input on all zones | ||
+ | |- | ||
+ | |open | ||
+ | |W | ||
+ | |enable the Eco-Sleep activation input in “normally open” mode on all zones | ||
+ | |- | ||
+ | |closed | ||
+ | |W | ||
+ | |enable the Eco-Sleep activation input in “normally closed” mode on all zones | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="3" |config.forcedoffinput | ||
+ | |disabled | ||
+ | |W | ||
+ | |disable the local forced off input on all zones | ||
+ | |- | ||
+ | |open | ||
+ | |W | ||
+ | |enable the local forced off input in “normally open” mode on all zones | ||
+ | |- | ||
+ | |closed | ||
+ | |W | ||
+ | |enable the local forced off input in “normally closed” mode on all zones | ||
|- | |- | ||
Line 696: | Line 741: | ||
|enabled the minimum air damper control on zone <n> | |enabled the minimum air damper control on zone <n> | ||
+ | |- | ||
+ | |||
+ | |rowspan="8" |z<n>.config.probe | ||
+ | |rowspan="2"|off | ||
+ | |R | ||
+ | |the local probe is off on zone <n> | ||
+ | |- | ||
+ | |W | ||
+ | |set the local probe to off on zone <n> | ||
+ | |- | ||
+ | |rowspan="2"|remote | ||
+ | |R | ||
+ | |the remote probe temperature is set to be the input temperature on zone <n> | ||
+ | |- | ||
+ | |W | ||
+ | |set the remote probe as input on zone <n> | ||
+ | |- | ||
+ | |rowspan="2"|floor | ||
+ | |R | ||
+ | |the probe is used as electrical heating floor protection probe on zone <n> | ||
+ | |- | ||
+ | |W | ||
+ | |set the probe as electrical heating floor protection on zone <n> | ||
+ | |- | ||
+ | |0 | ||
+ | |R | ||
+ | |remote probe not connected on zone <n> | ||
+ | |- | ||
+ | |1 | ||
+ | |R | ||
+ | |remote probe connected on zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="6" |z<n>.config.ecoinput | ||
+ | |rowspan="2"|disabled | ||
+ | |R | ||
+ | |the Eco-Sleep activation input is disabled on zone <n> | ||
+ | |- | ||
+ | |W | ||
+ | |disable the Eco-Sleep activation input on zone <n> | ||
+ | |- | ||
+ | |rowspan="2"|open | ||
+ | |R | ||
+ | |the Eco-Sleep activation input is enabled and set to “normally open” mode on zone <n> | ||
+ | |- | ||
+ | |W | ||
+ | |enable the Eco-Sleep activation input in “normally open” mode on zone <n> | ||
+ | |- | ||
+ | |rowspan="2"|closed | ||
+ | |R | ||
+ | |the Eco-Sleep activation input is enabled and set to “normally closed” mode on zone <n> | ||
+ | |- | ||
+ | |W | ||
+ | |enable the Eco-Sleep activation input in “normally closed” mode on zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="6" |z<n>.config.forcedoffinput | ||
+ | |rowspan="2"|disabled | ||
+ | |R | ||
+ | |the local forced off input is disabled on zone <n> | ||
+ | |- | ||
+ | |W | ||
+ | |disable the local forced off input on zone <n> | ||
+ | |- | ||
+ | |rowspan="2"|open | ||
+ | |R | ||
+ | |the local forced off input is enabled and set to “normally open” mode on zone <n> | ||
+ | |- | ||
+ | |W | ||
+ | |enable the local forced off input in “normally open” mode on zone <n> | ||
+ | |- | ||
+ | |rowspan="2"|closed | ||
+ | |R | ||
+ | |the local forced off input is enabled and set to “normally closed” mode on zone <n> | ||
+ | |- | ||
+ | |W | ||
+ | |enable the local forced off input in “normally closed” mode on zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="2" |z<n>.status.outlet | ||
+ | |0 | ||
+ | |R | ||
+ | |the motorized outlet is closed on zone <n> | ||
+ | |- | ||
+ | |1 | ||
+ | |R | ||
+ | |the motorized outlet is open on zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="2" |z<n>.status.motor | ||
+ | |0 | ||
+ | |R | ||
+ | |the outlet motor is inactive on zone <n> | ||
+ | |- | ||
+ | |1 | ||
+ | |R | ||
+ | |the outlet motor is active on zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="2" |z<n>.status.heatingfloor | ||
+ | |0 | ||
+ | |R | ||
+ | |the heating floor is inactive on zone <n> | ||
+ | |- | ||
+ | |1 | ||
+ | |R | ||
+ | |the heating floor is active on zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="2" |z<n>.status.moduletype | ||
+ | |outlet | ||
+ | |R | ||
+ | |the module type of zone <n> is motorized outlet | ||
+ | |- | ||
+ | |fancoil | ||
+ | |R | ||
+ | |the module type of zone <n> is fancoil module | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="2" |z<n>.status.ecoinput | ||
+ | |0 | ||
+ | |R | ||
+ | |the module Eco-Sleep input is inactive on zone <n> | ||
+ | |- | ||
+ | |1 | ||
+ | |R | ||
+ | |the module Eco-Sleep input is active on zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="2" |z<n>.status.onoffinput | ||
+ | |0 | ||
+ | |R | ||
+ | |the module on/off input is inactive on zone <n> | ||
+ | |- | ||
+ | |1 | ||
+ | |R | ||
+ | |the module on/off input is active on zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="4" |z<n>.status.fanspeed | ||
+ | |0 | ||
+ | |R | ||
+ | |the fancoil ventilation is off on zone <n> | ||
+ | |- | ||
+ | |1 | ||
+ | |R | ||
+ | |the fancoil ventilation speed is set to 1 on zone <n> | ||
+ | |- | ||
+ | |2 | ||
+ | |R | ||
+ | |the fancoil ventilation speed is set to 2 on zone <n> | ||
+ | |- | ||
+ | |3 | ||
+ | |R | ||
+ | |the fancoil ventilation speed is set to 3 on zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="4" |z<n>.status.propopening | ||
+ | |1 | ||
+ | |R | ||
+ | |the proportional opening status is set to step 1 on zone <n> | ||
+ | |- | ||
+ | |2 | ||
+ | |R | ||
+ | |the proportional opening status is set to step 2 on zone <n> | ||
+ | |- | ||
+ | |3 | ||
+ | |R | ||
+ | |the proportional opening status is set to step 3 on zone <n> | ||
+ | |- | ||
+ | |4 | ||
+ | |R | ||
+ | |the proportional opening status is set to step 4 on zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="2" |z<n>.status.thermconnection | ||
+ | |0 | ||
+ | |R | ||
+ | |the thermostat is not connected to zone <n> | ||
+ | |- | ||
+ | |1 | ||
+ | |R | ||
+ | |the thermostat is connected to zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="2" |z<n>.status.antifreeze | ||
+ | |0 | ||
+ | |R | ||
+ | |antifreeze function not active on zone <n> | ||
+ | |- | ||
+ | |1 | ||
+ | |R | ||
+ | |antifreeze function active on zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="2" |z<n>.error.motconnection | ||
+ | |0 | ||
+ | |R | ||
+ | |the motor is properly connected to the module of zone <n> | ||
+ | |- | ||
+ | |1 | ||
+ | |R | ||
+ | |the motor is not connected to the module of zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="2" |z<n>.error.motblock | ||
+ | |0 | ||
+ | |R | ||
+ | |the motor is not blocked zone <n> | ||
+ | |- | ||
+ | |1 | ||
+ | |R | ||
+ | |the motor is blocked on zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="2" |z<n>.error.probeopen | ||
+ | |0 | ||
+ | |R | ||
+ | |the probe input is not in open circuit on zone <n> | ||
+ | |- | ||
+ | |1 | ||
+ | |R | ||
+ | |the probe input is in open circuit on zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="2" |z<n>.error.probeshort | ||
+ | |0 | ||
+ | |R | ||
+ | |the probe input is not in short circuit on zone <n> | ||
+ | |- | ||
+ | |1 | ||
+ | |R | ||
+ | |the probe input is in short circuit on zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="2" |z<n>.error.config | ||
+ | |0 | ||
+ | |R | ||
+ | |the configuration is OK on zone <n> | ||
+ | |- | ||
+ | |1 | ||
+ | |R | ||
+ | |the configuration is not compatible with zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="2" |z<n>.error.comm | ||
+ | |0 | ||
+ | |R | ||
+ | |communication with remote probe OK on zone <n> | ||
+ | |- | ||
+ | |1 | ||
+ | |R | ||
+ | |communication with remote probe lost on zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="2" |z<n>.error | ||
+ | |0 | ||
+ | |R | ||
+ | |none of the above errors is active on zone <n> | ||
+ | |- | ||
+ | |1 | ||
+ | |R | ||
+ | |at least one of the above errors is active on zone <n> | ||
+ | |||
+ | |- | ||
+ | |||
+ | |rowspan="2" |z<n>.error | ||
+ | |0 | ||
+ | |W | ||
+ | |unset the system time | ||
+ | |- | ||
+ | |<d>:<h>:<m> | ||
+ | |W | ||
+ | |set the system time to the specified value. <d> indicates the day (1 = Monday, ..., 7 = Sunday) <h> specifies the hour (from 0 to 23) and <m> the minutes (from 1 to 59). For instance a value of “2:13:10” represents the time 1:10 pm of Tuesday. | ||
|} | |} |
Revision as of 16:22, 7 January 2014
Airzone is a control framework for ducted air conditioning systems which allows for the control of several zones independently. This I/O server provides support for this Airzone systems: INNOBUS, FLEXA, ANTREE and CEN.
Communication
Airzone communicates with HSYCO through a modbus connection employing a RS-485 gateway.
RS-485 parameters:
Baud rate | 19200 |
Data bits | 8 |
Stop bit | 1 |
Parity | even |
Flow control | none |
HSYCO Configuration
Options
ID | Default | Values | Description |
---|---|---|---|
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
pollinterval | 20 | n > 0 | the data acquisition interval, in seconds |
version | 1 | 1 | use protocol version 1 |
2 | use protocol version 2 |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
z<n>.name | <text> | R | the name of zone <n> is set to <text> |
power | 0 | R | the system is off |
W | turn off the system | ||
1 | R | the system is on | |
W | turn on the system | ||
setpoint.temp | <val> | W | set the setpoint temperature of all the zones to <val> |
temp.unit | c | R | the system unit for the temperature is set to °C/10 |
f | R | the system unit for the temperature is set to °F | |
mode | stop | RW | read/write the working mode of the system |
cold | |||
heatpump | |||
ventilation | |||
heatingfloor | |||
combheating | |||
dehumid | |||
mode.eco | 0 | W | set the Eco-Sleep mode off on all the zones |
1 | W | set the Eco-Sleep mode on on all the zones | |
mode.control | manual | W | set the control mode of all the zones to manual |
automatic | W | set the control mode of all the zones to automatic | |
mode.hold | 0 | W | disable the touch hold of the system |
1 | W | enable the touch hold of the system | |
mode.fanspeed | auto | R | the fancoil fan speed of the system is set to automatic |
W | set the fancoil fan speed of the system to automatic | ||
1 | R | the fancoil fan speed of the system is set to speed 1 | |
W | set the fancoil fan speed of the system to speed 1 | ||
2 | R | the fancoil fan speed of the system is set to speed 2 | |
W | set the fancoil fan speed of the system to speed 2 | ||
3 | R | the fancoil fan speed of the system is set to speed 3 | |
W | set the fancoil fan speed of the system to speed 3 | ||
flip | W | cycle on the fancoil fan speed status following the order: auto - 1 - 2 - 3 - auto ... | |
mode.sleep | off | W | set sleep mode to off on all zones |
30 | W | set sleep mode to 30 minutes on all zone | |
60 | W | set sleep mode to 60 minutes on all zones | |
90 | W | set sleep mode to 90 minutes on all zones | |
flip | W | cycle on the sleep mode status following the order: off - 30 - 60 - 90 - off ... | |
config.motregulationtype | on/off | W | set the motorization regulation type of all the zones to "on/off" |
proportional | W | set the motorization regulation type of all the zones to "proportional" | |
config.motcontrolled | 0 | W | disable the control of the motorization on all the zones |
1 | W | enable the control of the motorization on all the zones | |
config.ac | 0 | W | disable air conditioning on all zones |
1 | W | enable air conditioning on all zones | |
config.heatingfloorctrl | 0 | W | disable the heating floor controller on all zones |
1 | W | enable the heating floor controller on all zones | |
config.angle.heating | 90 | W | write the intelligent motorized grille opening angle on heating mode (expressed in °) on all the zones |
50 | |||
45 | |||
40 | |||
config.angle.cooling | 90 | W | write the intelligent motorized grille opening angle on cooling mode (expressed in °) on all the zones |
50 | |||
45 | |||
40 | |||
config.minairdamper | 0 | W | disabled the minimum air damper control on all the zones |
1 | W | enabled the minimum air damper control on all the zones | |
config.probe | off | W | set the local probe to off on all zones |
remote | W | set the remote probe as input on all zones | |
floor | W | set the probe as electrical heating floor protection on all zones | |
config.ecoinput | disabled | W | disable the Eco-Sleep activation input on all zones |
open | W | enable the Eco-Sleep activation input in “normally open” mode on all zones | |
closed | W | enable the Eco-Sleep activation input in “normally closed” mode on all zones | |
config.forcedoffinput | disabled | W | disable the local forced off input on all zones |
open | W | enable the local forced off input in “normally open” mode on all zones | |
closed | W | enable the local forced off input in “normally closed” mode on all zones | |
z<n>.power | 0 | R | the zone is off |
W | turn off the zone | ||
1 | R | the zone is on | |
W | turn on the zone | ||
flip | W | switch the status of the zone | |
z<n>.setpoint.temp | <val> | R | the setpoint temperature of this zone is set to <val> |
W | set the setpoint temperature of the zone to <val> | ||
up | W | increase the setpoint temperature of 0.5 °C or 1°F depending on the system settings | |
down | W | decrease the setpoint temperature of 0.5 °C or 1°F depending on the system settings | |
z<n>.localtemp | <val> | R | the local temperature is <val> |
z<n>.remotetemp | <val> | R | the temperature measured by the remote probe is <val> |
z<n>.temp | <val> | R | the temperature measured by the input probe of this zone is <val>.
For protocol version 1, if the 'z<n>.config.probe' datapoint has value 'remote', then <val> corresponds to the value of the 'z<n>.remotetemp' datapoint, otherwise to the value of the 'z<n>.localtemp' datapoint. For protocol version 2, if the 'z<n>.config.probe' datapoint has value '1', then <val> corresponds to the value of the 'z<n>.remotetemp' datapoint, otherwise to the value of the 'z<n>.localtemp' datapoint. |
z<n>.mode.eco | 0 | R | the Eco-Sleep mode is disabled for zone <n> |
W | set the Eco-Sleep mode off for zone <n> | ||
1 | R | the Eco-Sleep mode is active for zone <n> | |
W | set the Eco-Sleep mode on for zone <n> | ||
flip | W | switch the Eco-Sleep mode status of zone <n> | |
z<n>.mode.control | manual | R | the control mode for zone <n> is set to manual |
W | set the control mode of zone <n> to manual | ||
automatic | R | the control mode for zone <n> is set to automatic | |
W | set the control mode of zone <n> to automatic | ||
flip | W | switch the control mode of zone <n> | |
z<n>.mode.hold | 0 | R | the touch hold is disabled on zone <n> |
W | disable the touch hold of zone <n> | ||
1 | R | the touch hold is enabled on zone <n> | |
W | enable the touch hold of zone <n> | ||
z<n>.mode.fanspeed | auto | R | the fancoil fan speed of zone <n> is set to automatic |
W | set the fancoil fan speed of zone <n> to automatic | ||
1 | R | the fancoil fan speed of zone <n> is set to speed 1 | |
W | set the fancoil fan speed of zone <n> to speed 1 | ||
2 | R | the fancoil fan speed of zone <n> is set to speed 2 | |
W | set the fancoil fan speed of zone <n> to speed 2 | ||
3 | R | the fancoil fan speed of zone <n> is set to speed 3 | |
W | set the fancoil fan speed of zone <n> to speed 3 | ||
flip | W | cycle on the fancoil fan speed status following the order: auto - 1 - 2 - 3 - auto ... | |
z<n>.mode.fancoilpower | 0 | R | the activation status of the fancoil of this zone if set to off |
1 | R | the activation status of the fancoil of this zone if set to on | |
z<n>.mode.sleep | off | R | sleep mode is off on zone <n> |
W | set sleep mode to off on zone <n> | ||
30 | R | sleep mode is set to 30 minutes on zone <n> | |
W | set sleep mode to 30 minutes on zone <n> | ||
60 | R | sleep mode is set to 60 minutes on zone <n> | |
W | set sleep mode to 60 minutes on zone <n> | ||
90 | R | sleep mode is set to 90 minutes on zone <n> | |
W | set sleep mode to 90 minutes on zone <n> | ||
flip | W | cycle on the sleep mode status following the order: off - 30 - 60 - 90 - off ... | |
z<n>.mode.prog | 0 | R | time programming is disabled on this zone |
1 | R | time programming is enabled on this zone | |
z<n>.mode | stop | RW | read/write the working mode of zone <n>. It is possible to write the working mode of a zone only if it is configured as master (setting the working mode of a master zone will also change the mode of all the zones connected to the same controller) |
cold | |||
heatpump | |||
ventilation | |||
heatingfloor | |||
combheating | |||
dehumid | |||
z<n>.config.master | 0 | R | zone <n> is not configured as master |
W | set zone <n> as not master | ||
1 | R | zone <n> is configured as master | |
W | set zone <n> as master | ||
z<n>.config.motregulationtype | on/off | R | the motorization regulation type of zone <n> is set to "on/off" |
W | set the motorization regulation type of zone <n> to "on/off" | ||
proportional | R | the motorization regulation type of zone <n> is set to "proportional" | |
W | set the motorization regulation type of zone <n> to "proportional" | ||
z<n>.config.motcontrolled | 0 | R | the control of the motorization is disabled on zone <n> |
W | disable the control of the motorization on zone <n> | ||
1 | R | the control of the motorization is enabled on zone <n> | |
W | enable the control of the motorization on zone <n> | ||
z<n>.config.ac | 0 | R | air conditioning is disabled on zone <n> |
W | disable air conditioning on zone <n> | ||
1 | R | air conditioning is enabled on zone <n> | |
W | enable air conditioning on zone <n> | ||
z<n>.config.heatingfloorctrl | 0 | R | the heating floor controller is disabled on zone <n> |
W | disable the heating floor controller on zone <n> | ||
1 | R | the heating floor controller is enabled on zone <n> | |
W | enable the heating floor controller on zone <n> | ||
z<n>.config.antifreeze | 0 | R | antifreeze function not configured on zone <n> |
1 | R | antifreeze function configured on zone <n> | |
z<n>.config.angle.heating | 90 | RW | read/write the intelligent motorized grille opening angle on heating mode (expressed in °) |
50 | |||
45 | |||
40 | |||
z<n>.config.angle.cooling | 90 | RW | read/write the intelligent motorized grille opening angle on cooling mode (expressed in °) |
50 | |||
45 | |||
40 | |||
z<n>.config.minairdamper | 0 | R | the minimum air damper control on zone <n> is disabled |
W | disabled the minimum air damper control on zone <n> | ||
1 | R | the minimum air damper control on zone <n> is enabled | |
W | enabled the minimum air damper control on zone <n> | ||
z<n>.config.probe | off | R | the local probe is off on zone <n> |
W | set the local probe to off on zone <n> | ||
remote | R | the remote probe temperature is set to be the input temperature on zone <n> | |
W | set the remote probe as input on zone <n> | ||
floor | R | the probe is used as electrical heating floor protection probe on zone <n> | |
W | set the probe as electrical heating floor protection on zone <n> | ||
0 | R | remote probe not connected on zone <n> | |
1 | R | remote probe connected on zone <n> | |
z<n>.config.ecoinput | disabled | R | the Eco-Sleep activation input is disabled on zone <n> |
W | disable the Eco-Sleep activation input on zone <n> | ||
open | R | the Eco-Sleep activation input is enabled and set to “normally open” mode on zone <n> | |
W | enable the Eco-Sleep activation input in “normally open” mode on zone <n> | ||
closed | R | the Eco-Sleep activation input is enabled and set to “normally closed” mode on zone <n> | |
W | enable the Eco-Sleep activation input in “normally closed” mode on zone <n> | ||
z<n>.config.forcedoffinput | disabled | R | the local forced off input is disabled on zone <n> |
W | disable the local forced off input on zone <n> | ||
open | R | the local forced off input is enabled and set to “normally open” mode on zone <n> | |
W | enable the local forced off input in “normally open” mode on zone <n> | ||
closed | R | the local forced off input is enabled and set to “normally closed” mode on zone <n> | |
W | enable the local forced off input in “normally closed” mode on zone <n> | ||
z<n>.status.outlet | 0 | R | the motorized outlet is closed on zone <n> |
1 | R | the motorized outlet is open on zone <n> | |
z<n>.status.motor | 0 | R | the outlet motor is inactive on zone <n> |
1 | R | the outlet motor is active on zone <n> | |
z<n>.status.heatingfloor | 0 | R | the heating floor is inactive on zone <n> |
1 | R | the heating floor is active on zone <n> | |
z<n>.status.moduletype | outlet | R | the module type of zone <n> is motorized outlet |
fancoil | R | the module type of zone <n> is fancoil module | |
z<n>.status.ecoinput | 0 | R | the module Eco-Sleep input is inactive on zone <n> |
1 | R | the module Eco-Sleep input is active on zone <n> | |
z<n>.status.onoffinput | 0 | R | the module on/off input is inactive on zone <n> |
1 | R | the module on/off input is active on zone <n> | |
z<n>.status.fanspeed | 0 | R | the fancoil ventilation is off on zone <n> |
1 | R | the fancoil ventilation speed is set to 1 on zone <n> | |
2 | R | the fancoil ventilation speed is set to 2 on zone <n> | |
3 | R | the fancoil ventilation speed is set to 3 on zone <n> | |
z<n>.status.propopening | 1 | R | the proportional opening status is set to step 1 on zone <n> |
2 | R | the proportional opening status is set to step 2 on zone <n> | |
3 | R | the proportional opening status is set to step 3 on zone <n> | |
4 | R | the proportional opening status is set to step 4 on zone <n> | |
z<n>.status.thermconnection | 0 | R | the thermostat is not connected to zone <n> |
1 | R | the thermostat is connected to zone <n> | |
z<n>.status.antifreeze | 0 | R | antifreeze function not active on zone <n> |
1 | R | antifreeze function active on zone <n> | |
z<n>.error.motconnection | 0 | R | the motor is properly connected to the module of zone <n> |
1 | R | the motor is not connected to the module of zone <n> | |
z<n>.error.motblock | 0 | R | the motor is not blocked zone <n> |
1 | R | the motor is blocked on zone <n> | |
z<n>.error.probeopen | 0 | R | the probe input is not in open circuit on zone <n> |
1 | R | the probe input is in open circuit on zone <n> | |
z<n>.error.probeshort | 0 | R | the probe input is not in short circuit on zone <n> |
1 | R | the probe input is in short circuit on zone <n> | |
z<n>.error.config | 0 | R | the configuration is OK on zone <n> |
1 | R | the configuration is not compatible with zone <n> | |
z<n>.error.comm | 0 | R | communication with remote probe OK on zone <n> |
1 | R | communication with remote probe lost on zone <n> | |
z<n>.error | 0 | R | none of the above errors is active on zone <n> |
1 | R | at least one of the above errors is active on zone <n> | |
z<n>.error | 0 | W | unset the system time |
<d>:<h>:<m> | W | set the system time to the specified value. <d> indicates the day (1 = Monday, ..., 7 = Sunday) <h> specifies the hour (from 0 to 23) and <m> the minutes (from 1 to 59). For instance a value of “2:13:10” represents the time 1:10 pm of Tuesday. |