RayCONTROL
Revision as of 17:09, 19 March 2014 by Manuela (talk | contribs) (Created page with "RayCONTROL 30 is the control unit for the FCC Planterm temperature control system. RayCONTROL 30 supports up to 30 individual zones. Category:I/O Server == Communicati...")
RayCONTROL 30 is the control unit for the FCC Planterm temperature control system.
RayCONTROL 30 supports up to 30 individual zones.
Contents
Communication
RayNET is an interface module that provides a standard Modbus/RTU interface over RS485 for RayCONTROL 30. The default connection parameters are:
Modbus address: 1
RS-485 parameters:
Baud rate | 9600 |
Data bits | 8 |
Stop bit | 1 |
Parity | none |
Flow control | none |
Refer to the RayNET and RayCONTROL 30 technical documentation for installation, wiring and power supply requirements.
HSYCO connects to the Modbus bus through any standard Modbus/TCP gateway.
EL.MO. Configuration
HSYCO Configuration
Options
ID | Default | Values | Description |
---|---|---|---|
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
pollinterval | 30 | 1 ... 45 | the data acquisition interval, in seconds |
address | 1 | > 0 | the Modbus address of the RayCONTROL device |
readinterval | 25 | 0 ... 1000 | minimum interval between consecutive Modbus commands |
systems | 1 | 1 ... 2 | set to 1 if using only system 1; set to 2 is system 2 is used |
zones | 15 | 1 ... 30 | set to the highest zone number used |
sensivity | 5 | >0 | measured temperatures’ changes are reported only if the difference from last reading is equal or greater than the sensivity option, in 10th of Celsius degrees |
language | en | en, fr, it | the language used for text messages. If undefined, the global language option is used. English is used if the global language is also undefined |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
s<n>.status | off | R | system <n> is off |
W | turn off system <n> | ||
on | R | system <n> is on | |
W | turn on system <n> | ||
maint | R | system <n> is in maintenance mode |
User Interface
UISET Actions
USER Commands
ID | Attribute | Set to |
---|
Name | Param | Action |
---|
Release Notes
3.3.0
- new data points: s<n>.setpoint.winter.max s<n>.setpoint.winter.min s<n>.setpoint.summer.max s<n>.setpoint.summer.min z<n>.lock
- new readinterval option (defaults to 20 msec.)
- improved communication errors handling
3.0.0
- full integration in HSYCO 3.0.0