Airzone is a control framework for ducted air conditioning systems which allows for the control of several zones independently. This I/O server provides support for this Airzone systems: INNOBUS, FLEXA, ANTREE and CEN.
Communication
Airzone communicates with HSYCO through a modbus connection employing a RS-485 gateway.
RS-485 parameters:
Baud rate
|
19200
|
Data bits
|
8
|
Stop bit
|
1
|
Parity
|
even
|
Flow control
|
none
|
HSYCO Configuration
Options
ID
|
Default
|
Values
|
Description
|
gui
|
true
|
true
|
enable support for the UI object, UISET actions and USER commands
|
false
|
disable UI support
|
startupevents
|
false
|
true
|
generate IO events also during the driver’s start-up phase
|
false
|
start generating events only after HSYCO is aligned with the current status of the system
|
pollinterval
|
20
|
n > 0
|
the data acquisition interval, in seconds
|
version
|
1
|
1
|
use protocol version 1
|
2
|
use protocol version 2
|
Datapoints
ID
|
Value
|
R/W
|
Description
|
connection
|
online
|
R
|
connection established
|
offline
|
R
|
HSYCO can't connect to the panel
|