Difference between revisions of "Tecnoalarm"

From HSYCO
Jump to navigation Jump to search
Line 86: Line 86:
 
|1
 
|1
 
|R
 
|R
|general system stand- by status
+
|general system stand-by status
 +
|-
 +
|0
 +
|R
 +
|reset
 +
|-
 +
 
 +
|rowspan="2"|system.fault
 +
|1
 +
|R
 +
|general system fault (low battery or no AC power)
 +
|-
 +
|0
 +
|R
 +
|reset
 +
|-
 +
 
 +
|rowspan="2"|system.lowbattery
 +
|1
 +
|R
 +
|general low battery fault
 +
|-
 +
|0
 +
|R
 +
|reset
 +
|-
 +
 
 +
|rowspan="2"|system.nopower
 +
|1
 +
|R
 +
|general no AC power fault
 +
|-
 +
|0
 +
|R
 +
|reset
 +
|-
 +
 
 +
|rowspan="2"|system.tamper
 +
|1
 +
|R
 +
|general tamper condition (central unit, zones, modules, modules loss of connection)
 +
|-
 +
|0
 +
|R
 +
|reset
 +
|-
 +
 
 +
|rowspan="2"|system.radiofault
 +
|1
 +
|R
 +
|general radio modules fault
 +
|-
 +
|0
 +
|R
 +
|reset
 +
|-
 +
 
 +
|rowspan="2"|system.duress
 +
|1
 +
|R
 +
|duress status
 +
|-
 +
|0
 +
|R
 +
|reset
 +
|-
 +
 
 +
|rowspan="2"|system.techzone
 +
|1
 +
|R
 +
|general technical zones open status
 +
|-
 +
|0
 +
|R
 +
|reset
 +
|-
 +
 
 +
|rowspan="2"|system.normal
 +
|1
 +
|R
 +
|normal status (AC power ok, battery ok, all zones closed, no tamper)
 +
|-
 +
|0
 +
|R
 +
|reset
 +
|-
 +
 
 +
|rowspan="2"|system.maintenance
 +
|1
 +
|R
 +
|maintenance mode
 
|-
 
|-
 
|0
 
|0

Revision as of 16:24, 16 December 2013

TECNOALARM TP16-256, TP8-64BUS, TP8-96VIDEO, TP8-96GSM and TP16-512GSM are advanced, multi-area security systems integrated with a variety of wired and wireless sensors. The TECNO OUT driver in HSYCO supports the integration of more than one TP unit within the same HSYCO interface. The integration with HSYCO can be accomplished with a TCP/IP network connection.

Options

ID Default Values Description
code code the user code that the driver uses when sending commands to the Tecnoalarm system. It must be a valid user code, or the MASTER code when using the TP8-64BUS
model string the system’s model. Use one of the following values: TP16-256, TP8-64BUS, TP8-96VIDEO, TP8-96GSM or TP16-512GSM
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
gui true true enable support of the tecnoalarm Web interface object
false disable support of the tecnoalarm Web interface object
logsize 50 >=0 the number of log events shown in the tecnoalarm Web object. Set to 0 to hide the log in the tecnoalarm object
pass string the passphrase used to encrypt the TCP/IP traffic. If the Tecnoalarm system doesn’t support the passphrase, you should omit this parameter
polltime 1000 >=0 the data polling interval, in milliseconds. Shorter time improve the response of the system, but increase the load on the CPU of both HSYCO and the Tecnoalarm system

Datapoints

ID Value R/W Description
connection online R connection established
offline R connection failed
system.standby 1 R general system stand-by status
0 R reset
system.fault 1 R general system fault (low battery or no AC power)
0 R reset
system.lowbattery 1 R general low battery fault
0 R reset
system.nopower 1 R general no AC power fault
0 R reset
system.tamper 1 R general tamper condition (central unit, zones, modules, modules loss of connection)
0 R reset
system.radiofault 1 R general radio modules fault
0 R reset
system.duress 1 R duress status
0 R reset
system.techzone 1 R general technical zones open status
0 R reset
system.normal 1 R normal status (AC power ok, battery ok, all zones closed, no tamper)
0 R reset
system.maintenance 1 R maintenance mode
0 R reset