EL.MO. ETR100 is a multi-area intrusion detection system. The integration with HSYCO can be accomplished via direct control through the RS232 port on the panel.

Communication

Employ the RS-232 cable provided with the EL.MO. panel to connect it directly to HSYCO or to an Ethernet/RS-232 gateway.

RS-232 parameters:

Baud rate 9600
Data bits 8
Stop bit 1
Parity none
Flow control none

Options

ID Default Values Description
gui true true enable automatic support of Web GUI objects to show the system status and intercept control buttons
false disable support for the Web GUI
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
offlinelogs true false at startup request the log of all the events occurred while HSYCO was disconnected from the panel
false log only events occurred while HSYCO was connected to the panel
pollinterval 1 n > 0 the data acquisition interval, in seconds
logsize 20 n ≥ 0 the data acquisition interval, in seconds


Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
armed 1 R at least one partition is armed
W arm all active areas
0 R no partition is armed
W disarm all active areas
armed.max 1 R at least one partition is armed in "max security" mode
W arm all active areas in "max security" mode
0 R no partition is armed in "max security" mode
W disarm all active areas in "max security" mode
alarm 1 R alarm state active
0 R no active alarm
tamper 1 R tamper alarm active
0 R no active tamper alarm
i<n>.name <text> R the name of input <n> is set to <text>
i<n>.open 1 R input <n> open
0 R input <n> closed
i<n>.alarm 1 R alarm on input <n>
0 R no alarm on input <n>
i<n>.tamper 1 R tamper alarm on input <n>
0 R no tamper alarm on input <n>
i<n>.bypassed 1 R input <n> bypassed
W bypass input <n>
0 R input <n> enabled
W enable input <n>
o<n> 1 R output <n> active
W activate output <n>
0 R output <n> inactive
W deactivate output <n>
a<n>.<m>.name <text> R the name of partition <m> of area <n> is set to <text>
a<n>.armed 1 W arm all partitions of area <n>
0 W disarm all partitions of area <n>