Aritech Interlogix FP2000 is a multi-area fire panel. The integration with HSYCO can be accomplished via direct control through the RS232 port on the panel. The FP2000 I/O Server in HSYCO supports the integration of more than one unit within the same HSYCO interface.
Communication
Employ an RS-232 cable to connect the panel directly to HSYCO.
RS-232 parameters:
| Baud rate | same as panel settings (default 9600) |
| Data bits | 8 |
| Stop bit | 1 |
| Parity | none |
| Flow control | RTS/CTS |
HSYCO Configuration
Options
| ID | Default | Values | Description |
|---|---|---|---|
| gui | true | true | enable support for the UI object, UISET actions and USER commands |
| false | disable UI support | ||
| startupevents | false | true | generate IO events also during the driver’s start-up phase |
| false | start generating events only after HSYCO is aligned with the current status of the system | ||
| accesscode | 0 | 0 | do not request for authentication (the I/O Server will only be usable as panel emulator) |
| 1 ... 9999 | use the specified value as access code for requesting authentication | ||
| keypaddisable | false | true | disable the emulator keypad buttons |
| false | the emulator keypad buttons are enabled | ||
| controldisable | false | true | disable the emulator control buttons |
| false | the emulator control buttons are enabled | ||
| displayhlcolor | 339933 | 000000 ... FFFFFF | use the specified hexadecimal value as the highlight color for the display of the emulator |
Datapoints
| ID | Value | R/W | Description |
|---|---|---|---|
| connection | online | R | connection established |
| offline | R | HSYCO can't connect to the panel | |
| emulation | 1 | R | emulation is active |
| W | activate emulation | ||
| 0 | R | emulation is disabled | |
| W | disable emulation | ||
| led.general.fire.1
led.general.fire.2 |
on | R | the corresponding LED is on |
| off | R | the corresponding LED is off | |
| blink | W | the corresponding LED is on, blinking | |
| status.alarm.count | <num> | R | count of fires |
| status.fault.count | <num> | R | count of faults |
| status.condition.count | <num> | R | count of conditions |
| status.event.count | <num> | R | count of all the events other than fire, fault or condition |
| clock | <date_time> | R | the panel’s clock is set to <date_time>. The value has the format "yyyy-mm-dd hh:mm:ss" (e.g. "2012-12-30 16:59:23") |
| W | set the data and time of the panel to <date_time>. The value has the format "yyyy-mm-dd hh:mm:ss" (e.g. "2012-12-30 16:59:23") | ||
| read | W | request for reading date and time set on the panel | |
| l<n>.s<m>.name | <name> | R | reports the name of sensor <m> on loop <n> |
| l<n>.s<m>.alarm.fire | 1 | R | fire alarm active for sensor <m> on loop <n> |
| 0 | R | no fire alarm active for sensor <m> on loop <n> | |
| l<n>.s<m>.alarm.communication | 1 | R | fault alarm active for sensor <m> on loop <n> |
| 0 | R | no fault alarm active for sensor <m> on loop <n> | |
| l<n>.s<m>.alarm.disabled | 1 | R | disabled alarm active for sensor <m> on loop <n> |
| 0 | R | no disabled alarm active for sensor <m> on loop <n> | |
| l<n>.s<m>.alarm.type | 1 | R | wrong type alarm active for sensor <m> on loop <n> |
| 0 | R | no wrong type alarm active for sensor <m> on loop <n> | |
| l<n>.s<m>.alarm.address | 1 | R | double address alarm active for sensor <m> on loop <n> |
| 0 | R | no double address alarm active for sensor <m> on loop <n> | |
| l<n>.s<m>.alarm.condition | 1 | R | pre condition alarm active for sensor <m> on loop <n> |
| 0 | R | no pre condition alarm active for sensor <m> on loop <n> | |
| l<n>.s<m>.alarm.maintenance | 1 | R | maintenance alarm active for sensor <m> on loop <n> |
| 0 | R | no maintenance alarm active for sensor <m> on loop <n> | |
| l<n>.s<m>.alarm.notype | 1 | R | no type alarm active for sensor <m> on loop <n> |
| 0 | R | type alarm active for sensor <m> on loop <n> | |
| l<n>.s<m>.alarm.enabled | 1 | R | enabled alarm active for sensor <m> on loop <n> |
| 0 | R | no enabled alarm active for sensor <m> on loop <n> | |
| l<n>.s<m>.alarm.twoset | 1 | R | two set alarm active for sensor <m> on loop <n> |
| 0 | R | no two set alarm active for sensor <m> on loop <n> | |
| l<n>.s<m>.alarm.segment | 1 | R | 7 segment alarm active for sensor <m> on loop <n> |
| 0 | R | no 7 segment alarm active for sensor <m> on loop <n> | |
| l<n>.s<m>.alarm.led | 1 | R | LED alarm active for sensor <m> on loop <n> |
| 0 | R | no LED alarm active for sensor <m> on loop <n> | |
| l<n>.s<m>.alarm.segment.cont | 1 | R | 7 segment continuous alarm active for sensor <m> on loop <n> |
| 0 | R | no 7 segment continuous alarm active for sensor <m> on loop <n> | |
| l<n>.s<m>.alarm.flag | 1 | R | flag alarm active for sensor <m> on loop <n> |
| 0 | R | no flag alarm active for sensor <m> on loop <n> | |
| l<n>.s<m>.alarm.pending | 1 | R | alarm pending for sensor <m> on loop <n> |
| 0 | R | no alarm pending for sensor <m> on loop <n> | |
| l<n>.s<m>.alarm | 1 | R | one of the above alarms is active for sensor <m> on loop <n> |
| 0 | R | none of the above alarms is active for sensor <m> on loop <n> | |
| l<n>.s<m>.alarm.count | <num> | R | reports the number of alarm states been active for sensor <m> on loop <n> |
| z<n>.name | <name> | R | reports the name of zone <n> |
| z<n>.alarm.fire | 1 | R | MCP fire alarm active on zone <n> |
| 0 | R | no MCP fire alarm active on zone <n> | |
| z<n>.alarm.fault | 1 | R | fault alarm active on zone <n> |
| 0 | R | no fault alarm active on zone <n> | |
| z<n>.alarm.coincidence | 1 | R | coincidence alarm active on zone <n> |
| 0 | R | no coincidence fire alarm active on zone <n> | |
| z<n>.alarm.isolated | 1 | R | isolated alarm active on zone <n> |
| 0 | R | no isolated alarm active on zone <n> | |
| z<n>.alarm.test | 1 | R | test alarm active on zone <n> |
| 0 | R | no test alarm active on zone <n> | |
| z<n>.alarm.condition | 1 | R | condition alarm active on zone <n> |
| 0 | R | no condition alarm active on zone <n> | |
| z<n>.alarm.enabled | 1 | R | enabled alarm active on zone <n> |
| 0 | R | no enabled alarm active on zone <n> | |
| z<n>.alarm.autofire | 1 | R | auto fire alarm active on zone <n> |
| 0 | R | no auto fire alarm active on zone <n> | |
| z<n>.alarm.action | 1 | R | action zone alarm active on zone <n> |
| 0 | R | no action zone alarm active on zone <n> | |
| z<n>.alarm.warning | 1 | R | pre warning alarm active on zone <n> |
| 0 | R | no pre warning alarm active on zone <n> | |
| z<n>.zone.alarm | 1 | R | one of the above alarms is active on zone <n> |
| 0 | R | none of the above alarms is active on zone <n> | |
| z<n>.alarm.count | <num> | R | reports the number of alarm states active on sensors of zone <n> |
| z<n>.fault.count | <num> | R | reports the number of faults states active on sensors of zone <n> |
| z<n>.condition.count | <num> | R | reports the number of conditions active on sensors of zone <n> |
| z<n>.coincidence.count | <num> | R | reports the number of coincidence alarms active on sensors of zone <n> |
| z<n>.isolate.count | <num> | R | reports the number of isolations in zone <n> |
| a<n>.name | <name> | R | reports the name of area <n> |
| a<n>.alarm.fire | 1 | R | MCP fire alarm active on area <n> |
| 0 | R | no MCP fire alarm active on area <n> | |
| a<n>.alarm.fault | 1 | R | fault alarm active on area <n> |
| 0 | R | no fault alarm active on area <n> | |
| a<n>.alarm.coincidence | 1 | R | coincidence alarm active on area <n> |
| 0 | R | no coincidence alarm active on area <n> | |
| a<n>.alarm.isolated | 1 | R | isolated alarm active on area <n> |
| 0 | R | no isolated alarm active on area <n> | |
| a<n>.alarm.condition | 1 | R | condition alarm active on area <n> |
| 0 | R | no condition alarm active on area <n> | |
| a<n>.alarm.enabled | 1 | R | enabled alarm active on area <n> |
| 0 | R | no enabled alarm active on area <n> | |
| a<n>.alarm.action | 1 | R | action alarm active on area <n> |
| 0 | R | no action alarm active on area <n> | |
| a<n>.area.alarm | 1 | R | one of the above alarms is active on area <n> |
| 0 | R | none of the above alarms is active on area <n> | |
| a<n>.alarm.count | <num> | R | reports the number of alarm states active on sensors of area <n> |
| a<n>.fault.count | <num> | R | reports the number of faults states active on sensors of area <n> |
| a<n>.condition.count | <num> | R | reports the number of conditions active on sensors of area <n> |
| a<n>.coincidence.count | <num> | R | reports the number of coincidence alarms active on sensors of area <n> |
| a<n>.isolate.count | <num> | R | reports the number of isolations in area <n> |
| o<n>.name | <name> | R | reports the number of output <n> |
| o<n>.status | 1 | R | output <n> is active |
| 0 | R | output <n> is inactive | |
| read | W | request for reading the state of output <n> | |
| i<n>.name | <name> | R | reports the number of input <n> |
| i<n>.status | 1 | R | input <n> is active |
| 0 | R | input <n> is inactive | |
| read | W | request for reading the state of input <n> | |
| event.action.text
event.fire.text |
<text> | R | reports the text of the most recently logged event accordingly to its category |
| key | <key_value> | W | send the specified emulation key command to the panel (see following table for the list of key values) |
The following table shows the association between <key_values> and relative function:
| <key_value> | Function |
|---|---|
| 1 | Scroll |
| 2 | Display Alarm |
| 4 | Print Screen |
| 5 | Alpha Numeric |
| 6 | Right Arrow |
| 8 | Left Arrow |
| 9 | Silence Buzzer |
| 10 | Down Arrow |
| 11 | Reset |
| 12 | Disable |
| 13 | Enter |
| 14 | Test |
| 15 | Sound Sounder |
| 16 | Sounder Delay |
| 17 | Sounder Disable |
| 18 | Silence Sounder |
| 19 | Fire Brigade Disable |
| 20 | Fire Brigade Delay |
| 22 | Fire Brigade Stop |
| 26 | Up Arrow |
| 27 | Exit |
| 29 | Panel |
| 30 | All |
| 31 | Fire Brigade Signal |
| 48 | Key “0” |
| 49 | Key “1” |
| 50 | Key “2” |
| 51 | Key “3” |
| 52 | Key “4” |
| 53 | Key “5” |
| 54 | Key “6” |
| 55 | Key “7” |
| 56 | Key “8” |
| 57 | Key “9” |
| 211 | Fire Protection on |
| 212 | Fire Protection Silenced |
| 213 | Fire Protection Silenced |
| 214 | Fire Protection Enabled |
| 215 | Fire Protection Disabled |
| 216 | Fire Protection Disable |
| 217 | Fire Protection Delay off |
| 218 | Fire Protection Delay on |
| 219 | Fire Protection Delay |
| 220 | Fire Protection Delay |
| 221 | Fire Protection Delay |
| 222 | Fault Routing Test |
| 223 | Fault Routing Enabled |
| 224 | Fault Routing Disabled |
| 225 | Fault Routing Disable |
| 226 | Fault Routing Delay off |
| 227 | Fault Routing Delay on |
| 228 | Fault Routing Delay |
| 229 | Fire Brigade Test |
| 230 | Fire Brigade Enabled |
| 231 | Fire Brigade Disabled |
| 232 | Fire Brigade Delay off |
| 233 | Fire Brigade Delay on |
| 234 | Sounder Test |
| 235 | Sounder Enable |
| 236 | Sounder Disable |
| 237 | Sounder Delay off |
| 238 | Sounder Delay on |
| 239 | External Reset (from Repeater) |