Difference between revisions of "Hidedgesolo"

From HSYCO
Jump to navigation Jump to search
 
(16 intermediate revisions by 3 users not shown)
Line 1: Line 1:
The HID Edge solo ESR40, ESRP40, ES400 are single-door IP access control solution. This driver allows the integration of HID Edge Solo devices by using a TCP/IP connection. More than one device can be controlled at the same time.
+
The [http://www.hidglobal.com HID Edge Solo] '''ESR40, ESRP40, ES400''' are single-door IP access control solutions.  
  
[[Category:I/O Server]]
+
This I/O Server allows the integration of HID Edge Solo devices by using a TCP/IP connection.
  
== Communication ==
+
More than one device can be controlled at the same time.
  
An IP address must be assigned to the HID Edge Solo.
+
[[Category:I/O Server]]
  
== HID Edge Solo configuration ==
+
== HID Edge Solo Configuration ==
  
 
The HID Edge Solo can be connected to a POE switch or to a normal ethernet switch. In this case the power supply must be provided with an external adapter.
 
The HID Edge Solo can be connected to a POE switch or to a normal ethernet switch. In this case the power supply must be provided with an external adapter.
First of all, assign an IP address to the Edge Solo, then it’s mandatory to disable the SSL/TLS encryption in the installer settings interface.
+
First of all, assign a static IP address to the Edge Solo, then it’s mandatory to disable the SSL/TLS encryption in the installer settings interface.
  
 
[[File:hidedgesolo1.png]]
 
[[File:hidedgesolo1.png]]
 +
 +
== HSYCO Configuration ==
 +
Add an HIDEDGESOLO I/O Server in the [[Settings#I/O Servers|I/O Servers section of the Settings]] and set its parameters:
 +
 +
=== Communication ===
 +
*'''IP Address''': IP address configured on the device
 +
*'''IP Port''': TCP/IP port to use, leave blank for default port 80.
 +
 +
=== Authentication ===
 +
*'''User''': username set in the installer settings
 +
*'''Password''': password set in the installer settings.
 +
 +
=== High Availability ===
 +
*'''Shutdown when inactive''': defaults to true.
  
 
== Datapoints ==
 
== Datapoints ==
Line 189: Line 203:
 
|R
 
|R
 
|door forced
 
|door forced
 +
|-
 +
|state.name
 +
|<name>
 +
|R
 +
|the door's name
 
|-
 
|-
 
|rowspan="2" |state.relay
 
|rowspan="2" |state.relay
Line 198: Line 217:
 
|R
 
|R
 
|door relay open
 
|door relay open
 +
|-
 +
|rowspan="2" |state.relay.alert
 +
|unset
 +
|R
 +
|alert relay not active
 +
|-
 +
|set
 +
|R
 +
|alert relay active
 
|-
 
|-
 
|rowspan="2" |state.relay.aux
 
|rowspan="2" |state.relay.aux
 
|unset
 
|unset
 
|R
 
|R
|the device is not in alarm state
+
|aux relay not active
 
|-
 
|-
 
|set
 
|set
 
|R
 
|R
|the device is in alarm state
+
|aux relay active
 
|-
 
|-
 
|command.access
 
|command.access
Line 228: Line 256:
 
|}
 
|}
  
== Examples ==
+
== Release Notes ==
 
+
=== 3.4.0 ===
A valid pin is digit on the Wiegand keyboard of the EDGE SOLO. Here’s the HSYCO log:
+
*added support for two readers door controller
<pre>
 
IO MONITOR EVENT: hid1.state.relay = unset
 
IO MONITOR FORCED: hid1.access.granted = Gaffuri
 
IO MONITOR EVENT: hid1.state.relay = set
 
IO MONITOR EVENT: hid1.state.relay = unset
 
</pre>
 
 
 
The relay is set, the access is granted for the user. They relay is set for a time specified in the EDGE SOLO settings.
 
 
 
Access granted from a user button. Here’s the HSYCO log:
 
<pre>
 
WEB USER COMMAND [hid1]: grant [OK]
 
IO MONITOR EVENT: command.access = grant
 
IO MONITOR EVENT: hid1.state.relay = set
 
IO MONITOR FORCED: hid1.access.granted.manual = true
 
IO MONITOR EVENT: hid1.state.relay = unset
 
</pre>
 
 
 
After the button is pressed the relay is set. The manuale access granted is reported in the log.
 
 
 
Door forced. Here’s the HSYCO log:
 
<pre>
 
IO MONITOR FORCED: hid1.alarm.door.forced = 1
 
IO MONITOR EVENT: hid1.state.alarm.door.forced = set
 
IO MONITOR EVENT: hid1.state.relay.aux = set
 
IO MONITOR EVENT: hid1.state.relay.alert = set
 
</pre>
 
 
 
To grant an access using a user button, open the Project Editor and create a new user button. Specify the following parameters:
 
  
 +
=== 3.0.0 ===
 +
*initial release
  
 +
----
  
Name e param are used to call a spacific line in the events.txt file:
 
io hid1.state.relay = set : UISET hid1.color = g
 
io hid1.state.relay = unset : UISET hid1.color = gr
 
user hid1=grant : io hid1.command.access=grant
 
  
where hid1 is the id of the I/O server. The button color changes according to the relay state.
+
''HID is a registered trademark of HID Global.''

Latest revision as of 11:27, 24 October 2014

The HID Edge Solo ESR40, ESRP40, ES400 are single-door IP access control solutions.

This I/O Server allows the integration of HID Edge Solo devices by using a TCP/IP connection.

More than one device can be controlled at the same time.

HID Edge Solo Configuration

The HID Edge Solo can be connected to a POE switch or to a normal ethernet switch. In this case the power supply must be provided with an external adapter. First of all, assign a static IP address to the Edge Solo, then it’s mandatory to disable the SSL/TLS encryption in the installer settings interface.

Hidedgesolo1.png

HSYCO Configuration

Add an HIDEDGESOLO I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • IP Address: IP address configured on the device
  • IP Port: TCP/IP port to use, leave blank for default port 80.

Authentication

  • User: username set in the installer settings
  • Password: password set in the installer settings.

High Availability

  • Shutdown when inactive: defaults to true.

Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
card.notfound <code> R badge <code> not found
pin.notfound <pin> R <pin> not found
access.granted <surname> R access granted to the user with surname <surname>
access.granted.extended <surname> R access granted extended to the user with surname <surname>
access.denied.schedule <surname> R access denied because badge/pin of the user <surname> was used outside scheduled time interval
access.denied.expired <surname> R access denied because badge/pin of the user <surname> is expired
card.notassigned <code> R access denied because the badge <code> is not assigned to an user.
access.denied.pin.expired <surname> R access denied because the pin assigned to the user <surname> is expired
alarm.acknowledged 0 R alarms reset
1 R normal conditions
door.lock.schedule false R normal conditions
true R door locked with a scheduled command
door.unlock.schedule false R normal conditions
true R door unlocked with a scheduled command
alarm.door.forced unset R normal conditions
set R door forced alarm
alarm.tamper unset R normal conditions
set R tamper alarm
access.granted.manual false R normal conditions
true R manual access granted
door.unlock false R normal conditions
true R door unlocked
state.alarm.tamper unset R normal conditions
set R tamper alarm
state.alarm.ac unset R normal conditions
set R power supply failure
state.alarm.battery unset R normal conditions
set R battery failure
state.alarm.door.held unset R normal conditions
set R door held
state.alarm.door.held unset R normal conditions
set R door held
state.alarm.door.forced unset R normal conditions
set R door forced
state.name <name> R the door's name
state.relay unset R door relay closed
set R door relay open
state.relay.alert unset R alert relay not active
set R alert relay active
state.relay.aux unset R aux relay not active
set R aux relay active
command.access grant W grant the access
command.door lock W lock the door
unlock W unlock the door
command.alarm stop W alarms reset

Release Notes

3.4.0

  • added support for two readers door controller

3.0.0

  • initial release


HID is a registered trademark of HID Global.