Difference between revisions of "Ats"
| (23 intermediate revisions by 3 users not shown) | |||
| Line 1: | Line 1: | ||
| − | Aritech ATS panels are multi-area intrusion detection systems. The integration with HSYCO can be accomplished via direct control through the RS-232 port on the serial module. | + | Aritech ATS panels are multi-area intrusion detection systems. The integration with HSYCO can be accomplished via direct control through the RS-232 port on the serial module. The ATS I/O Server supports the integration of more than one unit within the same HSYCO interface. |
[[Category:I/O Server]] | [[Category:I/O Server]] | ||
| Line 6: | Line 6: | ||
Employ an RS-232 cable to connect the panel directly to HSYCO or to an Ethernet/RS-232 gateway. | Employ an RS-232 cable to connect the panel directly to HSYCO or to an Ethernet/RS-232 gateway. | ||
| + | |||
The cable must follow this pinout diagram: | The cable must follow this pinout diagram: | ||
| + | |||
[[File:Ats_RS232_cable.png|400px|border]] | [[File:Ats_RS232_cable.png|400px|border]] | ||
| + | |||
RS-232 parameters: | RS-232 parameters: | ||
| Line 28: | Line 31: | ||
|} | |} | ||
| + | == HSYCO Configuration == | ||
| + | Add an ATS I/O Server in the [[Settings#I/O Servers|I/O Servers section of the Settings]] and set its parameters: | ||
| + | |||
| + | === Communication === | ||
| + | *'''Comm ID''': select the comm port connected to the panel. | ||
| − | == | + | === High Availability === |
| + | *'''Shutdown when inactive''': defaults to true. | ||
=== Options === | === Options === | ||
| Line 58: | Line 67: | ||
|false | |false | ||
|start generating events only after HSYCO is aligned with the current status of the system | |start generating events only after HSYCO is aligned with the current status of the system | ||
| − | |||
|- | |- | ||
| Line 65: | Line 73: | ||
|n > 0 | |n > 0 | ||
|the data acquisition interval, in seconds | |the data acquisition interval, in seconds | ||
| − | |||
|- | |- | ||
| Line 72: | Line 79: | ||
|n ≥ 0 | |n ≥ 0 | ||
|the number of log lines to display in the UI object | |the number of log lines to display in the UI object | ||
| − | |||
|- | |- | ||
|maxzone | |maxzone | ||
|256 | |256 | ||
| − | |0 | + | |0 ... 256 |
|highest zone index set on the panel. This option is recommended to improve the I/O Server's performances | |highest zone index set on the panel. This option is recommended to improve the I/O Server's performances | ||
| − | |||
|- | |- | ||
|maxoutput | |maxoutput | ||
|256 | |256 | ||
| − | |0 | + | |0 ... 256 |
|highest output index set on the panel. This option is recommended to improve the I/O Server's performances | |highest output index set on the panel. This option is recommended to improve the I/O Server's performances | ||
| − | |||
|- | |- | ||
|maxras | |maxras | ||
|16 | |16 | ||
| − | |0 | + | |0 ... 16 |
|highest RAS (Remote Arming Station) index set on the panel. This option is recommended to improve the I/O Server's performances | |highest RAS (Remote Arming Station) index set on the panel. This option is recommended to improve the I/O Server's performances | ||
| − | + | |- | |
|} | |} | ||
| Line 99: | Line 103: | ||
The ats.ini file is a specific configuration file located in the root directory. | The ats.ini file is a specific configuration file located in the root directory. | ||
| − | Here you can define the names of zones and areas so that they will be automatically added to the user interface. Add a new line for each name using this format: | + | Here you can define the names of zones and areas so that they will be automatically added to the user interface. |
| + | |||
| + | Add a new line for each name using this format: | ||
<pre> | <pre> | ||
| Line 122: | Line 128: | ||
!Description | !Description | ||
| + | |- | ||
| + | |||
| + | |rowspan="2" |connection | ||
| + | |online | ||
| + | |R | ||
| + | |connection established | ||
| + | |- | ||
| + | |offline | ||
| + | |R | ||
| + | |HSYCO can't connect to the panel | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="4" |armed | ||
| + | |rowspan="2" |1 | ||
| + | |R | ||
| + | |at least one area is armed | ||
| + | |- | ||
| + | |W | ||
| + | |arm all active areas | ||
| + | |- | ||
| + | |rowspan="2" |0 | ||
| + | |R | ||
| + | |no area is armed | ||
| + | |- | ||
| + | |W | ||
| + | |disarm all active areas | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="3" |alarm | ||
| + | |1 | ||
| + | |R | ||
| + | |at least one area is in alarm | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |no area is in alarm | ||
| + | |- | ||
| + | |reset | ||
| + | |W | ||
| + | |reset system alarms | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |clock | ||
| + | |read | ||
| + | |W | ||
| + | |request the reading of the panel’s clock value | ||
| + | |- | ||
| + | |<date_time> | ||
| + | |R | ||
| + | |the panel’s clock is set to <date_time>. The value has the format "yyyy-mm-dd hh:mm:ss" (e.g. "2012-12-30 16:59:23"). | ||
| + | This event is only triggered after a request. | ||
| + | |||
| + | |- | ||
| + | |||
| + | |a<n>.name | ||
| + | |<text> | ||
| + | |R | ||
| + | |area <n> has been assigned the name <text> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |z<n>.name | ||
| + | |<text> | ||
| + | |R | ||
| + | |zone <n> has been assigned the name <text> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="5" |a<n>.armed | ||
| + | |rowspan="2" |1 | ||
| + | |R | ||
| + | |area <n> is armed | ||
| + | |- | ||
| + | |W | ||
| + | |arm area <n> | ||
| + | |- | ||
| + | |rowspan="2" |0 | ||
| + | |R | ||
| + | |area <n> is disarmed | ||
| + | |- | ||
| + | |W | ||
| + | |disarm area <n> | ||
| + | |- | ||
| + | |force | ||
| + | |W | ||
| + | |force arm area <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |a<n>.alarm | ||
| + | |1 | ||
| + | |R | ||
| + | |area <n> is in alarm | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |area <n> is not in alarm | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |a<n>.open | ||
| + | |1 | ||
| + | |R | ||
| + | |area <n> has open zones | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |area <n> has no open zones | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |a<n>.isolated | ||
| + | |1 | ||
| + | |R | ||
| + | |area <n> has isolated zones | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |area <n> has no isolated zones | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |a<n>.exit | ||
| + | |1 | ||
| + | |R | ||
| + | |exit time is active on area <n> | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |exit time is not active on area <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |a<n>.entry | ||
| + | |1 | ||
| + | |R | ||
| + | |entry time is active on area <n> | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |entry time is not active on area <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |a<n>.alarm.local | ||
| + | |1 | ||
| + | |R | ||
| + | |local alarms are active on area <n> | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |no local alarm is active on area <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |a<n>.warning | ||
| + | |1 | ||
| + | |R | ||
| + | |console warning is active on area <n> | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |console warning is not active on area <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="6" |z<n>.state1<sup>[[#note|[Note]]]</sup> | ||
| + | |tamper | ||
| + | |R | ||
| + | |tamper active on zone <n> | ||
| + | |- | ||
| + | |alarm | ||
| + | |R | ||
| + | |alarm active on zone <n> | ||
| + | |- | ||
| + | |closed | ||
| + | |R | ||
| + | |zone <n> closed | ||
| + | |- | ||
| + | |night | ||
| + | |R | ||
| + | |night holdup active on zone <n> | ||
| + | |- | ||
| + | |local | ||
| + | |R | ||
| + | |local alarm active on zone <n> | ||
| + | |- | ||
| + | |isolated | ||
| + | |R | ||
| + | |zone <n> isolated | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="5" |z<n>.state2<sup>[[#note|[Note]]]</sup> | ||
| + | |short | ||
| + | |R | ||
| + | |zone <n> in short circuit | ||
| + | |- | ||
| + | |open | ||
| + | |R | ||
| + | |zone <n> open | ||
| + | |- | ||
| + | |closed | ||
| + | |R | ||
| + | |zone <n> closed | ||
| + | |- | ||
| + | |active | ||
| + | |R | ||
| + | |zone <n> active | ||
| + | |- | ||
| + | |masked | ||
| + | |R | ||
| + | |zone <n> masked | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |z<n>.isolated | ||
| + | |1 | ||
| + | |W | ||
| + | |isolate zone <n> | ||
| + | |- | ||
| + | |0 | ||
| + | |W | ||
| + | |de-isolate zone <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |z<n>.alarm | ||
| + | |reset | ||
| + | |W | ||
| + | |reset alarms on zone <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="4" |o<n>.active | ||
| + | |rowspan="2" |1 | ||
| + | |R | ||
| + | |output <n> is active | ||
| + | |- | ||
| + | |W | ||
| + | |activate output <n> | ||
| + | |- | ||
| + | |rowspan="2" |0 | ||
| + | |R | ||
| + | |output <n> is not active | ||
| + | |- | ||
| + | |W | ||
| + | |deactivate output <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |o<n>.inverted | ||
| + | |1 | ||
| + | |R | ||
| + | |output <n> is inverted | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |output <n> is not inverted | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |ras<n>.offline | ||
| + | |1 | ||
| + | |R | ||
| + | |RAS <n> is offline | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |RAS <n> is online | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |ras<n>.tamper | ||
| + | |1 | ||
| + | |R | ||
| + | |RAS <n> is tampered | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |RAS <n> is not tampered | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |ras<n>.isolated | ||
| + | |1 | ||
| + | |R | ||
| + | |RAS <n> is isolated | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |RAS <n> is not isolated | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |ras<n>.inhibited | ||
| + | |1 | ||
| + | |R | ||
| + | |RAS <n> is inhibited | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |RAS <n> is not inhibited | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |dgp<n>.offline | ||
| + | |1 | ||
| + | |R | ||
| + | |DGP <n> is offline | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |DGP <n> is online | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |dgp<n>.isolated | ||
| + | |1 | ||
| + | |R | ||
| + | |DGP <n> is isolated | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |DGP <n> is not isolated | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |dgp<n>.inhibited | ||
| + | |1 | ||
| + | |R | ||
| + | |DGP <n> is inhibited | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |DGP <n> is not inhibited | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |dgp<n>.battery.missing | ||
| + | |1 | ||
| + | |R | ||
| + | |battery missing on DGP <n> | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |battery ok on DGP <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |dgp<n>.battery.low | ||
| + | |1 | ||
| + | |R | ||
| + | |battery low on DGP <n> | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |battery ok on DGP <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |dgp<n>.battery.test | ||
| + | |1 | ||
| + | |R | ||
| + | |battery test active on DGP <n> | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |no battery test active on DGP <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |dgp<n>.battery.test.fail | ||
| + | |1 | ||
| + | |R | ||
| + | |battery test failed on DGP <n> | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |battery test ok on DGP <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |dgp<n>.mains.fail | ||
| + | |1 | ||
| + | |R | ||
| + | |mains failure on DGP <n> | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |mains ok on DGP <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |dgp<n>.fuse.fail | ||
| + | |1 | ||
| + | |R | ||
| + | |fuse failure on DGP <n> | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |fuses ok on DGP <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |dgp<n>.siren.fail | ||
| + | |1 | ||
| + | |R | ||
| + | |siren failure on DGP <n> | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |siren ok on DGP <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |dgp<n>.tamper | ||
| + | |1 | ||
| + | |R | ||
| + | |DGP <n> is tampered | ||
| + | |- | ||
| + | |0 | ||
| + | |R | ||
| + | |DGP <n> is not tampered | ||
| + | |} | ||
| + | |||
| + | <span id="note"> | ||
| + | ;Note: The value of a zone status (datapoints z<n>.state1 and z<n>.state2) depends on the configuration of the zone typology. | ||
| + | </span> | ||
| + | |||
| + | == User Interface == | ||
| + | |||
| + | === Ats Object === | ||
| + | |||
| + | {{:Ats_(UI Object)}} | ||
| + | |||
| + | === UISET Actions === | ||
| + | |||
| + | {| class="wikitable" | ||
| + | !ID | ||
| + | !Attribute | ||
| + | !colspan="2"|Set to | ||
| + | |- | ||
| + | |||
| + | |log<n> | ||
| + | |value | ||
| + | |the line <n> of the log list (<n> from 1 to 20, <n> = 1 : latest entry) | ||
| + | |- | ||
| + | |||
| + | |log0 | ||
| + | |value | ||
| + | |the latest line of the log for a short period | ||
| + | |- | ||
| + | |||
| + | |a<n>.name | ||
| + | |value | ||
| + | |the name assigned to area <n> | ||
| + | |- | ||
| + | |||
| + | |z<n>.name | ||
| + | |value | ||
| + | |the name assigned to zone <n> | ||
| + | |- | ||
| + | |||
| + | |connection.label | ||
| + | |visible | ||
| + | |true when the system is not connected to HSYCO, false otherwise | ||
| + | |- | ||
| + | |||
| + | |armed.label.1 | ||
| + | |visible | ||
| + | |true when at least one area is armed, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |armed.label.0 | ||
| + | |visible | ||
| + | |true when no area is armed, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |alarm.label.1 | ||
| + | |visible | ||
| + | |true when at least one area is in alarm, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |alarm.label.0 | ||
| + | |visible | ||
| + | |true when no area is in alarm, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |a<n>.armed.label.1 | ||
| + | |visible | ||
| + | |true when area <n> is armed, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |a<n>.armed.label.0 | ||
| + | |visible | ||
| + | |true when area <n> is not armed, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |a<n>.alarm.label.1 | ||
| + | |visible | ||
| + | |true when area <n> is in alarm, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |a<n>.alarm.label.0 | ||
| + | |visible | ||
| + | |true when area <n> is not in alarm, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |a<n>.open.label.1 | ||
| + | |visible | ||
| + | |true when area <n> has open zones, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |a<n>.open.label.0 | ||
| + | |visible | ||
| + | |true when area <n> has no open zone, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |a<n>.isolated.label.1 | ||
| + | |visible | ||
| + | |true when area <n> has isolated zones, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |a<n>.isolated.label.0 | ||
| + | |visible | ||
| + | |true when area <n> has no isolated zone, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |a<n>.exit.label.1 | ||
| + | |visible | ||
| + | |true when the exit time is active on area <n>, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |a<n>.exit.label.0 | ||
| + | |visible | ||
| + | |true when the exit time is not active on area <n>, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |a<n>.entry.label.1 | ||
| + | |visible | ||
| + | |true when the entry time is active on area <n>, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |a<n>.entry.label.0 | ||
| + | |visible | ||
| + | |true when the entry time is not active on area <n>, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |a<n>.alarm.local.label.1 | ||
| + | |visible | ||
| + | |true when local alarms are active on area <n>, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |a<n>.alarm.local.label.0 | ||
| + | |visible | ||
| + | |true when no local alarm is active on area <n>, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |a<n>.warning.label.1 | ||
| + | |visible | ||
| + | |true when the console warning is active on area <n>, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |a<n>.warning.label.0 | ||
| + | |visible | ||
| + | |true when the console warning is not active on area <n>, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |o<n>.active.label.1 | ||
| + | |visible | ||
| + | |true when output <n> is active, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |o<n>.active.label.0 | ||
| + | |visible | ||
| + | |true when output <n> is inactive, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |o<n>.inverted.label.1 | ||
| + | |visible | ||
| + | |true if output <n> is inverted, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |o<n>.inverted.label.0 | ||
| + | |visible | ||
| + | |true if output <n> is not inverted, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |ras<n>.offline.label.1 | ||
| + | |visible | ||
| + | |true if RAS <n> is offline, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |ras<n>.offline.label.0 | ||
| + | |visible | ||
| + | |true if RAS <n> is online, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |ras<n>.tamper.label.1 | ||
| + | |visible | ||
| + | |true when RAS <n> is tampered, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |ras<n>.tamper.label.0 | ||
| + | |visible | ||
| + | |true when RAS <n> is not tampered, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |ras<n>.isolated.label.1 | ||
| + | |visible | ||
| + | |true if RAS <n> is isolated, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |ras<n>.isolated.label.0 | ||
| + | |visible | ||
| + | |true if RAS <n> is not isolated, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |ras<n>.inhibited.label.1 | ||
| + | |visible | ||
| + | |true if RAS <n> is inhibited, not visible otherwise | ||
| + | |- | ||
| + | |ras<n>.inhibited.label.0 | ||
| + | |visible | ||
| + | |true if RAS <n> is not inhibited, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.offline.label.1 | ||
| + | |visible | ||
| + | |true if DGP <n> is offline, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.offline.label.0 | ||
| + | |visible | ||
| + | |true if DGP <n> is online, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.isolated.label.1 | ||
| + | |visible | ||
| + | |true if DGP <n> is isolated, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.isolated.label.0 | ||
| + | |visible | ||
| + | |true if DGP <n> is not isolated, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.inhibited.label.1 | ||
| + | |visible | ||
| + | |true if DGP <n> is inhibited, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.inhibited.label.0 | ||
| + | |visible | ||
| + | |true if DGP <n> is not inhibited, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.battery.missing.label.1 | ||
| + | |visible | ||
| + | |true if the battery of DGP <n> is missing, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.battery.missing.label.0 | ||
| + | |visible | ||
| + | |true if the battery of DGP <n> is ok, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.battery.test.label.1 | ||
| + | |visible | ||
| + | |true if the battery test is active on DGP <n>, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.battery.test.label.0 | ||
| + | |visible | ||
| + | |true if the battery test is not active on DGP <n>, not visible otherwise | ||
| + | |- | ||
| + | |dgp<n>.battery.low.label.1 | ||
| + | |visible | ||
| + | |true if the battery of DGP <n> is low, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.battery.low.label.0 | ||
| + | |visible | ||
| + | |true if the battery of DGP <n> is ok, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.mains.fail.label.1 | ||
| + | |visible | ||
| + | |true if a mains failure is active on DGP <n>, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.mains.fail.label.0 | ||
| + | |visible | ||
| + | |true if no mains failure is active on DGP <n>, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.battery.test.fail.label.1 | ||
| + | |visible | ||
| + | |true if the battery test failed on DGP <n>, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.battery.test.fail.label.0 | ||
| + | |visible | ||
| + | |true if the battery test succeeded on DGP <n>, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.fuse.fail.label.1 | ||
| + | |visible | ||
| + | |true if a fuse failed on DGP <n>, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.fuse.fail.label.0 | ||
| + | |visible | ||
| + | |true if no fuse failed on DGP <n>, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.siren.fail.label.1 | ||
| + | |visible | ||
| + | |true if a siren failed on DGP <n>, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.siren.fail.label.0 | ||
| + | |visible | ||
| + | |true if no siren failed on DGP <n>, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.tamper.label.1 | ||
| + | |visible | ||
| + | |true when DGP <n> is tampered, not visible otherwise | ||
| + | |- | ||
| + | |||
| + | |dgp<n>.tamper.label.0 | ||
| + | |visible | ||
| + | |true when DGP <n> is not tampered, not visible otherwise | ||
| + | |- | ||
| + | |} | ||
| + | |||
| + | === USER Commands === | ||
| + | |||
| + | {| class="wikitable" | ||
| + | !Name | ||
| + | !Param | ||
| + | !Action | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |armed | ||
| + | |1 | ||
| + | |arm all active areas | ||
| + | |- | ||
| + | |0 | ||
| + | |disarm all active areas | ||
| + | |||
| + | |- | ||
| + | |||
| + | |alarm | ||
| + | |reset | ||
| + | |reset system alarms | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="3" |a<n>.armed | ||
| + | |1 | ||
| + | |arm area <n> | ||
| + | |- | ||
| + | |0 | ||
| + | |disarm area <n> | ||
| + | |- | ||
| + | |force | ||
| + | |force arm area <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |z<n>.isolated | ||
| + | |1 | ||
| + | |isolate zone <n> | ||
| + | |- | ||
| + | |0 | ||
| + | |de-isolate zone <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |z<n>.alarm | ||
| + | |reset | ||
| + | |reset alarms on zone <n> | ||
| + | |||
| + | |- | ||
| + | |||
| + | |rowspan="2" |o<n>.active | ||
| + | |1 | ||
| + | |activate output <n> | ||
| + | |- | ||
| + | |0 | ||
| + | |deactivate output <n> | ||
|} | |} | ||
| + | |||
| + | == Release Notes == | ||
| + | === 3.4.0 === | ||
| + | *bug fix: polling failure occurring for a high number of zones | ||
| + | |||
| + | === 3.2.0 === | ||
| + | *added event “ID.clock” | ||
| + | *removed I/O Server option “maxdgp” | ||
| + | |||
| + | === 3.1.0 === | ||
| + | *initial release | ||
| + | |||
| + | ---- | ||
| + | |||
| + | |||
| + | ''ATS and Aritech are registered trademarks of UTC Fire & Security.'' | ||
Latest revision as of 12:29, 24 October 2014
Aritech ATS panels are multi-area intrusion detection systems. The integration with HSYCO can be accomplished via direct control through the RS-232 port on the serial module. The ATS I/O Server supports the integration of more than one unit within the same HSYCO interface.
Contents
Communication
Employ an RS-232 cable to connect the panel directly to HSYCO or to an Ethernet/RS-232 gateway.
The cable must follow this pinout diagram:
RS-232 parameters:
| Baud rate | same as panel settings (default 4800) |
| Data bits | 8 |
| Stop bit | 1 |
| Parity | none |
| Flow control | RTS/CTS |
HSYCO Configuration
Add an ATS I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- Comm ID: select the comm port connected to the panel.
High Availability
- Shutdown when inactive: defaults to true.
Options
| ID | Default | Values | Description |
|---|---|---|---|
| gui | true | true | enable support for the UI object, UISET actions and USER commands |
| false | disable UI support | ||
| startupevents | false | true | generate IO events also during the driver’s start-up phase |
| false | start generating events only after HSYCO is aligned with the current status of the system | ||
| pollinterval | 5 | n > 0 | the data acquisition interval, in seconds |
| logsize | 20 | n ≥ 0 | the number of log lines to display in the UI object |
| maxzone | 256 | 0 ... 256 | highest zone index set on the panel. This option is recommended to improve the I/O Server's performances |
| maxoutput | 256 | 0 ... 256 | highest output index set on the panel. This option is recommended to improve the I/O Server's performances |
| maxras | 16 | 0 ... 16 | highest RAS (Remote Arming Station) index set on the panel. This option is recommended to improve the I/O Server's performances |
ats.ini
The ats.ini file is a specific configuration file located in the root directory. Here you can define the names of zones and areas so that they will be automatically added to the user interface.
Add a new line for each name using this format:
<io_server_id>.zone.<n> = <name> <io_server_id>.area.<n> = <name>
For instance:
ats.zone.1 = Kitchen ats.zone.2 = Corridor ats.area.1 = Floor 1
Datapoints
| ID | Value | R/W | Description |
|---|---|---|---|
| connection | online | R | connection established |
| offline | R | HSYCO can't connect to the panel | |
| armed | 1 | R | at least one area is armed |
| W | arm all active areas | ||
| 0 | R | no area is armed | |
| W | disarm all active areas | ||
| alarm | 1 | R | at least one area is in alarm |
| 0 | R | no area is in alarm | |
| reset | W | reset system alarms | |
| clock | read | W | request the reading of the panel’s clock value |
| <date_time> | R | the panel’s clock is set to <date_time>. The value has the format "yyyy-mm-dd hh:mm:ss" (e.g. "2012-12-30 16:59:23").
This event is only triggered after a request. | |
| a<n>.name | <text> | R | area <n> has been assigned the name <text> |
| z<n>.name | <text> | R | zone <n> has been assigned the name <text> |
| a<n>.armed | 1 | R | area <n> is armed |
| W | arm area <n> | ||
| 0 | R | area <n> is disarmed | |
| W | disarm area <n> | ||
| force | W | force arm area <n> | |
| a<n>.alarm | 1 | R | area <n> is in alarm |
| 0 | R | area <n> is not in alarm | |
| a<n>.open | 1 | R | area <n> has open zones |
| 0 | R | area <n> has no open zones | |
| a<n>.isolated | 1 | R | area <n> has isolated zones |
| 0 | R | area <n> has no isolated zones | |
| a<n>.exit | 1 | R | exit time is active on area <n> |
| 0 | R | exit time is not active on area <n> | |
| a<n>.entry | 1 | R | entry time is active on area <n> |
| 0 | R | entry time is not active on area <n> | |
| a<n>.alarm.local | 1 | R | local alarms are active on area <n> |
| 0 | R | no local alarm is active on area <n> | |
| a<n>.warning | 1 | R | console warning is active on area <n> |
| 0 | R | console warning is not active on area <n> | |
| z<n>.state1[Note] | tamper | R | tamper active on zone <n> |
| alarm | R | alarm active on zone <n> | |
| closed | R | zone <n> closed | |
| night | R | night holdup active on zone <n> | |
| local | R | local alarm active on zone <n> | |
| isolated | R | zone <n> isolated | |
| z<n>.state2[Note] | short | R | zone <n> in short circuit |
| open | R | zone <n> open | |
| closed | R | zone <n> closed | |
| active | R | zone <n> active | |
| masked | R | zone <n> masked | |
| z<n>.isolated | 1 | W | isolate zone <n> |
| 0 | W | de-isolate zone <n> | |
| z<n>.alarm | reset | W | reset alarms on zone <n> |
| o<n>.active | 1 | R | output <n> is active |
| W | activate output <n> | ||
| 0 | R | output <n> is not active | |
| W | deactivate output <n> | ||
| o<n>.inverted | 1 | R | output <n> is inverted |
| 0 | R | output <n> is not inverted | |
| ras<n>.offline | 1 | R | RAS <n> is offline |
| 0 | R | RAS <n> is online | |
| ras<n>.tamper | 1 | R | RAS <n> is tampered |
| 0 | R | RAS <n> is not tampered | |
| ras<n>.isolated | 1 | R | RAS <n> is isolated |
| 0 | R | RAS <n> is not isolated | |
| ras<n>.inhibited | 1 | R | RAS <n> is inhibited |
| 0 | R | RAS <n> is not inhibited | |
| dgp<n>.offline | 1 | R | DGP <n> is offline |
| 0 | R | DGP <n> is online | |
| dgp<n>.isolated | 1 | R | DGP <n> is isolated |
| 0 | R | DGP <n> is not isolated | |
| dgp<n>.inhibited | 1 | R | DGP <n> is inhibited |
| 0 | R | DGP <n> is not inhibited | |
| dgp<n>.battery.missing | 1 | R | battery missing on DGP <n> |
| 0 | R | battery ok on DGP <n> | |
| dgp<n>.battery.low | 1 | R | battery low on DGP <n> |
| 0 | R | battery ok on DGP <n> | |
| dgp<n>.battery.test | 1 | R | battery test active on DGP <n> |
| 0 | R | no battery test active on DGP <n> | |
| dgp<n>.battery.test.fail | 1 | R | battery test failed on DGP <n> |
| 0 | R | battery test ok on DGP <n> | |
| dgp<n>.mains.fail | 1 | R | mains failure on DGP <n> |
| 0 | R | mains ok on DGP <n> | |
| dgp<n>.fuse.fail | 1 | R | fuse failure on DGP <n> |
| 0 | R | fuses ok on DGP <n> | |
| dgp<n>.siren.fail | 1 | R | siren failure on DGP <n> |
| 0 | R | siren ok on DGP <n> | |
| dgp<n>.tamper | 1 | R | DGP <n> is tampered |
| 0 | R | DGP <n> is not tampered |
- Note
- The value of a zone status (datapoints z<n>.state1 and z<n>.state2) depends on the configuration of the zone typology.
User Interface
Ats Object
The user interface for the Aritech ATS multi-area intrusion detection system:
The Ats object is listed in the Project Editor’s new object list only when at least one Aritech ATS I/O Server is defined.
Parameters
- server id: the server ID
- position: the object's position. Use the pixels or rows and columns coordinates format
Syntax
(ats <server id>; <position>)
E.g.
(ats serverid; x10y20)
UISET Actions
| ID | Attribute | Set to | |
|---|---|---|---|
| log<n> | value | the line <n> of the log list (<n> from 1 to 20, <n> = 1 : latest entry) | |
| log0 | value | the latest line of the log for a short period | |
| a<n>.name | value | the name assigned to area <n> | |
| z<n>.name | value | the name assigned to zone <n> | |
| connection.label | visible | true when the system is not connected to HSYCO, false otherwise | |
| armed.label.1 | visible | true when at least one area is armed, not visible otherwise | |
| armed.label.0 | visible | true when no area is armed, not visible otherwise | |
| alarm.label.1 | visible | true when at least one area is in alarm, not visible otherwise | |
| alarm.label.0 | visible | true when no area is in alarm, not visible otherwise | |
| a<n>.armed.label.1 | visible | true when area <n> is armed, not visible otherwise | |
| a<n>.armed.label.0 | visible | true when area <n> is not armed, not visible otherwise | |
| a<n>.alarm.label.1 | visible | true when area <n> is in alarm, not visible otherwise | |
| a<n>.alarm.label.0 | visible | true when area <n> is not in alarm, not visible otherwise | |
| a<n>.open.label.1 | visible | true when area <n> has open zones, not visible otherwise | |
| a<n>.open.label.0 | visible | true when area <n> has no open zone, not visible otherwise | |
| a<n>.isolated.label.1 | visible | true when area <n> has isolated zones, not visible otherwise | |
| a<n>.isolated.label.0 | visible | true when area <n> has no isolated zone, not visible otherwise | |
| a<n>.exit.label.1 | visible | true when the exit time is active on area <n>, not visible otherwise | |
| a<n>.exit.label.0 | visible | true when the exit time is not active on area <n>, not visible otherwise | |
| a<n>.entry.label.1 | visible | true when the entry time is active on area <n>, not visible otherwise | |
| a<n>.entry.label.0 | visible | true when the entry time is not active on area <n>, not visible otherwise | |
| a<n>.alarm.local.label.1 | visible | true when local alarms are active on area <n>, not visible otherwise | |
| a<n>.alarm.local.label.0 | visible | true when no local alarm is active on area <n>, not visible otherwise | |
| a<n>.warning.label.1 | visible | true when the console warning is active on area <n>, not visible otherwise | |
| a<n>.warning.label.0 | visible | true when the console warning is not active on area <n>, not visible otherwise | |
| o<n>.active.label.1 | visible | true when output <n> is active, not visible otherwise | |
| o<n>.active.label.0 | visible | true when output <n> is inactive, not visible otherwise | |
| o<n>.inverted.label.1 | visible | true if output <n> is inverted, not visible otherwise | |
| o<n>.inverted.label.0 | visible | true if output <n> is not inverted, not visible otherwise | |
| ras<n>.offline.label.1 | visible | true if RAS <n> is offline, not visible otherwise | |
| ras<n>.offline.label.0 | visible | true if RAS <n> is online, not visible otherwise | |
| ras<n>.tamper.label.1 | visible | true when RAS <n> is tampered, not visible otherwise | |
| ras<n>.tamper.label.0 | visible | true when RAS <n> is not tampered, not visible otherwise | |
| ras<n>.isolated.label.1 | visible | true if RAS <n> is isolated, not visible otherwise | |
| ras<n>.isolated.label.0 | visible | true if RAS <n> is not isolated, not visible otherwise | |
| ras<n>.inhibited.label.1 | visible | true if RAS <n> is inhibited, not visible otherwise | |
| ras<n>.inhibited.label.0 | visible | true if RAS <n> is not inhibited, not visible otherwise | |
| dgp<n>.offline.label.1 | visible | true if DGP <n> is offline, not visible otherwise | |
| dgp<n>.offline.label.0 | visible | true if DGP <n> is online, not visible otherwise | |
| dgp<n>.isolated.label.1 | visible | true if DGP <n> is isolated, not visible otherwise | |
| dgp<n>.isolated.label.0 | visible | true if DGP <n> is not isolated, not visible otherwise | |
| dgp<n>.inhibited.label.1 | visible | true if DGP <n> is inhibited, not visible otherwise | |
| dgp<n>.inhibited.label.0 | visible | true if DGP <n> is not inhibited, not visible otherwise | |
| dgp<n>.battery.missing.label.1 | visible | true if the battery of DGP <n> is missing, not visible otherwise | |
| dgp<n>.battery.missing.label.0 | visible | true if the battery of DGP <n> is ok, not visible otherwise | |
| dgp<n>.battery.test.label.1 | visible | true if the battery test is active on DGP <n>, not visible otherwise | |
| dgp<n>.battery.test.label.0 | visible | true if the battery test is not active on DGP <n>, not visible otherwise | |
| dgp<n>.battery.low.label.1 | visible | true if the battery of DGP <n> is low, not visible otherwise | |
| dgp<n>.battery.low.label.0 | visible | true if the battery of DGP <n> is ok, not visible otherwise | |
| dgp<n>.mains.fail.label.1 | visible | true if a mains failure is active on DGP <n>, not visible otherwise | |
| dgp<n>.mains.fail.label.0 | visible | true if no mains failure is active on DGP <n>, not visible otherwise | |
| dgp<n>.battery.test.fail.label.1 | visible | true if the battery test failed on DGP <n>, not visible otherwise | |
| dgp<n>.battery.test.fail.label.0 | visible | true if the battery test succeeded on DGP <n>, not visible otherwise | |
| dgp<n>.fuse.fail.label.1 | visible | true if a fuse failed on DGP <n>, not visible otherwise | |
| dgp<n>.fuse.fail.label.0 | visible | true if no fuse failed on DGP <n>, not visible otherwise | |
| dgp<n>.siren.fail.label.1 | visible | true if a siren failed on DGP <n>, not visible otherwise | |
| dgp<n>.siren.fail.label.0 | visible | true if no siren failed on DGP <n>, not visible otherwise | |
| dgp<n>.tamper.label.1 | visible | true when DGP <n> is tampered, not visible otherwise | |
| dgp<n>.tamper.label.0 | visible | true when DGP <n> is not tampered, not visible otherwise | |
USER Commands
| Name | Param | Action |
|---|---|---|
| armed | 1 | arm all active areas |
| 0 | disarm all active areas | |
| alarm | reset | reset system alarms |
| a<n>.armed | 1 | arm area <n> |
| 0 | disarm area <n> | |
| force | force arm area <n> | |
| z<n>.isolated | 1 | isolate zone <n> |
| 0 | de-isolate zone <n> | |
| z<n>.alarm | reset | reset alarms on zone <n> |
| o<n>.active | 1 | activate output <n> |
| 0 | deactivate output <n> |
Release Notes
3.4.0
- bug fix: polling failure occurring for a high number of zones
3.2.0
- added event “ID.clock”
- removed I/O Server option “maxdgp”
3.1.0
- initial release
ATS and Aritech are registered trademarks of UTC Fire & Security.