Revision as of 12:40, 7 January 2014
Airzone is a control framework for ducted air conditioning systems which allows for the control of several zones independently. This I/O server provides support for this Airzone systems: INNOBUS, FLEXA, ANTREE and CEN.
Communication
Airzone communicates with HSYCO through a modbus connection employing a RS-485 gateway.
RS-485 parameters:
| Baud rate | 19200 |
| Data bits | 8 |
| Stop bit | 1 |
| Parity | even |
| Flow control | none |
HSYCO Configuration
Options
| ID | Default | Values | Description |
|---|---|---|---|
| gui | true | true | enable support for the UI object, UISET actions and USER commands |
| false | disable UI support | ||
| startupevents | false | true | generate IO events also during the driver’s start-up phase |
| false | start generating events only after HSYCO is aligned with the current status of the system | ||
| pollinterval | 20 | n > 0 | the data acquisition interval, in seconds |
| version | 1 | 1 | use protocol version 1 |
| 2 | use protocol version 2 |
Datapoints
| ID | Value | R/W | Description |
|---|---|---|---|
| connection | online | R | connection established |
| offline | R | HSYCO can't connect to the panel |