Difference between revisions of "Hidedgesolo"

From HSYCO
Jump to navigation Jump to search
 
(9 intermediate revisions by 2 users not shown)
Line 1: Line 1:
The [http://www.hidglobal.com HID Edge Solo] '''ESR40, ESRP40, ES400''' are single-door IP access control solution.  
+
The [http://www.hidglobal.com HID Edge Solo] '''ESR40, ESRP40, ES400''' are single-door IP access control solutions.  
  
 
This I/O Server allows the integration of HID Edge Solo devices by using a TCP/IP connection.  
 
This I/O Server allows the integration of HID Edge Solo devices by using a TCP/IP connection.  
Line 10: Line 10:
  
 
The HID Edge Solo can be connected to a POE switch or to a normal ethernet switch. In this case the power supply must be provided with an external adapter.
 
The HID Edge Solo can be connected to a POE switch or to a normal ethernet switch. In this case the power supply must be provided with an external adapter.
First of all, assign an IP address to the Edge Solo, then it’s mandatory to disable the SSL/TLS encryption in the installer settings interface.
+
First of all, assign a static IP address to the Edge Solo, then it’s mandatory to disable the SSL/TLS encryption in the installer settings interface.
  
 
[[File:hidedgesolo1.png]]
 
[[File:hidedgesolo1.png]]
 +
 +
== HSYCO Configuration ==
 +
Add an HIDEDGESOLO I/O Server in the [[Settings#I/O Servers|I/O Servers section of the Settings]] and set its parameters:
 +
 +
=== Communication ===
 +
*'''IP Address''': IP address configured on the device
 +
*'''IP Port''': TCP/IP port to use, leave blank for default port 80.
 +
 +
=== Authentication ===
 +
*'''User''': username set in the installer settings
 +
*'''Password''': password set in the installer settings.
 +
 +
=== High Availability ===
 +
*'''Shutdown when inactive''': defaults to true.
  
 
== Datapoints ==
 
== Datapoints ==
Line 189: Line 203:
 
|R
 
|R
 
|door forced
 
|door forced
 +
|-
 +
|state.name
 +
|<name>
 +
|R
 +
|the door's name
 
|-
 
|-
 
|rowspan="2" |state.relay
 
|rowspan="2" |state.relay
Line 198: Line 217:
 
|R
 
|R
 
|door relay open
 
|door relay open
 +
|-
 +
|rowspan="2" |state.relay.alert
 +
|unset
 +
|R
 +
|alert relay not active
 +
|-
 +
|set
 +
|R
 +
|alert relay active
 
|-
 
|-
 
|rowspan="2" |state.relay.aux
 
|rowspan="2" |state.relay.aux
 
|unset
 
|unset
 
|R
 
|R
|the device is not in alarm state
+
|aux relay not active
 
|-
 
|-
 
|set
 
|set
 
|R
 
|R
|the device is in alarm state
+
|aux relay active
 
|-
 
|-
 
|command.access
 
|command.access
Line 229: Line 257:
  
 
== Release Notes ==
 
== Release Notes ==
 +
=== 3.4.0 ===
 +
*added support for two readers door controller
 +
 
=== 3.0.0 ===
 
=== 3.0.0 ===
 
*initial release
 
*initial release

Latest revision as of 11:27, 24 October 2014

The HID Edge Solo ESR40, ESRP40, ES400 are single-door IP access control solutions.

This I/O Server allows the integration of HID Edge Solo devices by using a TCP/IP connection.

More than one device can be controlled at the same time.

HID Edge Solo Configuration

The HID Edge Solo can be connected to a POE switch or to a normal ethernet switch. In this case the power supply must be provided with an external adapter. First of all, assign a static IP address to the Edge Solo, then it’s mandatory to disable the SSL/TLS encryption in the installer settings interface.

Hidedgesolo1.png

HSYCO Configuration

Add an HIDEDGESOLO I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • IP Address: IP address configured on the device
  • IP Port: TCP/IP port to use, leave blank for default port 80.

Authentication

  • User: username set in the installer settings
  • Password: password set in the installer settings.

High Availability

  • Shutdown when inactive: defaults to true.

Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
card.notfound <code> R badge <code> not found
pin.notfound <pin> R <pin> not found
access.granted <surname> R access granted to the user with surname <surname>
access.granted.extended <surname> R access granted extended to the user with surname <surname>
access.denied.schedule <surname> R access denied because badge/pin of the user <surname> was used outside scheduled time interval
access.denied.expired <surname> R access denied because badge/pin of the user <surname> is expired
card.notassigned <code> R access denied because the badge <code> is not assigned to an user.
access.denied.pin.expired <surname> R access denied because the pin assigned to the user <surname> is expired
alarm.acknowledged 0 R alarms reset
1 R normal conditions
door.lock.schedule false R normal conditions
true R door locked with a scheduled command
door.unlock.schedule false R normal conditions
true R door unlocked with a scheduled command
alarm.door.forced unset R normal conditions
set R door forced alarm
alarm.tamper unset R normal conditions
set R tamper alarm
access.granted.manual false R normal conditions
true R manual access granted
door.unlock false R normal conditions
true R door unlocked
state.alarm.tamper unset R normal conditions
set R tamper alarm
state.alarm.ac unset R normal conditions
set R power supply failure
state.alarm.battery unset R normal conditions
set R battery failure
state.alarm.door.held unset R normal conditions
set R door held
state.alarm.door.held unset R normal conditions
set R door held
state.alarm.door.forced unset R normal conditions
set R door forced
state.name <name> R the door's name
state.relay unset R door relay closed
set R door relay open
state.relay.alert unset R alert relay not active
set R alert relay active
state.relay.aux unset R aux relay not active
set R aux relay active
command.access grant W grant the access
command.door lock W lock the door
unlock W unlock the door
command.alarm stop W alarms reset

Release Notes

3.4.0

  • added support for two readers door controller

3.0.0

  • initial release


HID is a registered trademark of HID Global.