Difference between revisions of "Dummy"
Line 64: | Line 64: | ||
|0 | |0 | ||
|>= 0 | |>= 0 | ||
− | |if > 0, the connection datapoint is set to "offline" if no httpcall request is received for more than the set value, and reset to "online" after a valid httpcall request.<br>Otherwise the connection datapoint is set to "online" when the I/O Server is started | + | |if > 0, the connection datapoint is set to "offline" if no httpcall request is received for more than the set value, and reset to "online" after a valid httpcall request.<br>Otherwise the connection datapoint is set to "online" when the I/O Server is started |
|} | |} |
Revision as of 16:41, 17 April 2019
The DUMMY I/O Server is a virtual server that doesn’t actually connect to any external system, but simulates basic lighting and automation devices, and general purpose virtual data points.
Data points can also be remotely set or read using a simple HTTP API, based on the /x/httpcall interface.
Contents
HSYCO Configuration
Add a DUMMY I/O Server in the I/O Servers section of the Settings and set its parameters.
High Availability
- Shutdown when inactive: defaults to false.
Options
ID | Default | Values | Description |
---|---|---|---|
discovery | true | true | automatically lists all virtual devices in the systemtopo.txt file |
false | auto-detect for devices is disabled | ||
lights | 10 | 0 ... 10000 | number of on/off light devices to generate |
dimmers | 10 | 0 ... 10000 | number of dimmer devices to generate |
automations | 10 | 0 ... 10000 | number of automation devices to generate |
httpcallpassword | string of 8 or more uppercase or lowercase letters and digits | enables the HTTP API | |
httpcalltimeoutseconds | 0 | >= 0 | if > 0, the connection datapoint is set to "offline" if no httpcall request is received for more than the set value, and reset to "online" after a valid httpcall request. Otherwise the connection datapoint is set to "online" when the I/O Server is started |
The Device Configuration Database
The systemtopo.txt file contains the list of all virtual devices that should be directly associated to graphic objects in the Web-based user interface.
This file can be filled manually or automatically by HSYCO at start-up. To enable automatic discovery and automatic generation of devices’ information in the systemtopo.txt file, use the discovery option in Settings.
This is an example of an automatically generated systemtopo.txt file:
(devices) dummy.autom.1 : AUTOM ; VSHUT ; DUMMY dummy.autom.2 : AUTOM ; VSHUT ; DUMMY dummy.autom.3 : AUTOM ; VSHUT ; DUMMY dummy.autom.4 : AUTOM ; VSHUT ; DUMMY dummy.autom.5 : AUTOM ; VSHUT ; DUMMY dummy.dimmer.1 : LIGHT ; DIMMER ; DUMMY dummy.dimmer.2 : LIGHT ; DIMMER ; DUMMY dummy.dimmer.3 : LIGHT ; DIMMER ; DUMMY dummy.dimmer.4 : LIGHT ; DIMMER ; DUMMY dummy.dimmer.5 : LIGHT ; DIMMER ; DUMMY dummy.light.1 : LIGHT ; LIGHT ; DUMMY dummy.light.2 : LIGHT ; LIGHT ; DUMMY dummy.light.3 : LIGHT ; LIGHT ; DUMMY dummy.light.4 : LIGHT ; LIGHT ; DUMMY dummy.light.5 : LIGHT ; LIGHT ; DUMMY
You should then manually add comments and other optional parameters:
(devices) dummy.autom.1 : AUTOM ; VSHUT ; Dummy automation 1 dummy.autom.2 : AUTOM ; VSHUT ; Dummy automation 2
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | I/O Server ready |
light.<n> | 0 | R | light <n> is off |
W | switch off light <n> | ||
off | W | ||
1 | R | light <n> is on | |
W | switch on light <n> | ||
on | W | ||
dimmer.<n> | 0 | R | dimmer <n> is off |
W | switch off dimmer <n> | ||
off | W | ||
1 | W | switch on dimmer <n> | |
on | W | ||
1% ... 100% | R | the light level of dimmer <n> corresponds to the reported value | |
W | set the light level of dimmer <n> to the specified value | ||
autom.<n> | offup | R | autom <n> is stopped in upper position
(set to this value 30 seconds after a 'up' command) |
offdown | R | autom <n> is stopped in lower position
(set to this value 30 seconds after a 'down' command) | |
stop | W | stop autom <n> | |
off | |||
0 | |||
up | R | autom <n> is moving upwards (opening) | |
W | move autom <n> upwards | ||
down | R | autom <n> is moving downwards (closing) | |
W | move autom <n> downwards | ||
<name> | <value> | R | generic data point <name> has value <value> |
W | set value of generic data point <name> to <value> |
Virtual automation devices automatically go to the offup or offdown state 30 seconds after the up or down command.
Note that generic data point names must not start with "light", "autom" or "dimmer".
User Interface
All the devices that have been added in systemtopo.txt (automatically or manually) are listed in the Project Editor and can be directly associated to button and dimmer objects.
For example, adding a slider for a dimmer requires just a few clicks and no additional EVENTS logic.
HTTP API
The HTTP API, when enabled, allows remote applications to read or set data points of the Dummy I/O Server using a simple HTTP/HTTPS API. This API is enabled setting the "httpcallpassword" option.
The HSYCO HTTP server will process GET requests with the following path:
/x/httpcall/<dummy server id>/<httpcallpassword>?<query>
where <query> is one or more data point names separated by the "&" character. A data point name followed by the "=" character and a string sets the data point value, while a data point name not followed by the "=" character will return that data point value, if present, in the HTTP text response.
For example, the following HTTP GET request:
/x/httpcall/dummy/dlskd9sd9dk9s?datapoint1=value1&datapoint2=value2&datapoint3&datapoint4
will set data point "dummy.datapoint1" to "value1", "dummy.datapoint2" to "value2" and, assuming that "dummy.datapoint3" and "dummy.datapoint4" exist, return:
datapoint3=value3 datapoint4=value4
Data point names and values must be URL encoded in the query string, and will be returned URL encoded in the response text.
Release Notes
3.7.0
- new HTTP API: data points can now be set and read remotely with the /x/httpcall HTTP API
3.6.0
- added support for generic read/write data points
3.0.0
- initial release