EL.MO. ETR100 is a multi-area intrusion detection system. The integration with HSYCO can be accomplished via direct control through the RS232 port on the panel.
Contents
Communication
Employ the RS-232 cable provided with the EL.MO. panel to connect it directly to HSYCO or to an Ethernet/RS-232 gateway.
RS-232 parameters:
Baud rate | 9600 |
Data bits | 8 |
Stop bit | 1 |
Parity | none |
Flow control | none |
Options
ID | Default | Values | Description |
---|---|---|---|
gui | true | true | enable automatic support of UI objects to show the system status and intercept control buttons |
false | disable support for the UI | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
offlinelogs | true | false | at startup request the log of all the events occurred while HSYCO was disconnected from the panel |
false | log only events occurred while HSYCO was connected to the panel | ||
pollinterval | 1 | n > 0 | the data acquisition interval, in seconds |
logsize | 20 | n ≥ 0 | the number of log lines to display in the UI object |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
armed | 1 | R | at least one partition is armed |
W | arm all active areas | ||
0 | R | no partition is armed | |
W | disarm all active areas | ||
armed.max | 1 | R | at least one partition is armed in "max security" mode |
W | arm all active areas in "max security" mode | ||
0 | R | no partition is armed in "max security" mode | |
W | disarm all active areas in "max security" mode | ||
alarm | 1 | R | alarm state active |
0 | R | no active alarm | |
tamper | 1 | R | tamper alarm active |
0 | R | no active tamper alarm | |
i<n>.name | <text> | R | the name of input <n> is set to <text> |
i<n>.open | 1 | R | input <n> open |
0 | R | input <n> closed | |
i<n>.alarm | 1 | R | alarm on input <n> |
0 | R | no alarm on input <n> | |
i<n>.tamper | 1 | R | tamper alarm on input <n> |
0 | R | no tamper alarm on input <n> | |
i<n>.bypassed | 1 | R | input <n> bypassed |
W | bypass input <n> | ||
0 | R | input <n> enabled | |
W | enable input <n> | ||
o<n> | 1 | R | output <n> active |
W | activate output <n> | ||
0 | R | output <n> inactive | |
W | deactivate output <n> | ||
a<n>.<m>.name | <text> | R | the name of partition <m> of area <n> is set to <text> |
a<n>.armed | 1 | W | arm all partitions of area <n> |
0 | W | disarm all partitions of area <n> | |
a<n>.armed.max | 1 | W | arm all partitions of area <n> in "max security" mode |
0 | W | disarm all partitions of area <n> in "max security" mode | |
a<n>.<m>.armed | 1 | R | partition <m> of area <n> is armed |
W | arm partition <m> of area <n> | ||
0 | R | partition <m> of area <n> is disarmed | |
W | disarm partition <m> of area <n> | ||
a<n>.<m>.armed.max | 1 | R | partition <m> of area <n> is armed in "max security" mode |
W | arm partition <m> of area <n> in "max security" mode | ||
0 | R | partition <m> of area <n> is not armed in "max security" mode | |
W | disarm partition <m> of area <n> in "max security" mode | ||
usr<n>.name | <text> | R | the name of user <n> is set to <text> |
kp<n>.tamper | 1 | R | keypad <n> tampered |
0 | R | keypad <n> not tampered | |
fault.battery | 1 | R | battery fault active |
0 | R | no battery fault active | |
panel.tamper | 1 | R | panel tampered |
0 | R | panel not tampered | |
rel.tamper | 1 | R | tamper relay is on |
0 | R | tamper relay is off | |
rel.alarm | 1 | R | alarm relay is on |
0 | R | alarm relay is off |
User Interface
Object
The user interface for the EL.MO. multi-area intrusion detection system:
The (elmo) object is listed in the Project Editor’s new object list only when at least one EL.MO. I/O Server is defined
Parameters
- server id: the server ID. Supports Redirect variables
- area: the area. Supports Redirect variables
- position: the object's position. Use the pixels or rows and columns coordinates format
Syntax
(elmo <server id>; <area>; <position>)
E.g.
(elmo elm; 1; x10y20)
Display Objects
ID | Attribute | Set to | |
---|---|---|---|
log | text | latest security log lines (as many as specified by the 'logsize' option) | |
log0 | text | latest line of the security log when a new entry is added, set back to blank after a short period | |
i<n>.name | text | name assigned to input <n> | |
a<n>.<m>.name | text | name assigned to partition <m> of area <n> | |
usr<n>.name | text | name assigned to user <n> | |
connection.label | visible | true | when datapoint connection = offline |
false | when datapoint connection = online | ||
<datapoint_id>.label.1 | visible | true | when datapoint with ID <datapoint_id> has value '1' |
false | when datapoint with ID <datapoint_id> has value '0' | ||
<datapoint_id>.label.0 | visible | true | when datapoint with ID <datapoint_id> has value '0' |
false | when datapoint with ID <datapoint_id> has value '1' |
Command Objects
Name | Param | Action |
---|---|---|
armed | 1 | arm all active areas |
0 | disarm all active areas | |
armed.max | 1 | arm all active areas in "max security" mode |
0 | disarm all active areas in "max security" mode | |
ID.a<n>.armed | 1 | arm all partitions of area <n> |
0 | disarm all partitions of area <n> | |
a<n>.armed.max | 1 | arm all partitions of area <n> in "max security" mode |
0 | disarm all partitions of area <n> in "max security" mode | |
a<n>.<m>.armed | 1 | arm partition <m> of area <n> |
0 | disarm partition <m> of area <n> | |
a<n>.<m>.armed.max | 1 | arm partition <m> of area <n> in "max security" mode |
0 | disarm partition <m> of area <n> in "max security" mode | |
i<n>.bypassed | 1 | bypass input <n> |
0 | enable input <n> | |
o<n> | 1 | activate output <n> |
0 | deactivate output <n> |