GSM

From HSYCO
Revision as of 14:57, 9 June 2016 by Giampiero (talk | contribs)
Jump to navigation Jump to search

This I/O Server provides services for sending and receiving SMSs and events generation for incoming calls via serial GSM modem.

The employed protocol complies with the AT commands set specified by the GSM standard set. It has been tested on the following modems:

  • GenPro 16e and GenPro 18e modems by Erco&Gener
  • AirLink FXT009 modem by Sierra Wireless
  • RB800/RB900 series modems by Teleorigin


Communication

Employ a RS-232 straight cable to connect the modem directly to HSYCO or to an Ethernet/RS-232 gateway.

RS-232 parameters:

Baud rate 9600 (GenPro modems)
115200 (default setting on other modems)
Data bits 8
Stop bit 1
Parity none
Flow control RTS/CTS

HSYCO Configuration

Add a GSM I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • Comm ID: select the comm port the device is connected to.

High Availability

  • Shutdown when inactive: defaults to true.

Options

ID Default Values Description
pin <code> 4-digits PIN code of the SIM card (if used)
gui true true enable support for the UI object, UISET actions and USER commands
false disable UI support
inboxsize 10 n ≥ 0 the number of incoming messages to display in the UI object
countrycode <code> the default country code (e.g. “39”, for Italy) to be used when not otherwise specified. If omitted all provided numbers shall include the country code


srvc <number> phone number of the SMS service center (use the international format, e.g. +393492000200). If not specified, the default number saved on the SIM card will be used. If not available, the driver will not be able to send SMS messages
resend 4 n ≥ 0 number of sending attempts on an outgoing SMS in case of error

Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the modem
sms.<num> <text> R an SMS message has been received form the number <num>[Note 2] with <text> as body
W send an SMS message to the number <num>[Note 1] with <text> as body
call <num> R incoming call from number <num>[Note 2] in progress. An event is generated for each “ring” during the call
W start a voice call to number <num>[Note 1]
end W end the ongoing voice call
unknown R incoming call from an unknown number in progress
call.state start R a voice call has been started
alerting R the ongoing voice call is in the alerting state, i.e. the phone on the other end is ringing
active R the ongoing voice call is active, i.e. the call has been answered from the other end
held R the ongoing voice call is being held
dialing R the modem is dialing the number
waiting R the ongoing voice call is waiting
end R the voice call has ended
sms.<num>.sent <mr> R a message has been successfully sent to the number <num> and the message reference number is <mr>
sms.<num>.errors <val> R an error occurred while sending a message to number <num>. The value <val> is an increasing counter of the occurred errors since the I/O Server started
signal {0 ... 31} R the GSM signal level has the reported value (ranging from 0 to 31)
unknown R the GSM signal level is unknown

Note 1 
If the option 'countrycode' is used, then the country code will be automatically added to the specified numbers, unless the latter begins with a '+' character. For instance, assuming the option 'countrycode' is set to “39”, the addressee number “3480077000” will be automatically changed to “+393480077000”, while the number “+46765007700” will remain unchanged. If, on the other hand, no default country code has been specified, then the addressee numbers must always be provided prepending the country code.

Note 2 
The numbers are reported as sent from the modem and the format may vary depending on the number itself and the modem settings. If the reported number is an international number, then a '+' will be prepended to it, unless the country code is equal to the value of the 'countrycode' option. In the last case the country code will be omitted. In some cases, the sender number field might also be replaced by an alphanumeric string.

User Interface

SMS Object

The user interface for sending SMS messages:

UI Object sms.png

The SMS object is listed in the Project Editor’s new object list only when at least one GSM I/O Server is defined.


Parameters

  • server id: the server ID. Supports Redirect variables
  • position: the object's position. Use the pixels or rows and columns coordinates format

Syntax

(sms <server id>; <position>)

E.g.

(sms serverid; x10y20)

UISET Actions

ID Attribute Set to
inbox value latest incoming SMS messages (as many as specified by the 'inboxsize' option)
connection.label.online visible true when datapoint connection = online
false when datapoint connection = offline
connection.label.offline visible true when datapoint connection = offline
false when datapoint connection = online
signal.label.0 visible true when the GSM signal level is equal to 0
false when the GSM signal level is not 0
signal.label.1 visible true when the GSM signal level is between 1 and 8
false when the GSM signal level is not between 1 and 8
signal.label.2 visible true when the GSM signal level is between 9 and 16
false when the GSM signal level is not between 9 and 16
signal.label.3 visible true when the GSM signal level is between 17 and 24
false when the GSM signal level is not between 17 and 24
signal.label.4 visible true when the GSM signal level is above 24
false when the GSM signal level is below 25
signal.label.unknown visible true when the GSM signal level is unknown
false when the GSM signal level is known
sending.label visible true when the modem is sending a message
false when the modem is not sending a message
error.label visible
blink
true for 5 seconds after there’s been an error sending a message
false default value

USER Commands

UI Object ID
input <ioserver_id>.sms.number
input <ioserver_id>.sms.text
submit <ioserver_id>.sms.send

From the resulting interface, digit the addressee number (or comma-separated list of numbers) in the input field with ID “<ioserver_id>.sms.number” and the body text in the input field “<ioserver_id>.sms.text”, then press the submit button.

N.B. If the option 'countrycode' is used, then the country code will be automatically added to the numbers, unless the latter begins with a '+'. For instance, assuming the value of the option 'countrycode' is set to “39”, the addressee number “3480077000” will be automatically changed to “+393480077000”, while the number “+46765007700” will remain unchanged. If, on the other hand, no default country code has been specified, then the addressee numbers must always be provided prepending the country code.

PUK-locked SIM

In case the SIM card used for the GSM modem is PUK-locked, it is required to provide the PUK code and a new PIN to set on the SIM card. To this end, create in the root folder of HSYCO a file named “<ioserver_id>.puk”, where <ioserver_id> is the ID of the corresponding I/O Server (e.g. “gsm.puk”). In this file add a single line containing the PUK code and the new PIN code separated by a comma, for instance:

12345678,1234

The file will be automatically deleted after it has been used by the I/O Server.

Examples

Sending an SMS

Assuming that we are sending an SMS at 12 o' clock to number 777123456 located in Italy (International prefix code: +39) and the option "countrycode" of the GSM IO server is not specified, this is the corresponding EVENTS programming declaration:

time = 1200 : io gsm.sms.+39777123456 = "I'm sending and sms to the world"

You can send multiple SMSs to different numbers using this syntax:

time = 1200 : io gsm.sms.+39777123456 gsm.sms.+39777654321 = "I'm sending an sms to the world"

Receiving an SMS

Hsyco can receive SMSs through the GSM IO server and perform actions according to the text contained in the SMS.

io gsm.sms.777123456 = "Help" : io gsm.sms.777123456 = "I accept the following commands: Open, Status"
io gsm.sms.777123456 = "Open" : io knx.1/1/2 = 1, wait = 1, io knx.1/1/2 = 0

Release Notes

3.5.0

  • added voice call functionality
  • improved stability for Teleorigin modem

3.4.0

  • fixed bug occurring when sending messages containing the '=' character
  • minor fixes to the sms UI object

3.3.0

  • added “resend” server option
  • improved AT commands compatibility
  • added PUK-unlock functionality

3.2.1

  • added “srvc” server option
  • bug fix: user.IOStartupEvent() was not called at startup

3.1.0

  • initial release


GenPro 16e, GenPro 18e, and Erco&Gener are registered trademarks of Erco&Gener.