RayCONTROL

From HSYCO
Jump to navigation Jump to search

RayCONTROL 30 is the control unit for the FCC Planterm temperature control system.

RayCONTROL 30 supports up to 30 individual zones.

Communication

RayNET is an interface module that provides a standard Modbus/RTU interface over RS485 for RayCONTROL 30. The default connection parameters are:

Modbus address: 1

RS-485 parameters:

Baud rate 9600
Data bits 8
Stop bit 1
Parity none
Flow control none

Refer to the RayNET and RayCONTROL 30 technical documentation for installation, wiring and power supply requirements.

HSYCO connects to the Modbus bus through any standard Modbus/TCP gateway.

HSYCO Configuration

Options

ID Default Values Description
gui true true enable support for the UI object, UISET actions and USER commands
false disable UI support
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
pollinterval 30 1 ... 45 the data acquisition interval, in seconds
address 1 > 0 the Modbus address of the RayCONTROL device
readinterval 25 0 ... 1000 minimum interval between consecutive Modbus commands
systems 1 1 ... 2 set to 1 if using only system 1; set to 2 is system 2 is used
zones 15 1 ... 30 set to the highest zone number used
sensivity 5 >0 measured temperatures’ changes are reported only if the difference from last reading is equal or greater than the sensivity option, in 10th of Celsius degrees
language en en, fr, it the language used for text messages. If undefined, the global language option is used. English is used if the global language is also undefined

Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
s<n>.status off R system <n> is off
W turn off system <n>
on R system <n> is on
W turn on system <n>
maint R system <n> is in maintenance mode
s<n>.mode winter R system <n> is in winter mode
W set system <n> to winter mode
summer R system <n> is in winter mode
W set system <n> to summer mode
towinter R system <n> is in summer mode, transitioning to winter mode
tosummer R system <n> is in winter mode, transitioning to summer mode
s<n>.setpoint.winter.max 160 .. 300 R system <n> current maximum winter temperature set-point
W set system <n> maximum winter temperature set-point
s<n>.setpoint.winter.min 150 .. 290 R system <n> current minimum winter temperature set-point
W set system <n> minimum winter temperature set-point
s<n>.setpoint.summer.max 160 .. 300 R system <n> current maximum summer temperature set-point
W set system <n> maximum summer temperature set-point
s<n>.setpoint.summer.min 150 .. 290 R system <n> current minimum summer temperature set-point
W set system <n> minimum summer temperature set-point
s<n>.temp.out -400 ... +800 R outdoor temperature, in 10th of Celsius degrees (e.g. 210 corresponds to 21.0 °C)
s<n>.temp.inlet -400 ... +800 R inlet temperature, in 10th of Celsius degrees (e.g. 210 corresponds to 21.0 °C)
z<n>.mode off R zone <n> is off
W turn off zone <n>
maint R zone <n> is in maintenance mode
eco R zone <n> is in energy saving mode
W set zone <n> to energy saving mode
pgm R zone <n> is in program mode
W set zone <n> to program mode
man R zone <n> is in manual mode
W set zone <n> to manual mode
on W set zone <n> to the mode set before last off (ECO, PGM or MAN). If HSYCO starts with the zone already off, the on command sets the mode to ECO
z<n>.lock 0 R zone <n> is not locked
W unlock zone <n>
1 R zone <n> is locked
W lock zone <n>
z<n>.temp -400 ... 800 R measured temperature, in 10th of Celsius degrees (e.g. 210 corresponds to 21.0 °C)
z<n>.humidity 1... 100 R measured relative umidity, from 0 to 100
z<n>.setpoint.temp 150 ... 300 R zone <n> set-point temperature, in 10th of Celsius degrees
(e.g. 210 corresponds to 21.0 °C)
W zone <n> set-point temperature, in 10th of Celsius degrees
(e.g. 210 corresponds to 21.0 °C)
up W increase zone temperature set-point by 0.5 °C
down W decrease zone temperature set-point by 0.5 °C
alarm.<c> 0 R alarm code C (1-72) inactive
1 R alarm code C (1-72) active
alarm 0 R no active alarms
1 R the system is reporting at least one active alarm

User Interface

UISET Actions

USER Commands

ID Attribute Set to
Name Param Action

Release Notes

3.3.0

  • new data points: s<n>.setpoint.winter.max s<n>.setpoint.winter.min s<n>.setpoint.summer.max s<n>.setpoint.summer.min z<n>.lock
  • new readinterval option (defaults to 20 msec.)
  • improved communication errors handling

3.0.0

  • full integration in HSYCO 3.0.0


RayCONTROL is a registered trademark of Permasteelisa Impianti srl, FCC Planterm Division.