Difference between revisions of "Redscan"

From HSYCO
Jump to navigation Jump to search
Line 8: Line 8:
  
 
[[File:Redscan_event_code.png|500px|border]]
 
[[File:Redscan_event_code.png|500px|border]]
 +
  
 
To enable the drawing of detected objects on HSYCO's interface, you need to provide the I/O Server with the coordinates of the area that is monitored by the scanner.
 
To enable the drawing of detected objects on HSYCO's interface, you need to provide the I/O Server with the coordinates of the area that is monitored by the scanner.
Line 13: Line 14:
 
To this end, open the Redscan Manager and take note of the upper-left and lower-right corners of the virtual rectangular area covering the detection area set on the scanner:
 
To this end, open the Redscan Manager and take note of the upper-left and lower-right corners of the virtual rectangular area covering the detection area set on the scanner:
  
[[File:Redscan_detection_area.png|500px|border]]
+
[[File:Redscan_detection_area.png|800px|border]]
  
Set the coordinates of this two points in the [[#Options|I/O Server options]] 'areaX1', 'areaY1', 'areaX2' and 'areaY2'.
+
Set the coordinates (in millimeters) of this two points in the [[#Options|I/O Server options]] 'areaX1', 'areaY1', 'areaX2' and 'areaY2'.
  
 
== HSYCO Configuration ==
 
== HSYCO Configuration ==

Revision as of 14:23, 12 June 2017

The OPTEX REDSCAN is a laser scan detector that can detect a moving object's size, speed, and distance with high-reliability. The integration with HSYCO can be accomplished via direct control through Ethernet connection. The I/O Server complies with the Optex Redscan Protocol v1.71 and has been tested on firmware version 7.3.0.

Redscan Configuration

To enable alarm events, make sure the Event Code via Broadcast UPD is enabled. In the Redscan Manager go to Basic Settings > I/O Settings:

Redscan event code.png


To enable the drawing of detected objects on HSYCO's interface, you need to provide the I/O Server with the coordinates of the area that is monitored by the scanner.

To this end, open the Redscan Manager and take note of the upper-left and lower-right corners of the virtual rectangular area covering the detection area set on the scanner:

Redscan detection area.png

Set the coordinates (in millimeters) of this two points in the I/O Server options 'areaX1', 'areaY1', 'areaX2' and 'areaY2'.

HSYCO Configuration

Add a REDSCAN I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • IP Address: host name or IP address of the panel
  • IP Port: TCP/IP port to use (as configured on the panel)

High Availability

  • Shutdown when inactive: defaults to true.

Options

ID Default Values Description
eventsport 1234 <port_number> port number to which UDP alarm messages are sent by the scanner. Set to 0 to disable alarm events
areaX1 <x> X coordinate of the upper-left corner of the detection area. If not specified the image is not drawn
areaY1 <y> Y coordinate of the upper-left corner of the detection area. If not specified the image is not drawn
areaX2 <x> X coordinate of the lower-right corner of the detection area. If not specified the image is not drawn
areaY2 <y> Y coordinate of the lower-right corner of the detection area. If not specified the image is not drawn
flipx false true the detected objects image is flipped horizontally
false the image not flipped horizontally
flipy false true the detected objects image is flipped vertically
false the image not flipped vertically
bordercolor red <color> color for the border of the circles representing the detected objects
fillcolor white <color> color for the inner part of the circles representing the detected objects
detectioninterval 10 0 ≤ n ≤ 100 interval between detection reports sent by the scanner. 1 = 50ms, 100 = 5sec. Set to 0 to disable detection events

Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
armed 0 R all partitions are disarmed
1 R the system is (partially) armed

User Interface