DEA XENSITY is a Point ID intrusion detection system using special piezoelectric sensors for the protection of doors, windows, glass surfaces, security grilles and walls. This driver is compatible with the following controllers: Xensity128, Xensity64, Xensity32. Make sure to install the latest available firmware.

DEA XENSITY controllers can be connected via ethernet. A valid IP address must be assigned to the controller using the configuration software.

Note  In case of multiple XENSITY IO Servers running on the same HSYCO Server you must assign a different UDP port to each XENSITY controller

Add a XENSITY I/O Server in the I/O Servers section of the Settings and set its parameters:

  • Address: IP address of the XENSITY controller (mandatory)
  • Port: UDP port (mandatory)
  • Shutdown when inactive: defaults to false.
ID Default Values Description
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
pollinterval 1000 n ≥ 0 the data polling interval, in milliseconds. Shorter time improve the response of the system, but increase the load on the CPU of both HSYCO and the Xensity system
ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
alarm 0 R no alarms
1 R at least one zone of this controller on alarm
link.x16 0 R connection with X16-ER16L is not stable
1 R connection with X16-ER16L is stable
link.sens 0 R connection with sensors is not stable
1 R connection with sensors is stable
bus.power 0 R bus sensors power supply not ok
1 R bus sensors power supply ok
alarm.nf 0 R no alarms
1 R At least one alarm is active - not filtered-
tamper.nf 0 R no tamper alarms
1 R at least one tamper alarm is active - not filtered-
arm 0 R arm is not active
1 R arm is active
in.tamper 0 R tamper input is not active
1 R tamper input is active
battery.low 0 R battery charge ok
1 R battery charge is low
test.fail 0 R autotest is ok
1 R at least one sensor failed autotest
bus.fault 0 R sensors bus is ok
1 R sensors bus fault
bus.overcurr 0 R current on sensors bus is ok
1 R over current on sensors bus
tamper 0 R no sensors in tamper alarm
1 R At least one sensor in tamper alarm
power.fault 0 R power ok
1 R power fail
vin <v> R power supply voltage <v> in mV
oc<n> 0 R open collector output <n> is open
1 R open collector output <n> is closed
rel<n> 0 R relay <n> is open
1 R relay <n> is closed
in<n> 0 R input <n> is open
1 R input <n> is closed
serial <string> R serial number <string>
seclev <n> R global security level <n>
pn <n> R hardware type <n>
z<n>.alarm 0 R zone <n> not on alarm
1 R zone <n> on alarm
z<n>.alarm.mem 0 R zone <n> not on alarm memory
1 R zone <n> on alarm memory
z<n>.prealarm.mem 0 R zone <n> not on prealarm memory
1 R zone <n> on prealarm memory
z<n>.tamper 0 R zone <n> not on tamper alarm
1 R zone <n> on on tamper alarm
z<n>.tamper.mem 0 R zone <n> not on tamper memory alarm
1 R zone <n> on on tamper memory alarm
z<n>.armed 0 R zone <n> disarmed
1 R zone <n> armed
z<n>.bypass 0 R zone <n> not bypassed
1 R zone <n> bypassed
z<n>.fault 0 R zone <n> not in fault
1 R zone <n> fault
z<n>.fault.mem 0 R zone <n> not in fault memory
1 R zone <n> fault memory
z<n>.line <v> R zone <n> line type
z<n>.name <string> R zone <n> name <string>
z<n>.pn <v> R zone <n> has hardware type <v>
z<n>.seclev <v> R zone <n> has security level <v>
z<n>.serial <string> R zone <n> has serial address <string>
  • now included in the HSYCO jar package
  • initial release