The KSENIA lares 4.0 is a multi-area security system. The I/O Server has been tested on unit with firmware version 1.72.2. Actually this driver runs only in HTTP mode (port 80 is set by default).

You must firstly configure your panel in the web app at the following address https://<panel_ip_address> (the panel starts in DHCP mode so you have to find the relative IP address assigned). In the web app, select your panel and log into it with installer privileges, then go to settings. In network settings, disable DHCP mode and set a static ip address, then disable HTTPS connection (you must unflag protocol TLS in "Web Server" section and select port 80). When you have finished save your configuration. In alternative, you can configure your panel passing by Ksenia SecureWeb cloud.

ATTENTION: this driver works only with Lares4 firmware version 1.72.2 or higher. You can download the latest firmware version from Kseniasecurity.com in the reserved area.

Add a LARES4 I/O Server in the I/O Servers section of the Settings and set its parameters:

  • IP Address: host name or IP address of the panel
  • IP Port: leave it blank
  • Password: pin to access the web server with user privileges (NOT installer!)
  • Shutdown when inactive: defaults to false.
ID Default Values Description
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
pollinterval 1000 n > 1000 the data acquisition interval, in milliseconds
logsize 50 0 ≤ n ≤ 300 the number of log lines to display in the UI object
gui true true enable the UISET "visible" field for all partition zones
false disable the UISET "visible" field for all partition zones
maxpartitions 3 1≤n≤30 number of partitions that are configured in the security panel
ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
armed 1 W arm all partitions in the system
0 W disarm all partitions in the system
p<n>.desc <text> R description of partition <n>
p<n>.armed 0 R partition <n> is disarmed
W disarm partition <n>
1 R partition <n> is armed
W arm partition <n>
p<n>.alarm 0 R partition <n> not in alarm
1 R partition <n> in alarm
mem R partition <n> in alarm memory state
p<n>.tamper 0 R partition <n> not in tamper
1 R partition <n> in tamper
mem R partition <n> in tamper memory state
z<n>.desc <text> R description of zone <n>
z<n>.alarm 0 R zone <n> not in alarm
1 R zone <n> in alarm
z<n>.mask 0 R zone <n> not masked
1 R zone <n> masked
z<n>.tamper 0 R zone <n> not in tamper
1 R zone <n> in tamper
z<n>.error 0 R zone <n> not in error
1 R zone <n> in error
z<n>.bypass 0 R zone <n> is not bypassed
W unbypass zone <n>
1 R zone <n> is bypassed
W bypass zone <n>
o<n>.desc <text> R description of output <n>
o<n> 0 R output <n> is off
W turn off output <n>
1 R output n <n> is on
W turn on output <n>
voltage.low 0 R system voltage is ok
1 R system voltage is low
batt.low 0 R battery is ok
1 R battery is low
batt.fault 0 R battery is ok
1 R battery fault
pstn.fault 0 R pstn is ok
1 R pstn fault
credit.low 0 R credit is ok
1 R credit is low
system.fault 0 R system is ok
1 R system fault
mobile.fault 0 R mobile is ok
1 R mobile fault
s<n>.desc <text> R description of scenario <n>
s<n> 1 W trigger scenario <n>
g<n>.desc <text> R description of gate <n>
g<n>.status <text> R raw status of gate <n>, in lower case (enabled, open, open_fd, open_dotl, ...)
g<n>.open 0 R gate <n> is closed
1 R gate <n> is open
W open gate <n> (momentary command)
g<n>.forced 0 R gate <n> not forced open
1 R gate <n> forced open
g<n>.dotl 0 R gate <n> not in door open too long state
1 R gate <n> in door open too long state
g<n>.byp_dotl 0 R door open too long bypass not active on gate <n>
1 R door open too long bypass active on gate <n>
W bypass the door open too long alarm on gate <n>
na R door open too long bypass not available on gate <n>
u<n>.desc <text> R description of account <n>
u<n>.auth <text> R authorization status of account <n>, in lower case (authorized, ...)
log0 <text> R last log line generated by the panel; automatically cleared to an empty string after 5 seconds

The g<n>.open and g<n>.byp_dotl datapoints only accept the value 1 in write: they are momentary commands, the written value is not stored.

Note that g<n>.open reflects the actual state of the gate as reported by the panel, not the command sent to it. When you send the open command, the panel generates a momentary opening and the gate status typically goes back to enabled immediately, so g<n>.open may well stay at 0. It goes to 1 when the gate is really open, for example when it is kept open manually.

The u<n>.desc datapoints are read from the panel configuration, that may not be available when connecting with a USER role login. In that case only u<n>.auth is generated.

The user interface for the Lares4 multi-area intrusion detection system:

Lares4 UI Object 1.png Lares4 UI Object 2.png Lares4 UI Object 3.png

The first image shows the list of configured partitions. You can set the alarm for all the partitions, otherwise you can open a popup on a dedicated partition and set the alarm only for that one. The two icons on the top of the page represent in order: partition tamper (at least one partition is in tamper state), partition alarm (at least one partition is in alarm state).

The second image shows the popup associated to a zone; the four icons shown inside the popup represent in order: zone alarm, zone tamper, zone bypassed, zone fault. Inside the popup you can bypass/unbypass the selected zone.

The (lares4) object is listed in the Project Editor’s new object list only when at least one Lares4 I/O Server is defined

  • server id: the server ID. Supports Redirect variables
  • position: the object's position. Use the pixels or rows and columns coordinates format
(lares4 <server id>; <position>)

E.g.

(lares4 lares; x10y20)
ID Attribute Set to
log value latest security log lines (as many as specified by the 'logsize' option)
log0 value latest security log (it will vanish after 5 seconds)
access.log value latest access log lines (as many as specified by the 'logsize' option)
access.log0 value latest access log (it will vanish after 5 seconds)
z<n>.tamper visible false zone n not in tampering
true zone n in tampering
z<n>.bypass visible false zone n not bypassed
true zone n bypassed
z<n>.alarm visible false zone n not in alarm
true zone n in alarm
z<n>.error visible false zone n not in error state
true zone n in error state
z<n>.mask visible false zone n not masked
true zone n masked

If a Ksenia anti-intrusion unit is connected to HSYCO, the security.log file will be written in the same directories as the daily log files.

This file is never overwritten or deleted from HSYCO SERVER.

2018.02.20 16:59:28.516 - lares - 20/02/2018 16:56:36 - Disinserimento - Part 1 - U1
2018.02.20 17:00:24.527 - lares - 20/02/2018 16:57:36 - Inserimento - Part 1 - U1
2018.02.20 17:00:44.318 - lares - 20/02/2018 16:57:57 - Allarme - Zone 1
2018.02.20 17:00:49.241 - lares - 20/02/2018 16:57:58 - Ripristino - Zone 1
2018.02.20 17:00:54.043 - lares - 20/02/2018 16:58:06 - Disinserimento - Part 1 - U1
2018.02.20 17:01:18.905 - lares - 20/02/2018 16:58:29 - Fallita Comunicazione - Leonardo - Vocale GSM
2018.02.20 17:01:29.053 - lares - 20/02/2018 16:58:40 - Fallita Comunicazione - Leonardo - SMS

Other information about the Ksenia driver are stored in the message.log daily file.

The driver also retrieves the access control events history from the panel. At start-up the existing history is downloaded from the panel, then new events are received in real time.

The following event types are collected: gate opening, gate forced open, gate open too long, valid code, valid key, invalid code, installer connection and user modification.

Access events are written to the security.log file, marked with the [access] tag, and are displayed in the UI object. The number of lines kept in the history is set by the logsize option.

2026.07.10 09:12:04.318 - lares4 [access] - 10/07/2026 09:12:03 - GATEOPEN - Gate 1 (Hsyco)
  • added support for gates
  • added support for access logs
  • added support for accounts
  • the log0 datapoint now mirrors the last log line displayed in the UI object
  • communication with panel now based on asynchronous protocol
  • polling discontinued, pollinterval attribute will be ignored
  • changed default log size to 50 lines, max 300 lines
  • minor bug fixes and optimization
  • initial version release