NotifierESibM
Notifier E-SIB-M is a license key to enable Modbus TCP communication for a series of Notifier and Honeywell fire detection panels:
AM8200 Notifier (legacy up to 8 lines per control panel)
AM8100 Notifier
AM1000CL
AM2000CL
AM6000CL
MA1000-03
MA2000-03
MA1000-01
MA2000-01
MA1000-02
MA2000-02
AM8200N Notifier (up to 4 lines per control panel)
AM8200N Honeywell (up to 4 lines per control panel)
AM8200 Honeywell (legacy up to 8 lines per control panel)
AM8100 Honeywell
MA1000-04
MA2000-04
The integration with HSYCO can be accomplished via a standard Modbus TCP/IP connection. This I/O server was developed following the MODBUS documentation Mod-Bus_Prot_rev.01.
For any information regarding the activation of the Modbus protocol on the E-SIB-M dongle, please contact your Notifier distributor.
Communication
Section titled “Communication”Notifier E-SIB-M compatible panels can be connected via ethernet. A valid IP address must be assigned to the panel. MODBUS PROTOCOL must be enabled. Please refer to the panel manual for detailed instruction about MODBUS protocol configuration.
HSYCO Configuration
Section titled “HSYCO Configuration”Add a Notifieresibm I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
Section titled “Communication”- Address: IP address of the Notifier E-SIB-M panel
- Port: TCP/IP port for MODBUS communication (default 502)
High Availability
Section titled “High Availability”- Shutdown when inactive: defaults to false.
Options
Section titled “Options”| ID | Default | Values | Description |
|---|---|---|---|
| gui | true | true | enable support for the UI object, UISET actions and USER commands |
| false | disable UI support | ||
| startupevents | false | true | generate IO events also during the driver’s start-up phase |
| false | start generating events only after HSYCO is aligned with the current status of the system | ||
| modulesnumber | 159 | n = 0..159 | highest module address of all the connected panels. E.G. If 2 panel with 2 lines are connected and the first panel has 20 modules on the first line, and 10 on the second, and the second panel has 30 modules on the first line and 10 on the second you should set modulesnumber = 30 to read all the modules |
| sensorsnumber | 159 | n = 0..159 | highest sensor address of all the connected panels. E.G. If 2 panel with 2 lines are connected and the first panel has 30 sensors on the first line, and 10 on the second, and the second panel has 50 sensors on the first line and 10 on the second you should set sensorsnumber = 50 to read all the modules |
| zonesnumber | 10 | n = 0..2000 | set to the highest zone number configured in the system. |
| pollinterval | 250 | n = 100..30000 | time interval in milliseconds added at the end of each driver loop cycle. |
| readpause | 0 | n = 0..1000 | time interval in milliseconds added between consecutive Modbus read operations, for every 100 Modbus registers requested. Use this parameter carefully: on systems with hundreds of zones and sensors, setting a value close to 1000 ms may significantly extend the overall polling cycle, potentially approaching or exceeding the driver timeout. |
| maxpanelsnumber | n = 1..64 | forces the driver to read the control panel status up to the specified panel number, overriding the automatic panel detection. | |
| maxlinesnumber | n = 1..12 | forces the driver to read the control panel status up to the specified line number, overriding the automatic line detection. |
notifieresibm.ini
Section titled “notifieresibm.ini”The notifieresibm.ini file is a specific configuration file located in the root directory.
This file is required to provide the I/O Server the name assignment of zones and devices.
This is an example of the file content:
noti.z1 = Zone 1
noti.panel.1.line.1.sensor.1 = Sensor 1 Line 1 Panel 1
noti.panel.1.line.1.sensor.10 = Sensor 10 Line 1 Panel 1
noti.panel.1.line.1.module.1.subddr.2 = Module 1 Line 1 Panel 1 Subaddr 2
noti.panel.1.line.2.module.1.subddr.1 = Module 1 Line 2 Panel 1 Subaddr 1
Where "noti" is the I/O Server id of the NOTIFIERESIBM I/O Server
If you have multiples NOTIFIERESIBM I/O Servers:
noti1.z1 = Zone 1
noti1.panel.1.line.1.sensor.1 = Sensor 1 Line 1 Panel 1
noti2.panel.1.line.1.sensor.10 = Sensor 10 Line 1 Panel 1
noti2.panel.1.line.1.module.1.subddr.2 = Module 1 Line 1 Panel 1 Subaddr 2
noti3.panel.1.line.2.module.1.subddr.1 = Module 1 Line 2 Panel 1 Subaddr 1
Datapoints
Section titled “Datapoints”| ID | Value | R/W | Description |
|---|---|---|---|
| connection | online | R | connection established |
| offline | R | HSYCO can't connect to the panel, or the Modbus license is missing (global.license.missing = 1) | |
| version | <String> | R | panel firmware version, in the format <major>.<minor>.<build> (e.g. 1.0.50) |
| command.reset | 1 | W | force panel reset |
| command.silence | 1 | W | silence panel |
| command.sirens.toggle | 1 | W | toggle sirens status, if a fire alarm is active |
| global.alarm.led.faulty | 0 | R | fault led is off |
| 1 | R | fault led is on | |
| global.alarm.led.faulty.flashing | 0 | R | fault led is not flashing |
| 1 | R | fault led is flashing | |
| global.alarm.led.flashing | 0 | R | alarm led is not flashing |
| 1 | R | alarm led is flashing | |
| global.alarm.led.status | 0 | R | alarm led is off |
| 1 | R | alarm led is on | |
| global.evacuation | 0 | R | not in evacuation |
| 1 | R | evacuation active | |
| global.exclusions.present | 0 | R | no active exclusions |
| 1 | R | at least one sensor or zone excluded | |
| global.hardware.key.present | 0 | R | the hardware key is not present |
| 1 | R | the hardware key is present | |
| global.hardware.key.register | 0..65535 | R | raw value of the panel hardware key register (Modbus register 1). 0 = hardware key present, any other value = hardware key not present. Useful for diagnostics |
| global.license.missing | 0 | R | license key not missing |
| 1 | R | license key is missing | |
| global.system.buzzer.status | 0 | R | system buzzers are off |
| 1 | R | system buzzers are on | |
| global.system.siren.silenced | 0 | R | sirens are not silenced |
| 1 | R | sirens are silenced | |
| global.system.siren.status | 0 | R | sirens status is off |
| 1 | R | sirens status is on | |
| global.test.events.presents | 0 | R | no test events present |
| 1 | R | at least one test event present | |
| global.lines.number | 1..12 | R | number of lines configured on the system |
| global.panels.number | 1..64 | R | number of panels configured on the system |
| global.model | <String> | R | panel model, list of supported panels: am8200,am8100,am1000cl,am2000cl,am6000cl,ma1000-03,ma2000-03,ma1000-01,ma2000-01,ma1000-02,ma2000-02,am8200n,am8200n-honeywell,am8200-honeywell,am8100-honeywell,ma1000-04,ma2000-04. unknown if the model is not recognized |
| global.zone.<n>.alarm | 0 | R | zone <n> not in alarm |
| 1 | R | zone <n> in alarm | |
| global.zone.<n>.empty | 0 | R | zone <n> not empty |
| 1 | R | zone <n> is empty | |
| global.zone.<n>.fault | 0 | R | zone <n> not faulty |
| 1 | R | zone <n> is faulty | |
| global.zone.<n>.normal | 0 | R | zone <n> not in normal mode |
| 1 | R | zone <n> is in normal mode | |
| global.zone.<n>.prealarm | 0 | R | zone <n> not in prealarm |
| 1 | R | zone <n> is in prealarm | |
| global.zone.<n>.test | 0 | R | zone <n> not in test |
| 1 | R | zone <n> is in test | |
| global.zone.<n>.status | 0,1,3,4,5,6 | R | zone <n> status in numeric value. 0=normal,1=empty,3=test, 4=alarm,5=fault,6=prealarm |
| global.zone.<n> | include | W | include zone |
| exclude | W | exclude zone | |
| panel.<pan>.line.<lin>.sensor.<sens>.alarm | 0 | R | sensor not in alarm |
| 1 | R | sensor in alarm | |
| panel.<pan>.line.<lin>.sensor.<sens>.excluded | 0 | R | sensor included |
| 1 | R | sensor excluded | |
| panel.<pan>.line.<lin>.sensor.<sens>.fault | 0 | R | sensor not faulty |
| 1 | R | sensor faulty | |
| panel.<pan>.line.<lin>.sensor.<sens>.normal | 0 | R | sensor not in normal mode |
| 1 | R | sensor in normal mode | |
| panel.<pan>.line.<lin>.sensor.<sens>.not.programmed | 0 | R | sensor is programmed |
| 1 | R | sensor is not programmed | |
| panel.<pan>.line.<lin>.sensor.<sens>.test | 0 | R | sensor not in test |
| 1 | R | sensor in test | |
| panel.<pan>.line.<lin>.sensor.<sens>.analogval | 0..65535 | R | analog value of the sensor |
| panel.<pan>.line.<lin>.sensor.<sens>.status | 0,1,2,3,4,5 | R | sensor status numeric value. 0=normal,1=not programmed,2=excluded,3=test,4=alarm,5=fault |
| panel.<pan>.line.<lin>.sensor.<sens> | include | W | include sensor |
| exclude | W | exclude sensor | |
| panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.active | 0 | R | module is not active |
| 1 | R | module is active | |
| panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.excluded | 0 | R | module is not excluded |
| 1 | R | module is excluded | |
| panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.fault | 0 | R | module is not faulty |
| 1 | R | module is faulty | |
| panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.normal | 0 | R | module is not in normal mode |
| 1 | R | module is in normal mode | |
| panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.not.programmed | 0 | R | module is programmed |
| 1 | R | module is not programmed | |
| panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.test | 0 | R | module is not in test |
| 1 | R | module is in test | |
| panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr>.status | 0,1,2,3,4,5 | R | module status numeric value. 0=normal,1=not programmed,2=excluded,3=test,4=active,5=fault |
| panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr> | include | W | include module |
| exclude | W | exclude module | |
| panel.<pan>.line.<lin>.module.<mode>.subaddr.<addr> | 0 | W | deactivate module |
| 1 | W | activate module |
UISET Actions
Section titled “UISET Actions”| ID | Attribute | Set to | |
|---|---|---|---|
| <datapoint_id>.name | <String> | name assigned to <datapoint_id> has specified in the notifieresibm.ini file
| |
| panel.<pan>.line.<lin>.sensor.<sens>.analogval | value | analog value of panel.<pan>.line.<lin>.sensor.<sens>
| |
| version | value | panel firmware version | |
| global.model | value | panel model | |
| connection | visible | true | when datapoint connection = offline |
| false | when datapoint connection = online | ||
| <datapoint_id>.1 | visible | true | when datapoint with ID <datapoint_id> has value '1' |
| false | when datapoint with ID <datapoint_id> has value '0' | ||
| <datapoint_id>.0 | visible | true | when datapoint with ID <datapoint_id> has value '0' |
| false | when datapoint with ID <datapoint_id> has value '1' | ||
Release Notes
Section titled “Release Notes”3.10.1
Section titled “3.10.1”- bug fix: global.hardware.key.present was 1 even when the hardware key was not present
- bug fix: polling was not stopped when the Modbus license was missing
- bug fix: connection datapoint was set to online even if errors were encountered on some panels or lines
- connection datapoint is set to offline when the Modbus license is missing
- bug fix: panel model ma1000-01 was reported as am8200
- bug fix: panel model was written to the global.hardware.key.present UI object
- bug fix: wrong panel firmware version in the version datapoint and UI object
- added global.hardware.key.register datapoint
3.10.0
Section titled “3.10.0”- added pollinterval and readpause attributes
- added zone inclusion and exclusion commands
- bug fix: connection datapoint was set to online at startup even with read errors present
- added attributes maxpanelsnumber and maxlinesnumber
- initial release