Inim

From HSYCO
Revision as of 13:41, 23 December 2013 by Hsyco (talk | contribs) (→‎Options)
Jump to navigation Jump to search

Inim SmartLiving panels are multi-area intrusion detection systems. The integration with HSYCO can be accomplished via direct control through the RS-232 port on the board.

Communication

Employ a female-female RS-232 crossed cable to connect the panel directly to HSYCO or to an Ethernet/RS-232 gateway.

RS-232 parameters:

Baud rate 57600
Data bits 8
Stop bit 1
Parity none
Flow control none

HSYCO Configuration

Options

ID Default Values Description
gui true true enable support for the UI object, UISET actions and USER commands
false disable UI support
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
logsize 50 n ≥ 0 the number of log lines to display in the UI object
pollinterval 4 n > 0 the data acquisition interval, in seconds
mod 515 the panel model to control. This option is required
1050
10100
pin <code> use the specified user code to perform operations that require user authentication. If this option is not specified it will be required to manually insert the pin every time such operations are performed

inim.ini

The guardall.ini file is a specific configuration file located in the root directory. Here you can define the names of the groups so that they will be automatically added to the user interface. Add a new line for each group using this format:

<io_server_id>.group.<n> = <name>

For instance:

guard.group.1 = Kitchen
guard.group.2 = Living room

Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
armed 0 R all groups are disarmed
W disarm all groups
1 R the system is (partially) armed
W arm all groups
alarm 0 R the system is not in a alarm state
1 R the system is in a alarm state
tamper 0 R the system is not in a tamper state
1 R the system is in a tamper state
panel.tamper 0 R the panel is not tampered
1 R the panel is tampered
bell.tamper 0 R the bell is not tampered
1 R the bell is tampered
low.volts 0 R voltage ok
1 R low voltage detected
sounder 0 R the sounder is inactive
1 R the sounder is active
audio 0 R the audio signal of the panel is inactive
1 R the audio signal of the panel is active
strobe 0 R the strobe is inactive
1 R the strobe is active
mains.fail 0 R no mains fail
1 R mains fail
power.fail 0 R no power fail
1 R power fail
battery.fail 0 R no battery fail
1 R battery fail
fuse.1.fault 0 R fuse 1 is working
1 R fuse 1 in fault
fuse.2.fault 0 R fuse 2 is working
1 R fuse 2 in fault
fuse.3.fault 0 R fuse 3 is working
1 R fuse 3 in fault
line.fault 0 R communication line is working
1 R communication line in fault
c<n>.name <text> R the name of circuit <n> is set to <text>
g<n>.name <text> R the name of group <n> is set to <text>
g<n>.armed 0 R group <n> is disarmed
W disarm group <n>
1 R group <n> is armed
W arm group <n>
c<n>.alarm 0 R circuit <n> is not in alarm state
1 R circuit <n> is in alarm state
c<n>.tamper.alarm 0 R circuit <n> is not in tamper alarm
1 R circuit <n> is in tamper alarm
c<n>.open 0 R circuit <n> is closed
1 R circuit <n> is open
c<n>.tamper 0 R circuit <n> is not tampered
1 R circuit <n> is tampered
c<n>.fault 0 R circuit <n> is working properly
1 R circuit <n> is faulty
c<n>.bypassed 0 R circuit <n> is not bypassed
W unbypass circuit <n>
1 R circuit <n> is bypassed
W bypass circuit <n>
c<n>.isolated 0 R circuit <n> is not isolated
W un-isolate circuit <n>
1 R circuit <n> is isolated
W isolate circuit <n>
c<n>.soaked 0 R circuit <n> is not soaked
W un-soak circuit <n>
1 R circuit <n> is soaked
W soak circuit <n>
c<n>.status <status_values> R the status of circuit <n> is set to the reported values
c<n>.attributes <attributes_values> R the attributes of circuit <n> are set to the reported values
c<n>.resistance <value> R the measured resistance on circuit <n> is <value> ohm
>20k R the measured resistance on circuit <n> is greater than 20 K-ohm
k<n>.tamper 0 R keypad <n> is not tampered
1 R keypad <n> is tampered
k<n>.fault 0 R keypad <n> is working properly
1 R keypad <n> is faulty
logon.<n> <user_num> R user with number <user_num> logged in from keypad <n>
error R wrong pin entered in keypad <n>
system reset W reset alarms
Circuit status values
Value Description
A alarm/open
B alarm/open and tamper
E latched alarm and tamper
M marginal clear
m marginal alarm
N normal
T tamper
L latched alarm
F fault/no answer
X Auxiliary alarm
Circuit attributes values
Value Description
B bypassed circuit
I isolated circuit
S soak failed
T soaked circuit
Y temporarily bypassed circuit
Q temporarily isolated circuit
H circuit in shunt
A existing circuit
M multi-alarm
F bank reset failed/door forced
L locked
O open

Attributes can be combined together, for instance if a circuit is both isolated and bypassed, the attribute value will be “BI”.

User Interface

Guardall Object

The user interface for the Guardall multi-area intrusion detection system:

Guardall UI Object 1.png Guardall UI Object 2.png Guardall UI Object 3.png

The Guardall object is listed in the Project Editor’s new object list only when at least one Guardall I/O Server is defined.


Parameters

  • server id: the server ID
  • position: the object's position. Use the pixels or rows and columns coordinates format

Syntax

(guardall <server id>; <position>)

E.g.

(guardall serverid; x10y20)

UISET Actions

ID Attribute Set to
log value latest security log lines (as many as specified by the 'logsize' option)
log0 value latest line of the security log when a new entry is added, set back to blank after a short period
c<n>.name value name assigned to circuit <n> or its number if no name is defined
connection.label visible true when datapoint connection = offline
false when datapoint connection = online
<datapoint_id>.label.1 visible true when datapoint with ID <datapoint_id> has value '1'
false when datapoint with ID <datapoint_id> has value '0'
<datapoint_id>.label.0 visible true when datapoint with ID <datapoint_id> has value '0'
false when datapoint with ID <datapoint_id> has value '1'

USER Commands

Name Param Action
armed 0 disarm all groups
1 arm all groups
g<n>.armed 0 disarm group <n>
1 arm group <n>
c<n>.bypassed 0 unbypass zone <n>
1 bypass zone <n>
c<n>.isolated 0 un-isolate zone <n>
1 isolate zone <n>
c<n>.soaked 0 un-soak zone <n>
1 soak zone <n>
system reset reset alarms