Difference between revisions of "Hidedgesolo"

From HSYCO
Jump to navigation Jump to search
(Created page with "The HID Edge solo ESR40, ESRP40, ES400 are single-door IP access control solution. This driver allows the integration of HID Edge Solo devices by using a TCP/IP connection. Mo...")
 
 
(37 intermediate revisions by 3 users not shown)
Line 1: Line 1:
The HID Edge solo ESR40, ESRP40, ES400 are single-door IP access control solution. This driver allows the integration of HID Edge Solo devices by using a TCP/IP connection. More than one device can be controlled at the same time.
+
The [http://www.hidglobal.com HID Edge Solo] '''ESR40, ESRP40, ES400''' are single-door IP access control solutions.  
 +
 
 +
This I/O Server allows the integration of HID Edge Solo devices by using a TCP/IP connection.  
 +
 
 +
More than one device can be controlled at the same time.
  
 
[[Category:I/O Server]]
 
[[Category:I/O Server]]
 +
 +
== HID Edge Solo Configuration ==
 +
 +
The HID Edge Solo can be connected to a POE switch or to a normal ethernet switch. In this case the power supply must be provided with an external adapter.
 +
First of all, assign a static IP address to the Edge Solo, then it’s mandatory to disable the SSL/TLS encryption in the installer settings interface.
 +
 +
[[File:hidedgesolo1.png]]
 +
 +
== HSYCO Configuration ==
 +
Add an HIDEDGESOLO I/O Server in the [[Settings#I/O Servers|I/O Servers section of the Settings]] and set its parameters:
 +
 +
=== Communication ===
 +
*'''IP Address''': IP address configured on the device
 +
*'''IP Port''': TCP/IP port to use, leave blank for default port 80.
 +
 +
=== Authentication ===
 +
*'''User''': username set in the installer settings
 +
*'''Password''': password set in the installer settings.
 +
 +
=== High Availability ===
 +
*'''Shutdown when inactive''': defaults to true.
 +
 +
== Datapoints ==
 +
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 +
 +
|-
 +
 +
|rowspan="2" |connection
 +
|online
 +
|R
 +
|connection established
 +
|-
 +
|offline
 +
|R
 +
|HSYCO can't connect to the panel
 +
|-
 +
|card.notfound
 +
|<nowiki><code></nowiki>
 +
|R
 +
|badge <nowiki><code></nowiki> not found
 +
|-
 +
|pin.notfound
 +
|<pin>
 +
|R
 +
|<pin> not found
 +
|-
 +
|access.granted
 +
|<surname>
 +
|R
 +
|access granted to the user with surname <surname>
 +
|-
 +
|access.granted.extended
 +
|<surname>
 +
|R
 +
|access granted extended to the user with surname <surname>
 +
|-
 +
|access.denied.schedule
 +
|<surname>
 +
|R
 +
|access denied because badge/pin of the user <surname> was used outside scheduled time interval
 +
|-
 +
|access.denied.expired
 +
|<surname>
 +
|R
 +
|access denied because badge/pin of the user <surname> is expired
 +
|-
 +
|card.notassigned
 +
|<nowiki><code></nowiki>
 +
|R
 +
|access denied because the badge <nowiki><code></nowiki> is not assigned to an user.
 +
|-
 +
|access.denied.pin.expired
 +
|<surname>
 +
|R
 +
|access denied because the pin assigned to the user <surname> is expired
 +
|-
 +
|rowspan="2" |alarm.acknowledged
 +
|0
 +
|R
 +
|alarms reset
 +
|-
 +
|1
 +
|R
 +
|normal conditions
 +
|-
 +
|rowspan="2" |door.lock.schedule
 +
|false
 +
|R
 +
|normal conditions
 +
|-
 +
|true
 +
|R
 +
|door locked with a scheduled command
 +
|-
 +
|rowspan="2" |door.unlock.schedule
 +
|false
 +
|R
 +
|normal conditions
 +
|-
 +
|true
 +
|R
 +
|door unlocked with a scheduled command
 +
|-
 +
|rowspan="2" |alarm.door.forced
 +
|unset
 +
|R
 +
|normal conditions
 +
|-
 +
|set
 +
|R
 +
|door forced alarm
 +
|-
 +
|rowspan="2" |alarm.tamper
 +
|unset
 +
|R
 +
|normal conditions
 +
|-
 +
|set
 +
|R
 +
|tamper alarm
 +
|-
 +
|rowspan="2" |access.granted.manual
 +
|false
 +
|R
 +
|normal conditions
 +
|-
 +
|true
 +
|R
 +
|manual access granted
 +
|-
 +
|rowspan="2" |door.unlock
 +
|false
 +
|R
 +
|normal conditions
 +
|-
 +
|true
 +
|R
 +
|door unlocked
 +
|-
 +
|rowspan="2" |state.alarm.tamper
 +
|unset
 +
|R
 +
|normal conditions
 +
|-
 +
|set
 +
|R
 +
|tamper alarm
 +
|-
 +
|rowspan="2" |state.alarm.ac
 +
|unset
 +
|R
 +
|normal conditions
 +
|-
 +
|set
 +
|R
 +
|power supply failure
 +
|-
 +
|rowspan="2" |state.alarm.battery
 +
|unset
 +
|R
 +
|normal conditions
 +
|-
 +
|set
 +
|R
 +
|battery failure
 +
|-
 +
|rowspan="2" |state.alarm.door.held
 +
|unset
 +
|R
 +
|normal conditions
 +
|-
 +
|set
 +
|R
 +
|door held
 +
|-
 +
|rowspan="2" |state.alarm.door.held
 +
|unset
 +
|R
 +
|normal conditions
 +
|-
 +
|set
 +
|R
 +
|door held
 +
|-
 +
|rowspan="2" |state.alarm.door.forced
 +
|unset
 +
|R
 +
|normal conditions
 +
|-
 +
|set
 +
|R
 +
|door forced
 +
|-
 +
|state.name
 +
|<name>
 +
|R
 +
|the door's name
 +
|-
 +
|rowspan="2" |state.relay
 +
|unset
 +
|R
 +
|door relay closed
 +
|-
 +
|set
 +
|R
 +
|door relay open
 +
|-
 +
|rowspan="2" |state.relay.alert
 +
|unset
 +
|R
 +
|alert relay not active
 +
|-
 +
|set
 +
|R
 +
|alert relay active
 +
|-
 +
|rowspan="2" |state.relay.aux
 +
|unset
 +
|R
 +
|aux relay not active
 +
|-
 +
|set
 +
|R
 +
|aux relay active
 +
|-
 +
|command.access
 +
|grant
 +
|W
 +
|grant the access
 +
|-
 +
|rowspan="2" |command.door
 +
|lock
 +
|W
 +
|lock the door
 +
|-
 +
|unlock
 +
|W
 +
|unlock the door
 +
|-
 +
|command.alarm
 +
|stop
 +
|W
 +
|alarms reset
 +
|}
 +
 +
== Release Notes ==
 +
=== 3.4.0 ===
 +
*added support for two readers door controller
 +
 +
=== 3.0.0 ===
 +
*initial release
 +
 +
----
 +
 +
 +
''HID is a registered trademark of HID Global.''

Latest revision as of 11:27, 24 October 2014

The HID Edge Solo ESR40, ESRP40, ES400 are single-door IP access control solutions.

This I/O Server allows the integration of HID Edge Solo devices by using a TCP/IP connection.

More than one device can be controlled at the same time.

HID Edge Solo Configuration

The HID Edge Solo can be connected to a POE switch or to a normal ethernet switch. In this case the power supply must be provided with an external adapter. First of all, assign a static IP address to the Edge Solo, then it’s mandatory to disable the SSL/TLS encryption in the installer settings interface.

Hidedgesolo1.png

HSYCO Configuration

Add an HIDEDGESOLO I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • IP Address: IP address configured on the device
  • IP Port: TCP/IP port to use, leave blank for default port 80.

Authentication

  • User: username set in the installer settings
  • Password: password set in the installer settings.

High Availability

  • Shutdown when inactive: defaults to true.

Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
card.notfound <code> R badge <code> not found
pin.notfound <pin> R <pin> not found
access.granted <surname> R access granted to the user with surname <surname>
access.granted.extended <surname> R access granted extended to the user with surname <surname>
access.denied.schedule <surname> R access denied because badge/pin of the user <surname> was used outside scheduled time interval
access.denied.expired <surname> R access denied because badge/pin of the user <surname> is expired
card.notassigned <code> R access denied because the badge <code> is not assigned to an user.
access.denied.pin.expired <surname> R access denied because the pin assigned to the user <surname> is expired
alarm.acknowledged 0 R alarms reset
1 R normal conditions
door.lock.schedule false R normal conditions
true R door locked with a scheduled command
door.unlock.schedule false R normal conditions
true R door unlocked with a scheduled command
alarm.door.forced unset R normal conditions
set R door forced alarm
alarm.tamper unset R normal conditions
set R tamper alarm
access.granted.manual false R normal conditions
true R manual access granted
door.unlock false R normal conditions
true R door unlocked
state.alarm.tamper unset R normal conditions
set R tamper alarm
state.alarm.ac unset R normal conditions
set R power supply failure
state.alarm.battery unset R normal conditions
set R battery failure
state.alarm.door.held unset R normal conditions
set R door held
state.alarm.door.held unset R normal conditions
set R door held
state.alarm.door.forced unset R normal conditions
set R door forced
state.name <name> R the door's name
state.relay unset R door relay closed
set R door relay open
state.relay.alert unset R alert relay not active
set R alert relay active
state.relay.aux unset R aux relay not active
set R aux relay active
command.access grant W grant the access
command.door lock W lock the door
unlock W unlock the door
command.alarm stop W alarms reset

Release Notes

3.4.0

  • added support for two readers door controller

3.0.0

  • initial release


HID is a registered trademark of HID Global.