Elmo
EL.MO. ETR panels are multi-area intrusion detection systems. The integration with HSYCO can be accomplished via direct control through the RS232 port on the panel.
Contents
Communication
Employ the RS-232 cable provided with the EL.MO. panel to connect it directly to HSYCO or to an Ethernet/RS-232 gateway.
RS-232 parameters:
Baud rate | 9600 |
Data bits | 8 |
Stop bit | 1 |
Parity | none |
Flow control | none |
EL.MO. Configuration
For the newer "G2" series of EL.MO. ETR panels it is necessary to enable the compatibility mode for direct connection in the panel configuration. Refer to its manual for further details.
HSYCO Configuration
Options
ID | Default | Values | Description |
---|---|---|---|
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
offlinelogs | true | false | at startup request the log of all the events occurred while HSYCO was disconnected from the panel |
false | log only events occurred while HSYCO was connected to the panel | ||
pollinterval | 1 | n > 0 | the data acquisition interval, in seconds |
logsize | 20 | n ≥ 0 | the number of log lines to display in the UI object |
maxinput | n ≥ 0 | highest input number among the inputs used on the panel. If not specified all the available inputs will be included. This option is recommended to improve the I/O Server's performances | |
maxoutput | n ≥ 0 | highest output number among the outputs used on the panel. If not specified all the available outputs will be included. This option is recommended to improve the I/O Server's performances | |
maxgroup | n ≥ 0 | highest group number among the groups used on the panel. If not specified all the available groups will be included. This option is recommended to improve the I/O Server's performances | |
maxuser | n ≥ 0 | highest user number among the users used on the panel. If not specified all the available users will be included. This option is recommended to improve the I/O Server's performances | |
userlogs | false | true | generates logs that can be viewed with the userlist object, and can be selected to generate user events |
false | logs for userlist objects disabled. Normal text logs are generated even when this option is false |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
armed | 1 | R | at least one partition is armed |
W | arm all active areas | ||
0 | R | no partition is armed | |
W | disarm all active areas | ||
armed.max | 1 | R | at least one partition is armed in "max security" mode |
W | arm all active areas in "max security" mode | ||
0 | R | no partition is armed in "max security" mode | |
W | disarm all active areas in "max security" mode | ||
alarm | 1 | R | alarm state active |
0 | R | no active alarm | |
tamper | 1 | R | tamper alarm active |
0 | R | no active tamper alarm | |
i<n>.name | <text> | R | the name of input <n> is set to <text> |
i<n>.open | 1 | R | input <n> open |
0 | R | input <n> closed | |
i<n>.alarm | 1 | R | alarm on input <n> |
0 | R | no alarm on input <n> | |
i<n>.tamper | 1 | R | tamper alarm on input <n> |
0 | R | no tamper alarm on input <n> | |
i<n>.bypassed | 1 | R | input <n> bypassed |
W | bypass input <n> | ||
0 | R | input <n> enabled | |
W | enable input <n> | ||
o<n> | 1 | R | output <n> active |
W | activate output <n> | ||
0 | R | output <n> inactive | |
W | deactivate output <n> | ||
a<n>.<m>.name | <text> | R | the name of partition <m> of area <n> is set to <text> |
a<n>.armed | 1 | W | arm all partitions of area <n> |
0 | W | disarm all partitions of area <n> | |
a<n>.armed.max | 1 | W | arm all partitions of area <n> in "max security" mode |
0 | W | disarm all partitions of area <n> in "max security" mode | |
a<n>.<m>.armed | 1 | R | partition <m> of area <n> is armed |
W | arm partition <m> of area <n> | ||
0 | R | partition <m> of area <n> is disarmed | |
W | disarm partition <m> of area <n> | ||
a<n>.<m>.armed.max | 1 | R | partition <m> of area <n> is armed in "max security" mode |
W | arm partition <m> of area <n> in "max security" mode | ||
0 | R | partition <m> of area <n> is not armed in "max security" mode | |
W | disarm partition <m> of area <n> in "max security" mode | ||
usr<n>.name | <text> | R | the name of user <n> is set to <text> |
kp<n>.tamper | 1 | R | keypad <n> tampered |
0 | R | keypad <n> not tampered | |
fault.battery | 1 | R | battery fault active |
0 | R | no battery fault active | |
panel.tamper | 1 | R | panel tampered |
0 | R | panel not tampered | |
rel.tamper | 1 | R | tamper relay is on |
0 | R | tamper relay is off | |
rel.alarm | 1 | R | alarm relay is on |
0 | R | alarm relay is off |
User Interface
Elmo Object
The user interface for the EL.MO. multi-area intrusion detection system:
The (elmo) object is listed in the Project Editor’s new object list only when at least one EL.MO. I/O Server is defined
Parameters
- server id: the server ID
- area:
- position: the object's position. Use the pixels or rows and columns coordinates format
Syntax
(elmo <server id>; <area>; <position>)
E.g.
(elmo elm; 1; x10y20)
UISET Actions
You can use any object that accepts a text attribute, usually text, but also marquee and others, to display the status of the system according to the following table:
ID | Attribute | Set to | |
---|---|---|---|
log | value | latest security log lines (as many as specified by the 'logsize' option) | |
log0 | value | latest line of the security log when a new entry is added, set back to blank after a short period | |
i<n>.name | value | name assigned to input <n> | |
a<n>.<m>.name | value | name assigned to partition <m> of area <n> | |
usr<n>.name | value | name assigned to user <n> | |
connection.label | visible | true | when datapoint connection = offline |
false | when datapoint connection = online | ||
userlogs (only if option userlogs=true) |
labels | comma-separated list of log entries | |
parameters | comma-separated list of log entries with format "yyyyMMddHHmmss message" (e.g. "20141230154513 ALARM ZONE 1") | ||
<datapoint_id>.label.1 | visible | true | when datapoint with ID <datapoint_id> has value '1' |
false | when datapoint with ID <datapoint_id> has value '0' | ||
<datapoint_id>.label.0 | visible | true | when datapoint with ID <datapoint_id> has value '0' |
false | when datapoint with ID <datapoint_id> has value '1' |
USER Commands
The EL.MO. I/O Server supports a few system commands to be inserted within the Web interface. The controls are directly supported as ordinary user objects, by setting the name and param fields according to the following table:
Name | Param | Action |
---|---|---|
armed | 1 | arm all active areas |
0 | disarm all active areas | |
armed.max | 1 | arm all active areas in "max security" mode |
0 | disarm all active areas in "max security" mode | |
ID.a<n>.armed | 1 | arm all partitions of area <n> |
0 | disarm all partitions of area <n> | |
a<n>.armed.max | 1 | arm all partitions of area <n> in "max security" mode |
0 | disarm all partitions of area <n> in "max security" mode | |
a<n>.<m>.armed | 1 | arm partition <m> of area <n> |
0 | disarm partition <m> of area <n> | |
a<n>.<m>.armed.max | 1 | arm partition <m> of area <n> in "max security" mode |
0 | disarm partition <m> of area <n> in "max security" mode | |
i<n>.bypassed | 1 | bypass input <n> |
0 | enable input <n> | |
o<n> | 1 | activate output <n> |
0 | deactivate output <n> |