Boschmap
The Bosch MAP panels are multi-area intrusion detection systems.
The integration with HSYCO can be accomplished via Ethernet connection.
HSYCO Configuration
Section titled “HSYCO Configuration”Add a BOSCHMAP I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
Section titled “Communication”- IP Address: IP address of the panel
- IP Port: TCP/IP port to use, leave blank to use default port 6793.
Authentication
Section titled “Authentication”- Password: password set on for the BIS user. Leave blank to use the default password.
High Availability
Section titled “High Availability”- Shutdown when inactive: defaults to true.
Options
Section titled “Options”| ID | Default | Values | Description |
|---|---|---|---|
| startupevents | false | true | generate IO events also during the driver’s start-up phase |
| false | start generating events only after HSYCO is aligned with the current status of the system
| ||
| pollinterval | 30 | n > 0 | number of seconds between consecutive requests of the open status of points. A low value can overload the panel |
boschmap.ini
Section titled “boschmap.ini”The boschmap.ini file is a specific configuration file located in the root directory. This file is required to specify which areas and points are configured on the panel and to assign them a name.
Add a new line for each area followed by a new line for each point belonging to that area, using the following format:
<io_server_id>.<area_siid> = <name>
<io_server_id>.<point_siid> = <name>
where <area_siid>/<point_siid> is the security identifier of the area/point as specified in the configuration software of the panel.
For instance:
bsc.1.1.ControlPanelArea.1.1 = Control Panel
bsc.1.1.Area.2.4 = Internal area
bsc.1.1.Point.01001.006 = Front door
bsc.1.1.Point.01001.007 = Back door
bsc.1.1.Area.2.5 = External area
bsc.1.1.Point.01001.008 = Gate
specifies three areas: the Control Panel area with no points, an internal area with two points and an external area with one point.
Datapoints
Section titled “Datapoints”| ID | Value | R/W | Description |
|---|---|---|---|
| connection | online | R | connection established |
| offline | R | HSYCO can't connect to the panel | |
| alarm[Note 1] | 0 | R | no alarm |
| 1 | R | alarm active | |
| armed | 0 | R | no area armed |
| 1 | R | at least one area armed | |
| trouble[Note 1] | 0 | R | no trouble |
| 1 | R | trouble active | |
| tamper[Note 1] | 0 | R | no tamper |
| 1 | R | tamper active | |
| user.tamper[Note 1] | 0 | R | no user tamper |
| 1 | R | user tamper active | |
| <siid>.name | <name> | R | the name of the area/point is set to <name> |
| <area_siid>.armed | 0 | R | area disarmed |
| W | disarm the area | ||
| 1 | R | area all armed, delayed | |
| W | arm all the area, delayed | ||
| 2 | R | area all armed, delayed with bypass | |
| W | arm all the area, instant | ||
| 3 | R | area all armed, instant | |
| W | arm the area partially, delayed | ||
| 4 | R | area al armed, instant with bypass | |
| W | arm the area partially, instant | ||
| 5 | R | area partially armed, delayed | |
| W | custom-arm the area, delayed | ||
| 6 | R | area partially armed, delayed with bypass | |
| W | custom-arm the area, instant | ||
| 7 | R | area partially armed, instant | |
| W | arm all the area, delay zero | ||
| 8 | R | area partially armed, instant with bypass | |
| W | arm the area partially, delay zero | ||
| 9 | R | area custom armed, delayed | |
| W | custom-arm the area, delay zero | ||
| 10 | R | area custom armed, delayed with bypass | |
| 11 | R | area custom armed, instant | |
| 12 | R | area custom armed, instant with bypass | |
| <area_siid>.clearmem | 1 | W | clear active events (alarm, trouble etc) in the area |
| <x>.<y>.area.0.0.clearmem | 1 | W | clear active events from all level 2 areas (except Control Panel Areas) |
| <area_siid>.ready.arm.instant | 0 | R | the area is not ready to be armed instantly |
| 1 | R | the area is ready to be armed instantly | |
| <area_siid>.ready.arm.delay | 0 | R | the area is not ready to be armed with delay |
| 1 | R | the area is ready to be armed with delay | |
| <area_siid>.ready.disarm | 0 | R | the area is not ready to be disarmed |
| 1 | R | the area is ready to be disarmed | |
| <area_siid>.force.instant | 0 | R | the area is not ready to be force armed instantly |
| 1 | R | the area is ready to be force armed instantly | |
| <area_siid>.force.delay | 0 | R | the area is not ready to be force armed with delay |
| 1 | R | the area is ready to be force armed with delay | |
| <area_siid>.bypassed | 0 | R | no bypassed devices in this area |
| 1 | R | there are bypassed devices in this area | |
| <area_siid>.alarm | 0 | R | no active alarm |
| 1 | R | alarm active | |
| <area_siid>.trouble | 0 | R | no trouble |
| 1 | R | trouble active | |
| <area_siid>.tamper | 0 | R | no tamper |
| 1 | R | tamper active | |
| <point_siid>.blocked | 0 | R | point not blocked |
| 1 | R | point blocked | |
| <point_siid>.bypassed | 0 | R | point not bypassed |
| W | unbypass point | ||
| 1 | R | point bypassed swinger | |
| W | bypass point | ||
| 2 | R | point bypassed auto | |
| 3 | R | point bypassed force | |
| 4 | R | point bypassed manual | |
| <point_siid>.open | 0 | R | point closed |
| 1 | R | point open | |
| read | W | request the reading of the point's open state | |
| <point_siid>.alarm[Note 2] | 0 | R | no alarm |
| 1 | R | alarm | |
| <point_siid>.holdup[Note 2] | 0 | R | no holdup alarm |
| 1 | R | holdup alarm | |
| <point_siid>.duress[Note 2] | 0 | R | no duress alarm |
| 1 | R | duress alarm | |
| <point_siid>.tamper[Note 2] | 0 | R | no tamper alarm |
| 1 | R | tamper alarm | |
| <device_siid>.tamper[Note 2] | 0 | R | no tamper alarm |
| 1 | R | device tampered | |
| <device_siid>.trouble[Note 2] | 0 | R | no trouble |
| 1 | R | trouble on device | |
| <device_siid>.alarm[Note 2] | 0 | R | no alarm |
| 1 | R | alarm on device | |
| <device_siid>.active[Note 2] | 0 | R | device deactivated |
| 1 | R | device active |
- Note 1
- These datapoints are only updated after the startup phase, i.e. events are generated only for events occurring after the driver is online.
- Note 2
- These datapoints, if their value is 1, generate events at startup even if the startupevents option is set to false.
Release Notes
Section titled “Release Notes”- added "clearmem" datapoints
- added "armed" datapoint
- improved communication error handling
- initial version release