Networx is a multi-area security system. The integration with HSYCO can be accomplished via direct control through their serial or ethernet interfaces.
Contents
Communication
RS-232 parameters:
Baud rate | same as configured on panel (default 9600) |
Data bits | 8 |
Stop bit | 1 |
Parity | none |
Flow control | none |
Networx Configuration
The panel must be previously configured to have the serial port enabled and to use the binary control protocol. Refer to its configuration manual for more details.
HSYCO Configuration
Add a Networx I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- Comm ID: select the comm port connected to the panel.
High Availability
- Shutdown when inactive: defaults to true.
Options
ID | Default | Values | Description |
---|---|---|---|
pin | <code> | 4 or 6-digits code. Use the specified PIN code to perform operations that require user authentication. If this option is not specified it will be required to manually insert the pin every time such operations are performed | |
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
pollinterval | 3 | n > 0 | the data acquisition interval, in seconds |
logsize | 20 | n ≥ 0 | the number of log lines to display in the UI object |
maxzone | 168 | n > 0 | highest zone number among the zones used on the panel |
networx.ini
The networx.ini file is a specific configuration file located in the root directory. Here you can define the names of the users so that they will be automatically added to the user interface. Add a new line for each user using this format:
<io_server_id>.user.<n> = <name>
For instance:
nx.user.1 = Bob nx.user.2 = Alice
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
alarm | 0 | R | no partition is alarmed |
1 | R | at least one partition is alarmed | |
armed | 0 | R | all partitions are disarmed |
W | disarm all partitions | ||
1 | R | the system is (partially) armed | |
away | W | arm all partitions in away mode | |
stay | W | arm all partitions in stay mode | |
auto | W | initiate auto-arm for all partitions | |
p<n>.armed | 0 | R | partition <n> is disarmed |
W | disarm partition <n> | ||
away | R | partition <n> is armed in away mode | |
W | arm partition <n> in away mode | ||
stay | R | partition <n> is armed in stay mode | |
W | arm partition <n> in stay mode | ||
auto | W | initiate auto-arm on partition <n> | |
p<n>.alarm | 0 | R | partition <n> is not in an alarm state |
1 | R | partition <n> is in an alarm state | |
p<n>.tamper | 0 | R | no tamper condition for partition <n> |
1 | R | partition <n> has been tampered | |
p<n>.last.user | <num> | R | last user number entered was <num> |
p<n>.fire | 0 | R | no fire on partition <n> |
1 | R | fire on partition <n> | |
p<n>.fire.trouble | 0 | R | no fire trouble on partition <n> |
1 | R | fire trouble on partition <n> | |
p<n>.buzzer | 0 | R | buzzer off on partition <n> |
1 | R | buzzer on on partition <n> | |
W | start buzzer on partition <n> | ||
p<n>.tlm.fault | 0 | R | TLM ok |
1 | R | TLM memory fault | |
p<n>.instant | 0 | R | instant flag not set on partition <n> |
1 | R | instant flag set on partition <n> | |
p<n>.siren | 0 | R | siren off on partition <n> |
1 | R | siren on on partition <n> | |
p<n>.steady.siren | 0 | R | steady siren off on partition <n> |
1 | R | steady siren on on partition <n> | |
p<n>.alarm.mem | 0 | R | alarm memory flag not set on partition <n> |
1 | R | alarm memory flag set on partition <n> | |
p<n>.cancel | 0 | R | no cancel command entered on partition <n> |
1 | R | cancel command entered on partition <n> | |
W | issue cancel command | ||
p<n>.exit.silent | 0 | R | silent exit disabled on partition <n> |
1 | R | silent exit enabled on partition <n> | |
W | enable silent exit for this arm cycle on partition <n> | ||
p<n>.chime.mode | 0 | R | chime mode off on partition <n> |
1 | R | chime mode on on partition <n> | |
toggle | W | toggle chime mode on partition <n> | |
p<n>.entry | 0 | R | entry inactive on partition <n> |
1 | R | entry active on partition <n> | |
p<n>.delay.exp | 0 | R | delay expiration warning off |
1 | R | delay expiration warning on | |
p<n>.exit.1 | 0 | R | exit 1 inactive on partition <n> |
1 | R | exit 1 active on partition <n> | |
p<n>.exit.2 | 0 | R | exit 2 inactive on partition <n> |
1 | R | exit 2 active on partition <n> | |
p<n>.exit.error | 0 | R | exit error not triggered on partition <n> |
1 | R | exit error triggered on partition <n> | |
p<n>.night.mode | 0 | R | night mode inactive on partition <n> |
1 | R | night mode active on partition <n> | |
p<n>.reexit | 0 | R | re-exit inactive on partition <n> |
1 | R | re-exit active on partition <n> | |
p<n>.force.arm | 0 | R | no force arm triggered on partition <n> |
1 | R | force arm triggered by auto arm on partition <n> | |
p<n>.arm.ready | 0 | R | partition <n> not ready to arm |
1 | R | partition <n> ready to arm | |
p<n>.force.arm.ready | 0 | R | partition <n> not ready to force arm |
1 | R | partition <n> ready to force arm | |
p<n>.chime | 0 | R | chime off on partition <n> |
1 | R | chime on on partition <n> | |
p<n>.error.beep | 0 | R | error beep off on partition <n> |
1 | R | error beep on on partition <n> | |
p<n>.tone | 0 | R | activation tone off on partition <n> |
1 | R | activation tone on on partition <n> | |
p<n>.entry.1 | 0 | R | entry 1 inactive on partition <n> |
1 | R | entry 1 active on partition <n> | |
p<n>.phone.1.alarm | 0 | R | no alarm sent using phone number 1 on partition <n> |
1 | R | alarm sent using phone number 1 on partition <n> | |
p<n>.phone.2.alarm | 0 | R | no alarm sent using phone number 2 on partition <n> |
1 | R | alarm sent using phone number 2 on partition <n> | |
p<n>.phone.3.alarm | 0 | R | no alarm sent using phone number 3 on partition <n> |
1 | R | alarm sent using phone number 3 on partition <n> | |
p<n>.keyswitch.armed | 0 | R | keyswitch not armed on partition <n> |
1 | R | keyswitch armed on partition <n> | |
z<n>.name | <text> | R | name of zone <n> is set to <text> |
z<n>.open | 0 | R | zone <n> is closed |
1 | R | zone <n> is open | |
z<n>.tamper | 0 | R | zone <n> is not tampered |
1 | R | zone <n> is tampered | |
z<n>.trouble | 0 | R | zone <n> OK |
1 | R | troubles on zone <n> | |
z<n>.bypassed | 0 | R | zone <n> not bypassed |
1 | R | zone <n> bypassed | |
toggle | W | toggle the bypass status on zone <n> | |
z<n>.inhibited | 0 | R | zone <n> not inhibited |
1 | R | zone <n> inhibited | |
z<n>.battery.low | 0 | R | zone <n> battery OK |
1 | R | zone <n> battery low | |
z<n>.supervision.loss | 0 | R | supervision OK on zone <n> |
1 | R | loss of supervision on zone <n> | |
z<n>.alarm.mem | 0 | R | alarm memory flag not set on zone <n> |
1 | R | alarm memory flag set on zone <n> | |
z<n>.bypass.mem | 0 | R | bypass memory flag not set on zone <n> |
1 | R | bypass memory flag set on zone <n> | |
user<n>.name | <text> | R | name of user <n> is set to <text> |
comm.fail | 0 | R | communication OK |
1 | R | communication failure | |
fuse.fault | 0 | R | fuse OK |
1 | R | fuse fault | |
panel.tamper | 0 | R | panel box not tampered |
1 | R | panel box tampered | |
siren.tamper | 0 | R | siren OK |
1 | R | siren tampered | |
battery.low | 0 | R | battery OK |
1 | R | battery low | |
ac.fail | 0 | R | AC OK |
1 | R | AC failure | |
expander.tamper | 0 | R | expander box not tampered |
1 | R | expander box tampered | |
expander.ac.fail | 0 | R | expander’s AC OK |
1 | R | expander’s AC failure | |
expander.battery.low | 0 | R | expander’s battery OK |
1 | R | expander’s battery low | |
expander.fault | 0 | R | expander OK |
1 | R | general fault for the expander | |
buzzer | 0 | R | global buzzer off |
1 | R | global buzzer on | |
siren | 0 | R | global siren off |
1 | R | global siren on | |
steady.siren | 0 | R | global steady siren off |
1 | R | global steady siren on | |
bus.fault | 0 | R | bus line OK |
1 | R | bus device had line seized | |
ac.power | 0 | R | AC power off |
1 | R | AC power on | |
battery.low.mem | 0 | R | low battery memory flag not set |
1 | R | low battery memory flag set | |
powerup.delay | 0 | R | no power up delay in progress |
1 | R | power up delay in progress | |
walk.test | 0 | R | walk-test mode off |
W | stop walk-test mode | ||
1 | R | walk-test mode active | |
W | start walk-test mode | ||
time.loss | 0 | R | system time ok |
1 | R | loss of system time | |
aux1 p<n>.aux1 |
1 | W | activate auxiliary function 1 |
aux2 p<n>.aux2 |
1 | W | activate auxiliary function 2 |
panic p<n>.panic |
fire | W | issue the fire panic command |
medical | W | issue the medical panic command | |
police | W | issue the police panic command | |
smoke p<n>.smoke |
reset | W | smoke detector reset |
test p<n>.test |
1 | W | perform test |
command | restart | W | restart the driver |
clock | read | W | request the reading of the panel’s clock value |
<val> | R | the panel’s clock is set to <val>. The used format is "yyyy-mm-dd hh:mm:ss" (e.g. 2012-08-30 16:30:00). This datapoint is only updated after a request with the command "clock = read" | |
W | set the panel’s clock to <val>. One of the following formats must be used:
| ||
x10.<house>.<unit> | on | W | send the on command to the unit with the specified address in the specified house (e.g. x10.a.2 addresses unit 2 of house A) |
off | W | send the off command to the unit with the specified address in the specified house (e.g. x10.a.2 addresses unit 2 of house A) | |
dim | W | send the dim command to the unit with the specified address in the specified house (e.g. x10.a.2 addresses unit 2 of house A) | |
bright | W | send the bright command to the unit with the specified address in the specified house (e.g. x10.a.2 addresses unit 2 of house A) | |
x10.<house>.all | off | W | send the off command to the all the units in the specified house (e.g. x10.b.all) |
x10.<house>.lights | on | W | send the on command to all the light units in the specified house |
off | W | send the off command to all the light units in the specified house |
User Interface
Networx Object
UISET Actions
ID | Attribute | Set to | |
---|---|---|---|
log | value | latest security log lines (as many as specified by the 'logsize' option) | |
log0 | value | latest line of the security log when a new entry is added, set back to blank after a short period | |
z<n>.name | value | name assigned to zone <n> (base or double) or its number if no name is defined | |
p<n>.last.user | value | ID of the last user who logged in on partition <n> | |
user<n>.name | value | name assigned to user <n> | |
connection.label | visible | true | when datapoint connection = offline |
false | when datapoint connection = online | ||
p<n>.armed.0.label | visible | true | when partition <n> is disarmed |
false | when partition <n> is armed | ||
p<n>.armed.away.label | visible | true | when partition <n> is armed in "away" mode |
false | when partition <n> is not armed in "away" mode | ||
p<n>.armed.stay.label | visible | true | when partition <n> is armed in "stay" mode |
false | when partition <n> is not armed in "stay" mode | ||
<datapoint_id>.1.label | visible | true | when datapoint with ID <datapoint_id> has value '1' |
false | when datapoint with ID <datapoint_id> has value '0' | ||
<datapoint_id>.0.label | visible | true | when datapoint with ID <datapoint_id> has value '0' |
false | when datapoint with ID <datapoint_id> has value '1' |
USER Commands
Name | Param | Action |
---|---|---|
armed[Note] | 0 | disarm all partitions |
stay | arm all partitions in "stay" mode | |
away | arm all partitions in "away" mode | |
auto | initiate auto-arm on all partitions | |
p<n>.armed[Note] | 0 | disarm partition <n> |
stay | arm partition <n> in "stay" mode | |
away | arm partition <n> in "away" mode | |
auto | initiate auto-arm on partition <n> | |
p<n>.cancel[Note] | 1 | issue cancel command on partition <n> |
p<n>.buzzer | 1 | start buzzer on partition <n> |
p<n>.exit.silent | 1 | enable silent exit for this arm cycle on partition <n> |
Z<n>.bypassed | toggle | toggle the bypass status of zone <n> |
p<n>.chime.mode | toggle | toggle chime mode on partition <n> |
walk.test[Note] | 0 | stop walk-test mode |
1 | start walk-test mode | |
aux1 p<n>.aux1 |
1 | activate auxiliary function 1 |
aux2 p<n>.aux2 |
1 | activate auxiliary function 2 |
panic p<n>.panic |
fire | issue the fire panic command |
medical | issue the medical panic command | |
police | issue the police panic command
| |
smoke p<n>.smoke |
reset | smoke detector reset |
test p<n>.test |
1 | perform test |
command | restart | restarts the driver |
- Note
- To perform this operation it is necessary to enter the user code first. To enter the user code through the user interface use user buttons to create a virtual keypad and assign them name and param values according to this table:
Name | Param | Action |
---|---|---|
digit | {0 ... 9} | append the specified digit to the entered user code |
c | delete the last entered digit |
To visualize the number of entered digits use 4 or 6 text objects (depending on the number of digits used for user codes) and set their IDs to:
ID | Description |
---|---|
pin.<n> (0 ≤ <n> ≤ 5) |
shows the character '*' when the corresponding digit has been entered, shows '_' otherwise |
The entered code will be cleared after a short period of inactivity.
Log Files
A permanent record of all the log messages, also shown in the log page, is saved in a file called security.log in the logs/YYYY directory for the current year.
This file is never overwritten or deleted by HSYCO.
2014.03.21 14:50:40.010 - nx - Disarmed - Partition 1 2014.03.21 14:52:01.322 - nx - Walk test mode on 2014.03.21 14:53:17.687 - nx - Walk test mode off 2014.03.21 14:53:28.852 - nx - Bypass - [2] Zona 2 n 2014.03.21 14:53:29.998 - nx - Armed (stay) - Partition 1 2014.03.21 14:53:32.557 - nx - Bypass restore - [2] Zona 2 n 2014.03.21 14:53:33.698 - nx - Disarmed - Partition 1 2014.03.21 17:17:03.364 - nx - Online 2014.03.21 17:40:42.664 - nx - Bypass - [2] Zona 2 n 2014.03.21 17:40:43.859 - nx - Armed (stay) - Partition 1 2014.03.21 17:40:48.772 - nx - Bypass restore - [2] Zona 2 n 2014.03.21 17:40:50.067 - nx - Disarmed - Partition 1 2014.03.21 17:48:25.277 - nx - Bypass - [1] Zona 1 n 2014.03.21 17:48:26.729 - nx - Bypass restore - [1] Zona 1 n
Other information related to the driver are saved in the daily message.log files
Release Notes
3.6.0
- initial version release