Difference between revisions of "Hidedgesolo"
(32 intermediate revisions by 4 users not shown) | |||
Line 1: | Line 1: | ||
− | The HID Edge | + | The [http://www.hidglobal.com HID Edge Solo] '''ESR40, ESRP40, ES400''' are single-door IP access control solutions. |
− | + | This I/O Server allows the integration of HID Edge Solo devices by using a TCP/IP connection. | |
− | + | More than one device can be controlled at the same time. | |
− | + | [[Category:I/O Server]] | |
− | == HID Edge Solo | + | == HID Edge Solo Configuration == |
The HID Edge Solo can be connected to a POE switch or to a normal ethernet switch. In this case the power supply must be provided with an external adapter. | The HID Edge Solo can be connected to a POE switch or to a normal ethernet switch. In this case the power supply must be provided with an external adapter. | ||
− | First of all, assign | + | First of all, assign a static IP address to the Edge Solo, then it’s mandatory to disable the SSL/TLS encryption in the installer settings interface. |
[[File:hidedgesolo1.png]] | [[File:hidedgesolo1.png]] | ||
== HSYCO Configuration == | == HSYCO Configuration == | ||
+ | Add an HIDEDGESOLO I/O Server in the [[Settings#I/O Servers|I/O Servers section of the Settings]] and set its parameters: | ||
− | + | === Communication === | |
+ | *'''IP Address''': IP address configured on the device | ||
+ | *'''IP Port''': TCP/IP port to use, leave blank for default port 80. | ||
− | + | === Authentication === | |
− | + | *'''User''': username set in the installer settings | |
− | + | *'''Password''': password set in the installer settings. | |
− | |||
− | |||
− | |||
− | |||
− | + | === High Availability === | |
− | + | *'''Shutdown when inactive''': defaults to true. | |
== Datapoints == | == Datapoints == | ||
+ | |||
+ | If two readers are connected to the Edge Solo controller, the reader specific data points have a 0. or 1. prefix to identify each reader. | ||
{| class="wikitable" | {| class="wikitable" | ||
Line 47: | Line 48: | ||
|R | |R | ||
|HSYCO can't connect to the panel | |HSYCO can't connect to the panel | ||
+ | |- | ||
+ | |card.notfound | ||
+ | |<nowiki><code></nowiki> | ||
+ | |R | ||
+ | |badge <nowiki><code></nowiki> not found | ||
+ | |- | ||
+ | |pin.notfound | ||
+ | |<pin> | ||
+ | |R | ||
+ | |<pin> not found | ||
+ | |- | ||
+ | |access.granted | ||
+ | |<surname> | ||
+ | |R | ||
+ | |access granted to the user with surname <surname> | ||
+ | |- | ||
+ | |access.granted.extended | ||
+ | |<surname> | ||
+ | |R | ||
+ | |access granted extended to the user with surname <surname> | ||
+ | |- | ||
+ | |access.denied.schedule | ||
+ | |<surname> | ||
+ | |R | ||
+ | |access denied because badge/pin of the user <surname> was used outside scheduled time interval | ||
+ | |- | ||
+ | |access.denied.expired | ||
+ | |<surname> | ||
+ | |R | ||
+ | |access denied because badge/pin of the user <surname> is expired | ||
+ | |- | ||
+ | |card.notassigned | ||
+ | |<nowiki><code></nowiki> | ||
+ | |R | ||
+ | |access denied because the badge <nowiki><code></nowiki> is not assigned to an user. | ||
+ | |- | ||
+ | |access.denied.pin.expired | ||
+ | |<surname> | ||
+ | |R | ||
+ | |access denied because the pin assigned to the user <surname> is expired | ||
+ | |- | ||
+ | |rowspan="2" |alarm.acknowledged | ||
+ | |0 | ||
+ | |R | ||
+ | |alarms reset | ||
+ | |- | ||
+ | |1 | ||
+ | |R | ||
+ | |normal conditions | ||
+ | |- | ||
+ | |rowspan="2" |door.lock.schedule | ||
+ | |false | ||
+ | |R | ||
+ | |normal conditions | ||
+ | |- | ||
+ | |true | ||
+ | |R | ||
+ | |door locked with a scheduled command | ||
+ | |- | ||
+ | |rowspan="2" |door.unlock.schedule | ||
+ | |false | ||
+ | |R | ||
+ | |normal conditions | ||
+ | |- | ||
+ | |true | ||
+ | |R | ||
+ | |door unlocked with a scheduled command | ||
+ | |- | ||
+ | |rowspan="2" |alarm.door.forced | ||
+ | |unset | ||
+ | |R | ||
+ | |normal conditions | ||
+ | |- | ||
+ | |set | ||
+ | |R | ||
+ | |door forced alarm | ||
+ | |- | ||
+ | |rowspan="2" |alarm.tamper | ||
+ | |unset | ||
+ | |R | ||
+ | |normal conditions | ||
+ | |- | ||
+ | |set | ||
+ | |R | ||
+ | |tamper alarm | ||
+ | |- | ||
+ | |rowspan="2" |access.granted.manual | ||
+ | |false | ||
+ | |R | ||
+ | |normal conditions | ||
+ | |- | ||
+ | |true | ||
+ | |R | ||
+ | |manual access granted | ||
+ | |- | ||
+ | |rowspan="2" |door.unlock | ||
+ | |false | ||
+ | |R | ||
+ | |normal conditions | ||
+ | |- | ||
+ | |true | ||
+ | |R | ||
+ | |door unlocked | ||
+ | |- | ||
+ | |rowspan="2" |state.alarm.tamper | ||
+ | |unset | ||
+ | |R | ||
+ | |normal conditions | ||
+ | |- | ||
+ | |set | ||
+ | |R | ||
+ | |tamper alarm | ||
+ | |- | ||
+ | |rowspan="2" |state.alarm.ac | ||
+ | |unset | ||
+ | |R | ||
+ | |normal conditions | ||
+ | |- | ||
+ | |set | ||
+ | |R | ||
+ | |power supply failure | ||
+ | |- | ||
+ | |rowspan="2" |state.alarm.battery | ||
+ | |unset | ||
+ | |R | ||
+ | |normal conditions | ||
+ | |- | ||
+ | |set | ||
+ | |R | ||
+ | |battery failure | ||
+ | |- | ||
+ | |rowspan="2" |state.alarm.door.held | ||
+ | |unset | ||
+ | |R | ||
+ | |normal conditions | ||
+ | |- | ||
+ | |set | ||
+ | |R | ||
+ | |door held | ||
+ | |- | ||
+ | |rowspan="2" |state.alarm.door.held | ||
+ | |unset | ||
+ | |R | ||
+ | |normal conditions | ||
+ | |- | ||
+ | |set | ||
+ | |R | ||
+ | |door held | ||
+ | |- | ||
+ | |rowspan="2" |state.alarm.door.forced | ||
+ | |unset | ||
+ | |R | ||
+ | |normal conditions | ||
+ | |- | ||
+ | |set | ||
+ | |R | ||
+ | |door forced | ||
+ | |- | ||
+ | |state.name | ||
+ | |<name> | ||
+ | |R | ||
+ | |the door's name | ||
+ | |- | ||
+ | |rowspan="2" |state.relay | ||
+ | |unset | ||
+ | |R | ||
+ | |door relay closed | ||
+ | |- | ||
+ | |set | ||
+ | |R | ||
+ | |door relay open | ||
+ | |- | ||
+ | |rowspan="2" |state.relay.alert | ||
+ | |unset | ||
+ | |R | ||
+ | |alert relay not active | ||
+ | |- | ||
+ | |set | ||
+ | |R | ||
+ | |alert relay active | ||
+ | |- | ||
+ | |rowspan="2" |state.relay.aux | ||
+ | |unset | ||
+ | |R | ||
+ | |aux relay not active | ||
+ | |- | ||
+ | |set | ||
+ | |R | ||
+ | |aux relay active | ||
+ | |- | ||
+ | |command.access | ||
+ | |grant | ||
+ | |W | ||
+ | |grant the access | ||
+ | |- | ||
+ | |rowspan="2" |command.door | ||
+ | |lock | ||
+ | |W | ||
+ | |lock the door | ||
+ | |- | ||
+ | |unlock | ||
+ | |W | ||
+ | |unlock the door | ||
+ | |- | ||
+ | |command.alarm | ||
+ | |stop | ||
+ | |W | ||
+ | |alarms reset | ||
+ | |} | ||
+ | |||
+ | == Release Notes == | ||
+ | === 3.6.0 === | ||
+ | *added support for firmware version 2.0 | ||
+ | |||
+ | === 3.4.0 === | ||
+ | *added support for two readers door controller | ||
+ | |||
+ | === 3.0.0 === | ||
+ | *initial release | ||
− | + | ---- | |
− | |||
− | |||
− | |||
− | |||
− | + | ''HID is a registered trademark of HID Global.'' |
Latest revision as of 12:03, 18 April 2017
The HID Edge Solo ESR40, ESRP40, ES400 are single-door IP access control solutions.
This I/O Server allows the integration of HID Edge Solo devices by using a TCP/IP connection.
More than one device can be controlled at the same time.
Contents
HID Edge Solo Configuration
The HID Edge Solo can be connected to a POE switch or to a normal ethernet switch. In this case the power supply must be provided with an external adapter. First of all, assign a static IP address to the Edge Solo, then it’s mandatory to disable the SSL/TLS encryption in the installer settings interface.
HSYCO Configuration
Add an HIDEDGESOLO I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- IP Address: IP address configured on the device
- IP Port: TCP/IP port to use, leave blank for default port 80.
Authentication
- User: username set in the installer settings
- Password: password set in the installer settings.
High Availability
- Shutdown when inactive: defaults to true.
Datapoints
If two readers are connected to the Edge Solo controller, the reader specific data points have a 0. or 1. prefix to identify each reader.
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
card.notfound | <code> | R | badge <code> not found |
pin.notfound | <pin> | R | <pin> not found |
access.granted | <surname> | R | access granted to the user with surname <surname> |
access.granted.extended | <surname> | R | access granted extended to the user with surname <surname> |
access.denied.schedule | <surname> | R | access denied because badge/pin of the user <surname> was used outside scheduled time interval |
access.denied.expired | <surname> | R | access denied because badge/pin of the user <surname> is expired |
card.notassigned | <code> | R | access denied because the badge <code> is not assigned to an user. |
access.denied.pin.expired | <surname> | R | access denied because the pin assigned to the user <surname> is expired |
alarm.acknowledged | 0 | R | alarms reset |
1 | R | normal conditions | |
door.lock.schedule | false | R | normal conditions |
true | R | door locked with a scheduled command | |
door.unlock.schedule | false | R | normal conditions |
true | R | door unlocked with a scheduled command | |
alarm.door.forced | unset | R | normal conditions |
set | R | door forced alarm | |
alarm.tamper | unset | R | normal conditions |
set | R | tamper alarm | |
access.granted.manual | false | R | normal conditions |
true | R | manual access granted | |
door.unlock | false | R | normal conditions |
true | R | door unlocked | |
state.alarm.tamper | unset | R | normal conditions |
set | R | tamper alarm | |
state.alarm.ac | unset | R | normal conditions |
set | R | power supply failure | |
state.alarm.battery | unset | R | normal conditions |
set | R | battery failure | |
state.alarm.door.held | unset | R | normal conditions |
set | R | door held | |
state.alarm.door.held | unset | R | normal conditions |
set | R | door held | |
state.alarm.door.forced | unset | R | normal conditions |
set | R | door forced | |
state.name | <name> | R | the door's name |
state.relay | unset | R | door relay closed |
set | R | door relay open | |
state.relay.alert | unset | R | alert relay not active |
set | R | alert relay active | |
state.relay.aux | unset | R | aux relay not active |
set | R | aux relay active | |
command.access | grant | W | grant the access |
command.door | lock | W | lock the door |
unlock | W | unlock the door | |
command.alarm | stop | W | alarms reset |
Release Notes
3.6.0
- added support for firmware version 2.0
3.4.0
- added support for two readers door controller
3.0.0
- initial release
HID is a registered trademark of HID Global.