Difference between revisions of "Contatto"

From HSYCO
Jump to navigation Jump to search
 
(117 intermediate revisions by the same user not shown)
Line 36: Line 36:
  
 
{{tip|A speed of 115200 bps is recommended to achieve good performance, particularly when the number of devices connected to the bus is large.}}
 
{{tip|A speed of 115200 bps is recommended to achieve good performance, particularly when the number of devices connected to the bus is large.}}
 +
 +
 +
=== High Availability ===
 +
*'''Shutdown when inactive''': defaults to false.
  
 
== HSYCO Configuration ==
 
== HSYCO Configuration ==
Line 92: Line 96:
 
|rowspan="3"|virtualpoints
 
|rowspan="3"|virtualpoints
 
|rowspan="3"|false
 
|rowspan="3"|false
|1 ... 2033
+
|1 ... 2032
 
|enables polling for the first n virtual points of the MCP. Enable this option only if you need to generate I/O events based on these virtual points
 
|enables polling for the first n virtual points of the MCP. Enable this option only if you need to generate I/O events based on these virtual points
 
|-
 
|-
Line 117: Line 121:
 
|rowspan="2"|false
 
|rowspan="2"|false
 
|≥ 0 (MODANA address)
 
|≥ 0 (MODANA address)
|enables the automatic display in the GUI of the total real power measured by a DFANA module connected to this MCP. Note that, if you have more than one MCP gateway, you should enable this option for one gateway only
+
|enables the automatic display in the GUI of the total real power measured by a MODANA or MODANAM module connected to this MCP. Note that, if you have more than one MCP gateway, you should enable this option for one gateway only
 
|-
 
|-
 
|false
 
|false
Line 209: Line 213:
 
</pre>
 
</pre>
  
== MCP Virtual Data Points and Registers ==
+
== MCP Data Points ==
  
The MCP implements 2032 virtual points for binary (on/off) data and 1024 registers for positive scalar values (0-65535). All the virtual points and the registers can optionally generate I/O events. You can also write to the virtual data points and registers using the IO action in EVENTS or ioSet() method in Java.
+
The MCP implements 2032 virtual points for binary (on/off) data and 1024 registers and counters for positive scalar values (0-65535). All virtual points, registers and counters can optionally generate I/O events. You can also write to the virtual data points, registers and counters using the IO action in EVENTS or ioSet() method in Java.
  
You cannot directly control the MCP virtual data points and registers using GUI objects.
+
You cannot directly control the MCP virtual data points, registers or counters using GUI objects.
  
 
To enable polling of the current state of the MCP’s virtual data points, enable the ''virtualpoints'' options in hsyco.ini.
 
To enable polling of the current state of the MCP’s virtual data points, enable the ''virtualpoints'' options in hsyco.ini.
Line 219: Line 223:
 
To enable polling of the current state of the MCP’s registers, enable the ''registers'' options in hsyco.ini.
 
To enable polling of the current state of the MCP’s registers, enable the ''registers'' options in hsyco.ini.
  
If you only have to write to virtual points or registers, enabling polling is not strictly required.  
+
To enable polling of the current state of the MCP’s counters, enable the ''counters'' options in hsyco.ini.
 +
 
 +
If you only have to write to virtual points, registers or counters, enabling polling is not strictly required.  
  
 
{| class="wikitable"
 
{| class="wikitable"
Line 226: Line 232:
 
!R/W
 
!R/W
 
!Description
 
!Description
 +
|-
 +
 +
|rowspan="2"|busfault
 +
|0
 +
|R
 +
|no bus fault detected
 +
|-
 +
|1
 +
|R
 +
|bus fault detected
 +
|-
 +
 +
|rowspan="2"|modulefault
 +
|0
 +
|R
 +
|no modules fault detected
 +
|-
 +
|1
 +
|R
 +
|modules fault detected
 
|-
 
|-
  
Line 241: Line 267:
 
|<x>
 
|<x>
 
|RW
 
|RW
|register <n> off (<n>: 0-1023) set to value <x> (<x>: 0-65535)
+
|register <n> (<n>: 0-1023) set to value <x> (<x>: 0-65535)
 +
|-
 +
 
 +
|c0.<n>
 +
|<x>
 +
|RW
 +
|counter <n> (<n>: 0-1023) set to value <x> (<x>: 0-65535)
 
|-
 
|-
  
Line 279: Line 311:
  
 
== CONTATTO Modules Events and Control ==
 
== CONTATTO Modules Events and Control ==
 +
 +
Each CONTATTO module has its own set of read-only or read-write data points, mapping the specific set of features.
 +
 +
All modules also have a  read-only "fault" data point, set to 1 if the MCP has detected a module fault condition, or 0 if the module is working normally.
 +
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 +
|-
 +
 +
|rowspan="2"|i<address>.fault
 +
|0
 +
|R
 +
|input module working normally
 +
|-
 +
|1
 +
|R
 +
|input module fault detected
 +
|-
 +
 +
|rowspan="2"|o<address>.fault
 +
|0
 +
|R
 +
|output module working normally
 +
|-
 +
|1
 +
|R
 +
|output module fault detected
 +
|-
 +
|}
 +
  
 
{| class="wikitable"
 
{| class="wikitable"
Line 285: Line 350:
 
|-
 
|-
  
|MOD8I/A 8
+
|MOD8I/A
|digital input module for NO contacts in modular housing
+
|8 digital input module for NO contacts in modular housing
 
|-
 
|-
|MOD32I/A
+
|MOD32I/A
 
|32 digital input module for NO contacts in modular housing
 
|32 digital input module for NO contacts in modular housing
 
|-
 
|-
|MOD32IN
+
|MOD32IL
 
|32 digital input module for NO contacts in modular housing
 
|32 digital input module for NO contacts in modular housing
 
|-
 
|-
|MOD8INP2/A
+
|MOD32IN
 +
|32 digital input module for NO contacts in modular housing
 +
|-
 +
|MOD8INP2/A
 
|8 digital input module for NO contacts
 
|8 digital input module for NO contacts
 
|-
 
|-
|MOD8INP2/C
+
|MOD8INP2/C
 
|8 digital input module for NC contacts
 
|8 digital input module for NC contacts
 
|-
 
|-
Line 351: Line 419:
 
|4÷20mA analog output module
 
|4÷20mA analog output module
 
|-
 
|-
|MODLC MODLC-P
+
|MODLC, MODLC-P
 
|ambient light regulator module with integrated sensor
 
|ambient light regulator module with integrated sensor
 
|-
 
|-
Line 378: Line 446:
 
|DMX gateway
 
|DMX gateway
 
|-
 
|-
|MODDALI
+
|MODDALI
 
|4-channel DALI gateway
 
|4-channel DALI gateway
 +
|-
 +
|MODDALI8
 +
|8-channel broadcast DALI gateway
 
|-
 
|-
 
|CLIMA2
 
|CLIMA2
 
|module for the regulation of the ambient temperature
 
|module for the regulation of the ambient temperature
 
|-
 
|-
|MODANA
+
|MODANA
|network analyzer module for Contatto bus
+
|network analyzer module
 +
|-
 +
|MODANAM
 +
|network analyzer module
 
|-
 
|-
 
|MODPQ5
 
|MODPQ5
Line 404: Line 478:
 
|MODCL
 
|MODCL
 
|temperature control module
 
|temperature control module
 +
|-
 +
|MOD4TP/I
 +
|8 digital input and 4 roller shutters or blinds with detection of travel time
 +
|-
 +
|MODRHT
 +
|Temperature, relative humidity and dew point sensor
 +
|-
 +
|MODAM2
 +
|Multi-function, 2 inputs analog module
 +
|-
 +
|MODIGLASS, MODIGLASS3
 +
|6 button touch keypad
 
|-
 
|-
 
|}
 
|}
Line 842: Line 928:
 
----
 
----
  
=== MOD32IN ===
+
=== MOD32IL ===
  
 
32 digital input module for NO contacts in modular housing.
 
32 digital input module for NO contacts in modular housing.
Line 855: Line 941:
 
|-
 
|-
  
|rowspan="2"|i<address>.1
+
|rowspan="2"|i<address>.N
 +
N=1-32
 
|0
 
|0
 
|R
 
|R
|input pin 1 off
+
|input pin N off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 1 on
+
|input pin N on
 
|-
 
|-
  
|rowspan="2"|i<address>.2
+
|}
|0
+
 
|R
+
----
|input pin 2 off
+
 
|-
+
=== MOD32IN ===
|1
+
 
|R
+
32 digital input module for NO contacts in modular housing.
|input pin 2 on
+
 
 +
It uses one addresses of the Contatto bus and four channels, one for each group of 8 inputs.
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 
|-
 
|-
  
|rowspan="2"|i<address>.3
+
|rowspan="2"|i<address>.N
 +
N=1-32
 
|0
 
|0
 
|R
 
|R
|input pin 3 off
+
|input pin N off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 3 on
+
|input pin N on
 
|-
 
|-
  
|rowspan="2"|i<address>.4
+
|}
|0
 
|R
 
|input pin 4 off
 
|-
 
|1
 
|R
 
|input pin 4 on
 
|-
 
  
|rowspan="2"|i<address>.5
+
----
|0
+
 
 +
=== MOD8INP2/A ===
 +
 
 +
8 digital input module for NO contacts.
 +
 
 +
It uses one input address of the Contatto bus.
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 +
|-
 +
 
 +
|rowspan="2"|i<address>.1
 +
|0
 
|R
 
|R
|input pin 5 off
+
|input pin 1 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 5 on
+
|input pin 1 on
 
|-
 
|-
  
|rowspan="2"|i<address>.6
+
|rowspan="2"|i<address>.2
 
|0
 
|0
 
|R
 
|R
|input pin 6 off
+
|input pin 2 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 6 on
+
|input pin 2 on
 
|-
 
|-
  
|rowspan="2"|i<address>.7
+
|rowspan="2"|i<address>.3
 
|0
 
|0
 
|R
 
|R
|input pin 7 off
+
|input pin 3 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 7 on
+
|input pin 3 on
 
|-
 
|-
  
|rowspan="2"|i<address>.8
+
|rowspan="2"|i<address>.4
 
|0
 
|0
 
|R
 
|R
|input pin 8 off
+
|input pin 4 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 8 on
+
|input pin 4 on
 
|-
 
|-
  
|rowspan="2"|i<address+1>.1
+
|rowspan="2"|i<address>.5
 
|0
 
|0
 
|R
 
|R
|input pin 1 off
+
|input pin 5 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 1 on
+
|input pin 5 on
 
|-
 
|-
  
|rowspan="2"|i<address+1>.2
+
|rowspan="2"|i<address>.6
 
|0
 
|0
 
|R
 
|R
|input pin 2 off
+
|input pin 6 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 2 on
+
|input pin 6 on
 
|-
 
|-
  
|rowspan="2"|i<address+1>.3
+
|rowspan="2"|i<address>.7
 
|0
 
|0
 
|R
 
|R
|input pin 3 off
+
|input pin 7 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 3 on
+
|input pin 7 on
 
|-
 
|-
  
|rowspan="2"|i<address+1>.4
+
|rowspan="2"|i<address>.8
 
|0
 
|0
 
|R
 
|R
|input pin 4 off
+
|input pin 8 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 4 on
+
|input pin 8 on
 +
|-
 +
|}
 +
 
 +
----
 +
 
 +
=== MOD8INP2/C ===
 +
 
 +
8 digital input module for NC contacts.
 +
 
 +
It uses one input address of the Contatto bus.
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 
|-
 
|-
  
|rowspan="2"|i<address+1>.5
+
|rowspan="2"|i<address>.1
 
|0
 
|0
 
|R
 
|R
|input pin 5 off
+
|input pin 1 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 5 on
+
|input pin 1 on
 
|-
 
|-
  
|rowspan="2"|i<address+1>.6
+
|rowspan="2"|i<address>.2
 
|0
 
|0
 
|R
 
|R
|input pin 6 off
+
|input pin 2 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 6 on
+
|input pin 2 on
 
|-
 
|-
  
|rowspan="2"|i<address+1>.7
+
|rowspan="2"|i<address>.3
 
|0
 
|0
 
|R
 
|R
|input pin 7 off
+
|input pin 3 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 7 on
+
|input pin 3 on
 
|-
 
|-
  
|rowspan="2"|i<address+1>.8
+
|rowspan="2"|i<address>.4
|0
 
|R
 
|input pin 8 off
 
|-
 
|1
 
|R
 
|input pin 8 on
 
|-
 
 
 
|rowspan="2"|i<address+2>.1
 
|0
 
|R
 
|input pin 1 off
 
|-
 
|1
 
|R
 
|input pin 1 on
 
|-
 
 
 
|rowspan="2"|i<address+2>.2
 
|0
 
|R
 
|input pin 2 off
 
|-
 
|1
 
|R
 
|input pin 2 on
 
|-
 
 
 
|rowspan="2"|i<address+2>.3
 
|0
 
|R
 
|input pin 3 off
 
|-
 
|1
 
|R
 
|input pin 3 on
 
|-
 
 
 
|rowspan="2"|i<address+2>.4
 
 
|0
 
|0
 
|R
 
|R
Line 1,055: Line 1,133:
 
|-
 
|-
  
|rowspan="2"|i<address+2>.5
+
|rowspan="2"|i<address>.5
 
|0
 
|0
 
|R
 
|R
Line 1,065: Line 1,143:
 
|-
 
|-
  
|rowspan="2"|i<address+2>.6
+
|rowspan="2"|i<address>.6
 
|0
 
|0
 
|R
 
|R
Line 1,075: Line 1,153:
 
|-
 
|-
  
|rowspan="2"|i<address+2>.7
+
|rowspan="2"|i<address>.7
 
|0
 
|0
 
|R
 
|R
Line 1,085: Line 1,163:
 
|-
 
|-
  
|rowspan="2"|i<address+2>.8
+
|rowspan="2"|i<address>.8
 
|0
 
|0
 
|R
 
|R
Line 1,094: Line 1,172:
 
|input pin 8 on
 
|input pin 8 on
 
|-
 
|-
 +
|}
  
|rowspan="2"|i<address+3>.1
+
----
|0
+
 
|R
+
=== MOAN/I ===
|input pin 1 off
+
 
 +
0÷10V analog input module.
 +
 
 +
It uses one input address in the range 1 to 127 of the Contatto bus.
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 
|-
 
|-
|1
+
 
 +
|i<address>.1
 +
|0 ... 255
 
|R
 
|R
|input pin 1 on
+
|voltage value divided in 255 steps
 
|-
 
|-
 +
|}
  
|rowspan="2"|i<address+3>.2
+
----
|0
+
 
|R
+
=== MOAN/I4 ===
|input pin 2 off
+
 
 +
Quad 0÷10V analog input module.
 +
 
 +
It uses four consecutive addresses of the Contatto bus, one for each input.
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 
|-
 
|-
|1
+
 
 +
|i<address>.1
 +
|0 ... 255
 
|R
 
|R
|input pin 2 on
+
|voltage value divided in 255 steps
 
|-
 
|-
  
|rowspan="2"|i<address+3>.3
+
|i<address+1>.1
|0
+
|0 ... 255
 
|R
 
|R
|input pin 3 off
+
|voltage value divided in 255 steps
 
|-
 
|-
|1
+
 
 +
|i<address+2>.1
 +
|0 ... 255
 
|R
 
|R
|input pin 3 on
+
|voltage value divided in 255 steps
 
|-
 
|-
  
|rowspan="2"|i<address+3>.4
+
|i<address+3>.1
|0
+
|0 ... 255
 
|R
 
|R
|input pin 4 off
+
|voltage value divided in 255 steps
 
|-
 
|-
|1
+
|}
|R
+
 
|input pin 4 on
+
----
 +
 
 +
=== MI420 ===
 +
 
 +
4÷20mA analog input module.
 +
 
 +
It uses one input address in the range 1 to 127 of the Contatto bus.
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 
|-
 
|-
  
|rowspan="2"|i<address+3>.5
+
|i<address>.1
|0
+
|0 ... 255
 
|R
 
|R
|input pin 5 off
+
|current value divided in 255 steps
|-
 
|1
 
|R
 
|input pin 5 on
 
 
|-
 
|-
 +
|}
  
|rowspan="2"|i<address+3>.6
+
----
|0
+
 
|R
+
=== MI420-X4 ===
|input pin 6 off
+
 
 +
Quad 4÷20mA analog input module.
 +
 
 +
It uses four consecutive addresses of the Contatto bus, one for each input.
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 
|-
 
|-
|1
+
 
 +
|i<address>.1
 +
|0 ... 255
 
|R
 
|R
|input pin 6 on
+
|current value divided in 255 steps
 
|-
 
|-
  
|rowspan="2"|i<address+3>.7
+
|i<address+1>.1
|0
+
|0 ... 255
 
|R
 
|R
|input pin 7 off
+
|current value divided in 255 steps
 
|-
 
|-
|1
+
 
 +
|i<address+2>.1
 +
|0 ... 255
 
|R
 
|R
|input pin 7 on
+
|current value divided in 255 steps
 
|-
 
|-
  
|rowspan="2"|i<address+3>.8
+
|i<address+3>.1
|0
+
|0 ... 255
 
|R
 
|R
|input pin 8 off
+
|current value divided in 255 steps
|-
 
|1
 
|R
 
|input pin 8 on
 
 
|-
 
|-
 
 
|}
 
|}
  
 
----
 
----
  
=== MOD8INP2/A ===
+
=== MOD4AM12/V/I ===
  
8 digital input module for NO contacts.
+
4-channel 0÷10V or 4÷20mA (0÷21mA) analog input module.
  
 
It uses one input address of the Contatto bus.
 
It uses one input address of the Contatto bus.
Line 1,192: Line 1,313:
 
|-
 
|-
  
|rowspan="2"|i<address>.1
+
|i<address>.1
|0
+
|0 ... 4095
 
|R
 
|R
|input pin 1 off
+
|measurement range divided in 4095 steps
 
|-
 
|-
|1
+
 
 +
|i<address>.2
 +
|0 ... 4095
 
|R
 
|R
|input pin 1 on
+
|measurement range divided in 4095 steps
 
|-
 
|-
  
|rowspan="2"|i<address>.2
+
|i<address>.3
|0
+
|0 ... 4095
 
|R
 
|R
|input pin 2 off
+
|measurement range divided in 4095 steps
 
|-
 
|-
|1
+
 
 +
|i<address>.4
 +
|0 ... 4095
 
|R
 
|R
|input pin 2 on
+
|measurement range divided in 4095 steps
 
|-
 
|-
 +
|}
 +
 +
----
  
|rowspan="2"|i<address>.3
+
=== MOD2PT ===
|0
+
 
|R
+
Input module for two PT100 temperature probes.
|input pin 3 off
+
 
 +
It uses one or two addresses according to how the dip-switch is set.
 +
 
 +
If both channels are enabled (IN1 and IN2), setting the n “base” address through the FXPRO programmer, the input address and address+1 (consecutive) will be automatically assigned to the module. 
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 
|-
 
|-
|1
+
 
 +
|i<address>.1
 +
|0 ... 255
 
|R
 
|R
|input pin 3 on
+
|range –40 ÷ +87.5°C: code 0 corresponds to  –40°C and code 255 corresponds to +87.5°C
 
|-
 
|-
  
|rowspan="2"|i<address>.4
+
|i<address+1>.1
|0
+
|0 ... 255
 
|R
 
|R
|input pin 4 off
+
|range –40 ÷ +87.5°C: code 0 corresponds to  –40°C and code 255 corresponds to +87.5°C
 
|-
 
|-
|1
+
|}
|R
+
 
|input pin 4 on
+
----
 +
 
 +
=== MODCNT ===
 +
 
 +
4-channel counter module in modular housing.
 +
 
 +
It uses one input address of the Contatto bus.
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 
|-
 
|-
  
|rowspan="2"|i<address>.5
+
|i<address>.1
|0
+
|0 ... 65535
 
|R
 
|R
|input pin 5 off
+
|number of pulses
 
|-
 
|-
|1
+
 
 +
|i<address>.2
 +
|0 ... 65535
 
|R
 
|R
|input pin 5 on
+
|number of pulses
 
|-
 
|-
  
|rowspan="2"|i<address>.6
+
|i<address>.3
|0
+
|0 ... 65535
 
|R
 
|R
|input pin 6 off
+
|number of pulses
 
|-
 
|-
|1
+
 
 +
|i<address>.4
 +
|0 ... 65535
 
|R
 
|R
|input pin 6 on
+
|number of pulses
 
|-
 
|-
 +
|}
  
|rowspan="2"|i<address>.7
+
----
|0
+
 
 +
=== MODNTC ===
 +
 
 +
Input module for ambient temperature sensors and potentiometers.
 +
 
 +
It uses one input address of the Contatto bus.
 +
 
 +
The temperature values measured by MODNTC module are reported as Kelvin degrees multiplied by 10; in other words, 0°C will be reported as 2730, 0.1°C will be reported as 2731 and so on.
 +
 
 +
Concerning the potentiometer channels, the values read from the module will be 0 with the potentiometer at its minimum position and it will be 1000 with the potentiometer at its maximum position.
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 +
|-
 +
 
 +
|i<address>.1
 +
|0 ... 4095
 
|R
 
|R
|input pin 7 off
+
|temperature value
 
|-
 
|-
|1
+
 
 +
|i<address>.2
 +
|0 ... 4095
 
|R
 
|R
|input pin 7 on
+
|temperature value
 
|-
 
|-
  
|rowspan="2"|i<address>.8
+
|i<address>.3
|0
+
|0 ... 4095
 
|R
 
|R
|input pin 8 off
+
|temperature value
 
|-
 
|-
|1
+
 
 +
|i<address>.4
 +
|0 ... 4095
 
|R
 
|R
|input pin 8 on
+
|temperature value
 
|-
 
|-
 
|}
 
|}
Line 1,275: Line 1,454:
 
----
 
----
  
=== MOD8INP2/C ===
+
=== MOD4I/A ===
  
8 digital input module for NC contacts.
+
4-digital input module for NO contacts in modular housing.
  
It uses one input address of the Contatto bus.
+
It uses one input address in the range 1 to 127 of the Contatto bus.
  
 
{| class="wikitable"
 
{| class="wikitable"
Line 1,288: Line 1,467:
 
|-
 
|-
  
|rowspan="2"|i<address>.1
+
|rowspan="2"|i<address>
 
|0
 
|0
 
|R
 
|R
Line 1,298: Line 1,477:
 
|-
 
|-
  
|rowspan="2"|i<address>.2
+
|rowspan="2"|i<address+1>
 
|0
 
|0
 
|R
 
|R
|input pin 2 off
+
|input pin 1 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 2 on
+
|input pin 1 on
 
|-
 
|-
  
|rowspan="2"|i<address>.3
+
|rowspan="2"|i<address+2>
 
|0
 
|0
 
|R
 
|R
|input pin 3 off
+
|input pin 1 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 3 on
+
|input pin 1 on
 
|-
 
|-
  
|rowspan="2"|i<address>.4
+
|rowspan="2"|i<address+3>
 
|0
 
|0
 
|R
 
|R
|input pin 4 off
+
|input pin 1 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 4 on
+
|input pin 1 on
 +
|-
 +
|}
 +
 
 +
----
 +
 
 +
=== MOD4I/S ===
 +
 
 +
4-digital input module for NO contacts in 2M modular housing.
 +
 
 +
It uses one address of the Contatto bus.
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 
|-
 
|-
  
|rowspan="2"|i<address>.5
+
|rowspan="2"|i<address>
 
|0
 
|0
 
|R
 
|R
|input pin 5 off
+
|input pin 1 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 5 on
+
|input pin 1 on
 
|-
 
|-
  
|rowspan="2"|i<address>.6
+
|rowspan="2"|i<address+1>
 
|0
 
|0
 
|R
 
|R
|input pin 6 off
+
|input pin 1 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 6 on
+
|input pin 1 on
 
|-
 
|-
  
|rowspan="2"|i<address>.7
+
|rowspan="2"|i<address+2>
 
|0
 
|0
 
|R
 
|R
|input pin 7 off
+
|input pin 1 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 7 on
+
|input pin 1 on
 
|-
 
|-
  
|rowspan="2"|i<address>.8
+
|rowspan="2"|i<address+3>
 
|0
 
|0
 
|R
 
|R
|input pin 8 off
+
|input pin 1 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 8 on
+
|input pin 1 on
 
|-
 
|-
 
|}
 
|}
Line 1,371: Line 1,566:
 
----
 
----
  
=== MOAN/I ===
+
=== MODLUX ===
  
0÷10V analog input module.
+
Ambient light measurement module with sensor for ceiling mounting.  
  
It uses one input address in the range 1 to 127 of the Contatto bus.
+
It uses one address of the Contatto bus.
  
 
{| class="wikitable"
 
{| class="wikitable"
Line 1,385: Line 1,580:
  
 
|i<address>.1
 
|i<address>.1
|0 ... 255
+
|0 ... 1023
 
|R
 
|R
|voltage value divided in 255 steps
+
|ambient brightness value
 
|-
 
|-
 +
 
|}
 
|}
  
 
----
 
----
  
=== MOAN/I4 ===
+
=== MODMETEO ===
  
Quad 0÷10V analog input module.
+
Meteorological data detection module for Contatto bus.
  
It uses four consecutive addresses of the Contatto bus, one for each input.
+
It uses one input address and, if enabled by the configuration panel of MCP IDE, one output address with the same value.
  
 
{| class="wikitable"
 
{| class="wikitable"
Line 1,406: Line 1,602:
 
|-
 
|-
  
|i<address>.1
+
|i<address>.temp
|0 ... 255
+
|<temp>
 
|R
 
|R
|voltage value divided in 255 steps
+
|temperature value (in C/10)
 
|-
 
|-
  
|i<address+1>.1
+
|i<address>.lux
|0 ... 255
+
|<lux*10>
 
|R
 
|R
|voltage value divided in 255 steps
+
|daylight value in tens of LUX
 
|-
 
|-
  
|i<address+2>.1
+
|i<address>.wind
|0 ... 255
+
|1 m/s / 10
 
|R
 
|R
|voltage value divided in 255 steps
+
|wind speed value
 
|-
 
|-
  
|i<address+3>.1
+
|rowspan="2"|i<address>.rain
|0 ... 255
+
|0
 
|R
 
|R
|voltage value divided in 255 steps
+
|no rain
 
|-
 
|-
|}
+
|1
 
+
|R
----
+
|rain
 
 
=== MI420 ===
 
 
 
4÷20mA analog input module.
 
 
 
It uses one input address in the range 1 to 127 of the Contatto bus.
 
 
 
{| class="wikitable"
 
!ID
 
!Value
 
!R/W
 
!Description
 
 
|-
 
|-
  
|i<address>.1
+
|rowspan="2"|i<address>.night
|0 ... 255
+
|0
 
|R
 
|R
|current value divided in 255 steps
+
|day
 
|-
 
|-
|}
+
|1
 
+
|R
----
+
|night
 
 
=== MI420-X4 ===
 
 
 
Quad 4÷20mA analog input module.
 
 
 
It uses four consecutive addresses of the Contatto bus, one for each input.
 
 
 
{| class="wikitable"
 
!ID
 
!Value
 
!R/W
 
!Description
 
 
|-
 
|-
  
|i<address>.1
+
|rowspan="2"|i<address>.temp.limit
|0 ... 255
+
|0
 
|R
 
|R
|current value divided in 255 steps
+
|measured temperature <  threshold
 
|-
 
|-
 
+
|1
|i<address+1>.1
 
|0 ... 255
 
 
|R
 
|R
|current value divided in 255 steps
+
|measured temperature >  threshold
 
|-
 
|-
  
|i<address+2>.1
+
|rowspan="2"|i<address>.lux.limit
|0 ... 255
+
|0
 
|R
 
|R
|current value divided in 255 steps
+
|measured daylight <  threshold
 
|-
 
|-
 
+
|1
|i<address+3>.1
 
|0 ... 255
 
 
|R
 
|R
|current value divided in 255 steps
+
|measured daylight >  threshold
 
|-
 
|-
|}
 
  
----
+
|rowspan="2"|i<address>.wind.limit
 
+
|0
=== MOD4AM12/V/I ===
+
|R
 
+
|measured wind speed <  threshold
4-channel 0÷10V or 4÷20mA (0÷21mA) analog input module.
 
 
 
It uses one input address of the Contatto bus.
 
 
 
{| class="wikitable"
 
!ID
 
!Value
 
!R/W
 
!Description
 
 
|-
 
|-
 
+
|1
|i<address>.1
 
|0 ... 4095
 
 
|R
 
|R
|measurement range divided in 4095 steps
+
|measured wind speed >  threshold
 
|-
 
|-
  
|i<address>.2
+
|rowspan="2"|i<address>.light.south
|0 ... 4095
+
|0
 
|R
 
|R
|measurement range divided in 4095 steps
+
|light not from South
 
|-
 
|-
 
+
|1
|i<address>.3
 
|0 ... 4095
 
 
|R
 
|R
|measurement range divided in 4095 steps
+
|light from South
 
|-
 
|-
  
|i<address>.4
+
|rowspan="2"|i<address>.light.west
|0 ... 4095
+
|0
 
|R
 
|R
|measurement range divided in 4095 steps
+
|light not from West
 
|-
 
|-
|}
+
|1
 
+
|R
----
+
|light from West
 
 
=== MOD2PT ===
 
 
 
Input module for two PT100 temperature probes.
 
 
 
It uses one or two addresses according to how the dip-switch is set.
 
 
 
If both channels are enabled (IN1 and IN2), setting the n “base” address through the FXPRO programmer, the input address and address+1 (consecutive) will be automatically assigned to the module. 
 
 
 
{| class="wikitable"
 
!ID
 
!Value
 
!R/W
 
!Description
 
 
|-
 
|-
  
|i<address>.1
+
|rowspan="2"|i<address>.light.east
|0 ... 255
+
|0
 
|R
 
|R
|range –40 ÷ +87.5°C: code 0 corresponds to  –40°C and code 255 corresponds to +87.5°C
+
|light not from East
 
|-
 
|-
 
+
|1
|i<address+1>.1
 
|0 ... 255
 
 
|R
 
|R
|range –40 ÷ +87.5°C: code 0 corresponds to  –40°C and code 255 corresponds to +87.5°C
+
|light from East
 
|-
 
|-
|}
 
  
----
+
|rowspan="2"|i<address>.fault
 +
|0
 +
|R
 +
|sensor works correctly
 +
|-
 +
|1
 +
|R
 +
|sensor failure
 +
|-
  
=== MODCNT ===
+
|rowspan="2"|o<address>.temp
 +
|<temp>
 +
|RW
 +
|temperature threshold (in C/10)
 +
|-
 +
|off
 +
|RW
 +
|temperature threshold off
 +
|-
 +
 
 +
|rowspan="2"|o<address>.lux
 +
|<lux*10>
 +
|RW
 +
|daylight threshold
 +
|-
 +
|off
 +
|RW
 +
|daylight threshold off
 +
|-
 +
 
 +
|rowspan="2"|o<address>.wind
 +
|1 m/s / 10
 +
|RW
 +
|wind speed threshold
 +
|-
 +
|off
 +
|RW
 +
|wind speed threshold off
 +
|-
 +
 
 +
|}
 +
 
 +
----
 +
 
 +
=== MOD8R ===
  
4-channel counter module in modular housing.
+
8 power relay output module.
  
It uses one input address of the Contatto bus.
+
It uses one output address of the Contatto bus.
  
 
{| class="wikitable"
 
{| class="wikitable"
Line 1,578: Line 1,757:
 
|-
 
|-
  
|i<address>.1
+
|rowspan="2"|o<address>.1
|0 ... 65535
+
|0
|R
+
|RW
|number of pulses
+
|output pin 1 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 1 on
 
|-
 
|-
  
|i<address>.2
+
|rowspan="2"|o<address>.2
|0 ... 65535
+
|0
|R
+
|RW
|number of pulses
+
|output pin 2 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 2 on
 
|-
 
|-
  
|i<address>.3
+
|rowspan="2"|o<address>.3
|0 ... 65535
+
|0
|R
+
|RW
|number of pulses
+
|output pin 3 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 3 on
 
|-
 
|-
  
|i<address>.4
+
|rowspan="2"|o<address>.4
|0 ... 65535
+
|0
|R
+
|RW
|number of pulses
+
|output pin 4 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 4 on
 
|-
 
|-
|}
 
  
----
+
|rowspan="2"|o<address>.5
 
+
|0
=== MODNTC ===
+
|RW
 +
|output pin 5 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 5 on
 +
|-
 +
 
 +
|rowspan="2"|o<address>.6
 +
|0
 +
|RW
 +
|output pin 6 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 6 on
 +
|-
 +
 
 +
|rowspan="2"|o<address>.7
 +
|0
 +
|RW
 +
|output pin 7 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 7 on
 +
|-
 +
 
 +
|rowspan="2"|o<address>.8
 +
|0
 +
|RW
 +
|output pin 8 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 8 on
 +
|-
 +
|}
 +
 
 +
You can also set the value to “on” or “off”, that is equivalent to 1 and 0.
  
Input module for ambient temperature sensors and potentiometers.
+
----
  
It uses one input address of the Contatto bus.
+
=== MODPNP ===
  
The temperature values measured by MODNTC module are reported as Kelvin degrees multiplied by 10; in other words, 0°C will be reported as 2730, 0.1°C will be reported as 2731 and so on.  
+
8 positive logic (PNP) “open collector” digital output module.
  
Concerning the potentiometer channels, the values read from the module will be 0 with the potentiometer at its minimum position and it will be 1000 with the potentiometer at its maximum position.
+
It uses one output address in the range 1 to 127 of the Contatto bus.
  
 
{| class="wikitable"
 
{| class="wikitable"
Line 1,622: Line 1,855:
 
|-
 
|-
  
|i<address>.1
+
|rowspan="2"|o<address>.1
|0 ... 4095
+
|0
|R
+
|RW
|temperature value
+
|output pin 1 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 1 on
 
|-
 
|-
  
|i<address>.2
+
|rowspan="2"|o<address>.2
|0 ... 4095
+
|0
|R
+
|RW
|temperature value
+
|output pin 2 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 2 on
 
|-
 
|-
  
|i<address>.3
+
|rowspan="2"|o<address>.3
|0 ... 4095
+
|0
|R
+
|RW
|temperature value
+
|output pin 3 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 3 on
 
|-
 
|-
  
|i<address>.4
+
|rowspan="2"|o<address>.4
|0 ... 4095
+
|0
|R
+
|RW
|temperature value
+
|output pin 4 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 4 on
 
|-
 
|-
|}
 
  
----
+
|rowspan="2"|o<address>.5
 
 
=== MOD4I/A ===
 
 
 
4-digital input module for NO contacts in modular housing.
 
 
 
It uses one input address in the range 1 to 127 of the Contatto bus.
 
 
 
{| class="wikitable"
 
!ID
 
!Value
 
!R/W
 
!Description
 
|-
 
 
 
|rowspan="2"|i<address>
 
 
|0
 
|0
|R
+
|RW
|input pin 1 off
+
|output pin 5 off
 
|-
 
|-
 
|1
 
|1
|R
+
|RW
|input pin 1 on
+
|output pin 5 on
 
|-
 
|-
  
|rowspan="2"|i<address+1>
+
|rowspan="2"|o<address>.6
 
|0
 
|0
|R
+
|RW
|input pin 1 off
+
|output pin 6 off
 
|-
 
|-
 
|1
 
|1
|R
+
|RW
|input pin 1 on
+
|output pin 6 on
 
|-
 
|-
  
|rowspan="2"|i<address+2>
+
|rowspan="2"|o<address>.7
 
|0
 
|0
|R
+
|RW
|input pin 1 off
+
|output pin 7 off
 
|-
 
|-
 
|1
 
|1
|R
+
|RW
|input pin 1 on
+
|output pin 7 on
 
|-
 
|-
  
|rowspan="2"|i<address+3>
+
|rowspan="2"|o<address>.8
 
|0
 
|0
|R
+
|RW
|input pin 1 off
+
|output pin 8 off
 
|-
 
|-
 
|1
 
|1
|R
+
|RW
|input pin 1 on
+
|output pin 8 on
 
|-
 
|-
 
|}
 
|}
 +
 +
You can also set the value to “on” or “off”, that is equivalent to 1 and 0.
  
 
----
 
----
  
=== MOD4I/S ===
+
=== MODREL ===
  
4-digital input module for NO contacts in 2M modular housing.
+
8 relay output compact module in DIN 3M housing.
  
It uses one address of the Contatto bus.
+
It uses one output address in the range 1 to 127 of the Contatto bus.
  
 
{| class="wikitable"
 
{| class="wikitable"
Line 1,718: Line 1,953:
 
|-
 
|-
  
|rowspan="2"|i<address>
+
|rowspan="2"|o<address>.1
 
|0
 
|0
|R
+
|RW
|input pin 1 off
+
|output pin 1 off
 
|-
 
|-
 
|1
 
|1
|R
+
|RW
|input pin 1 on
+
|output pin 1 on
 
|-
 
|-
  
|rowspan="2"|i<address+1>
+
|rowspan="2"|o<address>.2
 
|0
 
|0
|R
+
|RW
|input pin 1 off
+
|output pin 2 off
 
|-
 
|-
 
|1
 
|1
|R
+
|RW
|input pin 1 on
+
|output pin 2 on
 
|-
 
|-
  
|rowspan="2"|i<address+2>
+
|rowspan="2"|o<address>.3
 
|0
 
|0
|R
+
|RW
|input pin 1 off
+
|output pin 3 off
 
|-
 
|-
 
|1
 
|1
|R
+
|RW
|input pin 1 on
+
|output pin 3 on
 
|-
 
|-
  
|rowspan="2"|i<address+3>
+
|rowspan="2"|o<address>.4
 
|0
 
|0
|R
+
|RW
|input pin 1 off
+
|output pin 4 off
 
|-
 
|-
 
|1
 
|1
|R
+
|RW
|input pin 1 on
+
|output pin 4 on
 
|-
 
|-
|}
 
  
----
+
|rowspan="2"|o<address>.5
 +
|0
 +
|RW
 +
|output pin 5 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 5 on
 +
|-
  
=== MODLUX ===
+
|rowspan="2"|o<address>.6
 +
|0
 +
|RW
 +
|output pin 6 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 6 on
 +
|-
  
Ambient light measurement module with sensor for ceiling mounting.
+
|rowspan="2"|o<address>.7
 
+
|0
It uses one address of the Contatto bus.
+
|RW
 
+
|output pin 7 off
{| class="wikitable"
 
!ID
 
!Value
 
!R/W
 
!Description
 
 
|-
 
|-
 
+
|1
|i<address>.1
+
|RW
|0 ... 1023
+
|output pin 7 on
|R
 
|ambient brightness value
 
 
|-
 
|-
  
|}
+
|rowspan="2"|o<address>.8
 +
|0
 +
|RW
 +
|output pin 8 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 8 on
 +
|-
 +
|}
 +
 
 +
You can also set the value to “on” or “off”, that is equivalent to 1 and 0.
  
 
----
 
----
  
=== MODMETEO ===
+
=== MOAN/U ===
  
Meteorological data detection module for Contatto bus.
+
0÷10V analog output module.
  
It uses one input address and, if enabled by the configuration panel of MCP IDE, one output address with the same value.
+
It uses one output address in the range 1 to 127 of the Contatto bus.
  
 
{| class="wikitable"
 
{| class="wikitable"
Line 1,797: Line 2,051:
 
|-
 
|-
  
|i<address>.temp
+
|o<address>
|<temp>
+
|x/255
 
|R
 
|R
|temperature value (in C/10)
+
|value in fractional format, where 0 &le; x &le; 255
 
|-
 
|-
  
|i<address>.lux
+
|rowspan="3"|o<address>
|<lux*10>
+
|<x%>
|R
+
|W
|daylight value in tens of LUX
+
|the percentage of signal (0÷100%) applied to the output
 +
|-
 +
|0...255
 +
|W
 +
|convert the 8 bits digital code received through the bus in the proper analog level.
 +
|-
 +
|x/y
 +
|W
 +
|fractional format, formatted as “x/y”, where 0 &le; x &le; y
 
|-
 
|-
 +
|}
  
|i<address>.wind
+
----
|1 m/s / 10
 
|R
 
|wind speed value
 
|-
 
  
|rowspan="2"|i<address>.rain
+
=== MO420 ===
|0
+
 
|R
+
4÷20mA analog output module.
|no rain
+
 
|-
+
It uses one output address in the range 1 to 127 of the Contatto bus.
|1
 
|R
 
|rain
 
|-
 
  
|rowspan="2"|i<address>.night
+
{| class="wikitable"
|0
+
!ID
|R
+
!Value
|day
+
!R/W
|-
+
!Description
|1
 
|R
 
|night
 
 
|-
 
|-
  
|rowspan="2"|i<address>.temp.limit
+
|rowspan="3"|o<address>
|0
+
|<x%>
|R
+
|RW
|measured temperature <  threshold
+
|the percentage of signal (0÷100%) applied to the output
 
|-
 
|-
|1
+
|0...255
|R
+
|RW
|measured temperature >  threshold
+
|convert the 8 bits digital code received through the bus in the proper analog level
 
|-
 
|-
 
+
|x/y
|rowspan="2"|i<address>.lux.limit
+
|RW
|0
+
|fractional format, formatted as “x/y”, where 0 &le; x &le; y
|R
 
|measured daylight <  threshold
 
 
|-
 
|-
|1
+
|}
|R
+
 
|measured daylight >  threshold
+
----
 +
 
 +
=== MODLC and MODLC-P ===
 +
 
 +
Ambient light regulator module with integrated sensor.
 +
 
 +
It uses one input address and, if enabled by the configuration panel of MCP IDE, one output address with the same value.
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 
|-
 
|-
  
|rowspan="2"|i<address>.wind.limit
+
|i<address>.lux
|0
+
|value equivalent to three times the brightness in lux detected by the sensor
 
|R
 
|R
|measured wind speed <  threshold
+
|the brightness value in lux detected by the MODLC
 
|-
 
|-
|1
+
 
 +
|i<address>.level
 +
|calculated value for the automatic brightness regulation
 
|R
 
|R
|measured wind speed >  threshold
+
|the value to be sent to the dimmer in order to execute the automatic regulation
 
|-
 
|-
  
|rowspan="2"|i<address>.light.south
+
|rowspan="2"|i<address>.mode
|0
+
|auto
 
|R
 
|R
|light not from South
+
|automatic regulation
 
|-
 
|-
|1
+
|man
 
|R
 
|R
|light from South
+
|manual regulation
 
|-
 
|-
  
|rowspan="2"|i<address>.light.west
+
|rowspan="2"|i<address>.in
 
|0
 
|0
 
|R
 
|R
|light not from West
+
|digital input 2 (including presence delay) OFF
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|light from West
+
|digital input 2 (including presence delay) ON
 
|-
 
|-
  
|rowspan="2"|i<address>.light.east
+
|rowspan="2"|i<address>.in1
 
|0
 
|0
 
|R
 
|R
|light not from East
+
|digital input 1 OFF
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|light from East
+
|digital input 1 ON
 
|-
 
|-
  
|rowspan="2"|i<address>.fault
+
|rowspan="2"|i<address>.in2
 
|0
 
|0
 
|R
 
|R
|sensor works correctly
+
|digital input 2 OFF
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|lsensor failure
+
|digital input 2 ON
 
|-
 
|-
  
|rowspan="2"|o<address>.temp
+
|o<address>.setpoint
|<temp>
+
|setpoint value
 
|RW
 
|RW
|temperature threshold (in C/10)
+
|set the setpoint for the automatic brightness regulation
 
|-
 
|-
|off
+
 
 +
|o<address>.preset
 +
|setpoint value
 
|RW
 
|RW
|temperature threshold off
+
|set the preset dimmer value (SMART mode only)
 
|-
 
|-
  
|rowspan="2"|o<address>.lux
+
|o<address>.delay
|<lux*10>
+
|setpoint value
 
|RW
 
|RW
|daylight threshold
+
|set the presence detector delay in seconds
|-
 
|off
 
|RW
 
|daylight threshold off
 
 
|-
 
|-
  
|rowspan="2"|o<address>.wind
+
|rowspan="2"|o<address>.mode
|1 m/s / 10
+
|auto
 
|RW
 
|RW
|wind speed threshold
+
|set automatic control
 
|-
 
|-
|off
+
|man
 
|RW
 
|RW
|wind speed threshold off
+
|set manual control
 
|-
 
|-
  
|}
+
|rowspan="2"|o<address>.in.reset
 
 
----
 
 
 
=== MOD8R ===
 
 
 
8 power relay output module.
 
 
 
It uses one output address of the Contatto bus.
 
 
 
{| class="wikitable"
 
!ID
 
!Value
 
!R/W
 
!Description
 
|-
 
 
 
|rowspan="2"|o<address>.1
 
 
|0
 
|0
|RW
+
|R
|output pin 1 off
+
|not active
 
|-
 
|-
 
|1
 
|1
 
|RW
 
|RW
|output pin 1 on
+
|force the expiring of the deactivation delay time of the digital input
 
|-
 
|-
  
|rowspan="2"|o<address>.2
+
|rowspan="2"|o<address>.mode.reset
 
|0
 
|0
 
|RW
 
|RW
|output pin 2 off
+
|not active
 
|-
 
|-
 
|1
 
|1
 
|RW
 
|RW
|output pin 2 on
+
|disable automatic control
 
|-
 
|-
  
|rowspan="2"|o<address>.3
+
|rowspan="2"|o<address>.full.reset
 
|0
 
|0
 
|RW
 
|RW
|output pin 3 off
+
|not active
 
|-
 
|-
 
|1
 
|1
 
|RW
 
|RW
|output pin 3 on
+
|perform a full reset
 
|-
 
|-
  
|rowspan="2"|o<address>.4
+
|rowspan="2"|o<address>.v
 
|0
 
|0
 
|RW
 
|RW
|output pin 4 off
+
|virtual point off
 
|-
 
|-
 
|1
 
|1
 
|RW
 
|RW
|output pin 4 on
+
|virtual point on
 
|-
 
|-
  
|rowspan="2"|o<address>.5
+
|rowspan="2"|o<address>.in.disable
 
|0
 
|0
 
|RW
 
|RW
|output pin 5 off
+
|normal presence detector operation (SMART mode)
 
|-
 
|-
 
|1
 
|1
 
|RW
 
|RW
|output pin 5 on
+
|disable light ON control from presence detector (SMART mode)
 
|-
 
|-
  
|rowspan="2"|o<address>.6
+
|rowspan="2"|o<address>.presence
 
|0
 
|0
 
|RW
 
|RW
|output pin 6 off
+
|not active
 
|-
 
|-
 
|1
 
|1
 
|RW
 
|RW
|output pin 6 on
+
|presence forced
|-
 
 
 
|rowspan="2"|o<address>.7
 
|0
 
|RW
 
|output pin 7 off
 
|-
 
|1
 
|RW
 
|output pin 7 on
 
|-
 
 
 
|rowspan="2"|o<address>.8
 
|0
 
|RW
 
|output pin 8 off
 
|-
 
|1
 
|RW
 
|output pin 8 on
 
 
|-
 
|-
 
|}
 
|}
  
You can also set the value to “on” or “off”, that is equivalent to 1 and 0.
+
----
  
----
+
=== MOD4-4S ===
  
=== MODPNP ===
+
4 digital input and 4 power relay output multifunction module.
  
8 positive logic (PNP) “open collector” digital output module.
+
HSYCO supports two configurations only: four independent outputs, or two shutters.
  
It uses one output address in the range 1 to 127 of the Contatto bus.
+
When set as four independent outputs, the module must be configured with the same base address for input and output.  
  
{| class="wikitable"
+
For example:
!ID
+
<pre>
 +
(I20, O20)
 +
</pre>
 +
The input address must be enabled. Configuration switches must be set as SW1=OFF, SW2=OFF and SW5=ON.
 +
 
 +
When set as two shutters, the module must be configured with the same base address for input and output.
 +
 
 +
For example:
 +
<pre>
 +
(I20, O20, O21)
 +
</pre>
 +
The input address must be enabled. Configuration switches must be set as SW1=ON, SW2=ON and SW5=ON.
 +
 
 +
{| class="wikitable"
 +
!ID
 
!Value
 
!Value
 
!R/W
 
!R/W
Line 2,050: Line 2,289:
 
|-
 
|-
  
|rowspan="2"|o<address>.1
+
|rowspan="2"|i<address>.1
 
|0
 
|0
|RW
+
|R
|output pin 1 off
+
|input pin 1 off
 
|-
 
|-
 
|1
 
|1
|RW
+
|R
|output pin 1 on
+
|input pin 1 on
 
|-
 
|-
  
|rowspan="2"|o<address>.2
+
|rowspan="2"|i<address>.2
 
|0
 
|0
|RW
+
|R
|output pin 2 off
+
|input pin 2 off
 
|-
 
|-
 
|1
 
|1
|RW
+
|R
|output pin 2 on
+
|input pin 2 on
 
|-
 
|-
  
|rowspan="2"|o<address>.3
+
|rowspan="2"|i<address>.3
 
|0
 
|0
|RW
+
|R
|output pin 3 off
+
|input pin 3 off
 
|-
 
|-
 
|1
 
|1
|RW
+
|R
|output pin 3 on
+
|input pin 3 on
 
|-
 
|-
  
|rowspan="2"|o<address>.4
+
|rowspan="2"|i<address>.4
 
|0
 
|0
|RW
+
|R
|output pin 4 off
+
|input pin 4 off
 
|-
 
|-
 
|1
 
|1
|RW
+
|R
|output pin 4 on
+
|input pin 4 on
 
|-
 
|-
  
|rowspan="2"|o<address>.5
+
|rowspan="6"|o<address>.1
|0
+
|up
 
|RW
 
|RW
|output pin 5 off
+
|shutter up command
 
|-
 
|-
|1
+
|down
 
|RW
 
|RW
|output pin 5 on
+
|shutter down command
 
|-
 
|-
 
+
|stop
|rowspan="2"|o<address>.6
 
|0
 
 
|RW
 
|RW
|output pin 6 off
+
|shutter stop command
 +
|-
 +
|unknown
 +
|R
 +
|unknown state
 +
|-
 +
|offup
 +
|R
 +
|shutter off, up position
 
|-
 
|-
|1
+
|offdown
|RW
+
|R
|output pin 6 on
+
|shutter off, down position
 
|-
 
|-
  
|rowspan="2"|o<address>.7
+
|rowspan="6"|o<address+1>.1
|0
+
|up
 
|RW
 
|RW
|output pin 7 off
+
|shutter up command
 
|-
 
|-
|1
+
|down
 
|RW
 
|RW
|output pin 7 on
+
|shutter down command
 
|-
 
|-
 
+
|stop
|rowspan="2"|o<address>.8
 
|0
 
 
|RW
 
|RW
|output pin 8 off
+
|shutter stop command
 +
|-
 +
|unknown
 +
|R
 +
|unknown state
 
|-
 
|-
|1
+
|offup
|RW
+
|R
|output pin 8 on
+
|shutter off, up position
 
|-
 
|-
|}
+
|offdown
 
+
|R
You can also set the value to “on” or “off”, that is equivalent to 1 and 0.
+
|shutter off, down position
 
 
----
 
 
 
=== MODREL ===
 
 
 
8 relay output compact module in DIN 3M housing.
 
 
 
It uses one output address in the range 1 to 127 of the Contatto bus.
 
 
 
{| class="wikitable"
 
!ID
 
!Value
 
!R/W
 
!Description
 
 
|-
 
|-
  
Line 2,187: Line 2,420:
 
|output pin 4 on
 
|output pin 4 on
 
|-
 
|-
 +
|}
 +
 +
You can also set the value to “on” or “off”, that is equivalent to 1 and 0.
  
|rowspan="2"|o<address>.5
+
----
|0
 
|RW
 
|output pin 5 off
 
|-
 
|1
 
|RW
 
|output pin 5 on
 
|-
 
  
|rowspan="2"|o<address>.6
+
=== MOD2-2R ===
|0
+
 
|RW
+
2 digital input and 2 power relay output module.
|output pin 6 off
+
 
 +
It uses one input address and one output address in the range 1 to 127 of the Contatto bus.
 +
 
 +
The input and the output addresses may be the same or they can be different each one to the other.
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 +
|-
 +
 
 +
|rowspan="2"|i<address>.1
 +
|0
 +
|R
 +
|input pin 1 off
 +
|-
 +
|1
 +
|R
 +
|input pin 1 on
 +
|-
 +
 
 +
|rowspan="2"|i<address>.2
 +
|0
 +
|R
 +
|input pin 2 off
 
|-
 
|-
 
|1
 
|1
|RW
+
|R
|output pin 6 on
+
|input pin 2 on
 
|-
 
|-
  
|rowspan="2"|o<address>.7
+
|rowspan="2"|o<address>.1
 
|0
 
|0
 
|RW
 
|RW
|output pin 7 off
+
|output pin 1 off
 
|-
 
|-
 
|1
 
|1
 
|RW
 
|RW
|output pin 7 on
+
|output pin 1 on
 
|-
 
|-
  
|rowspan="2"|o<address>.8
+
|rowspan="2"|o<address>.2
 
|0
 
|0
 
|RW
 
|RW
|output pin 8 off
+
|output pin 2 off
 
|-
 
|-
 
|1
 
|1
 
|RW
 
|RW
|output pin 8 on
+
|output pin 2 on
 
|-
 
|-
 +
 
|}
 
|}
  
Line 2,233: Line 2,487:
 
----
 
----
  
=== MOAN/U ===
+
=== MOD4-4R ===
 +
 
 +
4 digital input and 4 digital output module.
  
0÷10V analog output module.
+
It uses one input address and one output address in the range 1 to 127 of the Contatto bus.  
  
It uses one output address in the range 1 to 127 of the Contatto bus.
+
The input and the output addresses may be the same or they can be different each one to the other.
  
 
{| class="wikitable"
 
{| class="wikitable"
Line 2,246: Line 2,502:
 
|-
 
|-
  
|o<address>
+
|rowspan="2"|i<address>.1
|x/255
+
|0
 +
|R
 +
|input pin 1 off
 +
|-
 +
|1
 
|R
 
|R
|value in fractional format, where 0 &le; x &le; 255
+
|input pin 1 on
 
|-
 
|-
  
|rowspan="3"|o<address>
+
|rowspan="2"|i<address>.2
|<x%>
+
|0
|W
+
|R
|the percentage of signal (0÷100%) applied to the output
+
|input pin 2 off
 +
|-
 +
|1
 +
|R
 +
|input pin 2 on
 
|-
 
|-
|0...255
+
 
|W
+
|rowspan="2"|i<address>.3
|convert the 8 bits digital code received through the bus in the proper analog level.
+
|0
 +
|R
 +
|input pin 3 off
 
|-
 
|-
|x/y
+
|1
|W
+
|R
|fractional format, formatted as “x/y”, where 0 &le; x &le; y
+
|input pin 3 on
 
|-
 
|-
|}
 
  
----
+
|rowspan="2"|i<address>.4
 
+
|0
=== MO420 ===
+
|R
 +
|input pin 4 off
 +
|-
 +
|1
 +
|R
 +
|input pin 4 on
 +
|-
  
4÷20mA analog output module.
+
|rowspan="2"|o<address>.1
 +
|0
 +
|RW
 +
|output pin 1 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 1 on
 +
|-
  
It uses one output address in the range 1 to 127 of the Contatto bus.
+
|rowspan="2"|o<address>.2
 
+
|0
{| class="wikitable"
+
|RW
!ID
+
|output pin 2 off
!Value
 
!R/W
 
!Description
 
 
|-
 
|-
 
+
|1
|rowspan="3"|o<address>
 
|<x%>
 
 
|RW
 
|RW
|the percentage of signal (0÷100%) applied to the output
+
|output pin 2 on
 
|-
 
|-
|0...255
+
 
 +
|rowspan="2"|o<address>.3
 +
|0
 
|RW
 
|RW
|convert the 8 bits digital code received through the bus in the proper analog level
+
|output pin 3 off
 
|-
 
|-
|x/y
+
|1
 
|RW
 
|RW
|fractional format, formatted as “x/y”, where 0 &le; x &le; y
+
|output pin 3 on
 
|-
 
|-
|}
 
  
----
+
|rowspan="2"|o<address>.4
 +
|0
 +
|RW
 +
|output pin 4 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 4 on
 +
|-
  
=== MODLC and MODLC-P ===
+
|}
 +
 
 +
----
 +
 
 +
=== MOD2DM ===
 +
 
 +
2x300W dimmer module.
  
Ambient light regulator module with integrated sensor.
+
It uses 2 output addresses (one for each dimmer channel) and 2 input addresses.  
  
It uses one input address and, if enabled by the configuration panel of MCP IDE, one output address with the same value.
+
HSYCO supports this module only when its dip-switches are set as SW1=ON, SW2=ON, SW3=ON, SW4=ON.
  
 
{| class="wikitable"
 
{| class="wikitable"
Line 2,312: Line 2,601:
 
|-
 
|-
  
|i<address>.lux
+
|rowspan="2"|i<address>
|value equivalent to three times the brightness in lux detected by the sensor
+
|0...100
 
|R
 
|R
|the brightness value in lux detected by the MODLC
+
|brightness level according to current ramp
 
|-
 
|-
 
+
|off
|i<address>.level
 
|calculated value for the automatic brightness regulation
 
 
|R
 
|R
|the value to be sent to the dimmer in order to execute the automatic regulation
+
|dimmer off
 
|-
 
|-
  
|rowspan="2"|i<address>.mode
+
|rowspan="2"|i<address+1>
|auto
+
|0...100
 
|R
 
|R
|automatic regulation
+
|brightness level according to current ramp
 
|-
 
|-
|man
+
|off
 
|R
 
|R
|manual regulation
+
|dimmer off
 
|-
 
|-
  
|rowspan="2"|i<address>.in
+
|rowspan="3"|o<address>
|0
+
|0...100
|R
+
|RW
|digital input OFF
+
|brightness level according to current ramp
 
|-
 
|-
|1
+
|off
|R
+
|RW
|digital input ON
+
|dimmer off
 
|-
 
|-
 
+
|101...255
|o<address>.setpoint
+
|W
|setpoint value
+
|command (see MOD2DM commands table)
|RW
 
|set the setpoint for the automatic brightness regulation
 
 
|-
 
|-
  
|rowspan="2"|o<address>.mode
+
|rowspan="3"|o<address+1>
|auto
+
|0...100
 
|RW
 
|RW
|set automatic regulation
+
|brightness level according to current ramp
 
|-
 
|-
|man
+
|off
 
|RW
 
|RW
|set manual regulation
+
|dimmer off
 
|-
 
|-
 
+
|101...255
|rowspan="2"|o<address>.in.reset
+
|W
|0
+
|command (see MOD2DM commands table)
|RW
 
|not active
 
|-
 
|1
 
|R
 
|force the expiring of the deactivation delay time of the digital input
 
 
|-
 
|-
  
|rowspan="2"|o<address>.mode.reset
 
|0
 
|RW
 
|not active
 
|-
 
|1
 
|R
 
|disable the automatic regulation and it reset the input channel
 
|-
 
 
|}
 
|}
 +
 +
The dimmer level can be set using additional formats besides the standard percent values:
 +
*absolute positive integer number between 0 and 100
 +
*percent number, formatted as x%
 +
*fractional format, formatted as “n/m”, where 0 <= n <= m.
  
 
----
 
----
  
=== MOD4-4S ===
+
=== MOD2DV ===
  
4 digital input and 4 power relay output multifunction module.
+
Dual 1-10V output for electronic ballast driving.
  
HSYCO supports two configurations only: four independent outputs, or two shutters.
+
It uses 2 output addresses (one for each dimmer channel) and 2 input addresses.  
  
When set as four independent outputs, the module must be configured with the same base address for input and output.
+
HSYCO supports this module only when its dip-switches are set as SW1=ON, SW2=ON, SW3=ON, SW4=ON.
 
 
For example:
 
<pre>
 
(I20, O20)
 
</pre>
 
The input address must be enabled. Configuration switches must be set as SW1=OFF, SW2=OFF and SW5=ON.
 
 
 
When set as two shutters, the module must be configured with the same base address for input and output.
 
 
 
For example:
 
<pre>
 
(I20, O20, O21)
 
</pre>
 
The input address must be enabled. Configuration switches must be set as SW1=ON, SW2=ON and SW5=ON.
 
  
 
{| class="wikitable"
 
{| class="wikitable"
Line 2,412: Line 2,673:
 
|-
 
|-
  
|rowspan="2"|i<address>.1
+
|rowspan="2"|i<address>
|0
+
|0...100
 
|R
 
|R
|input pin 1 off
+
|brightness level according to current ramp
 
|-
 
|-
|1
+
|off
 
|R
 
|R
|input pin 1 on
+
|dimmer off
 
|-
 
|-
  
|rowspan="2"|i<address>.2
+
|rowspan="2"|i<address+1>
|0
+
|0...100
 
|R
 
|R
|input pin 2 off
+
|brightness level according to current ramp
 
|-
 
|-
|1
+
|off
 
|R
 
|R
|input pin 2 on
+
|dimmer off
 
|-
 
|-
  
|rowspan="2"|i<address>.3
+
|rowspan="3"|o<address>
|0
+
|0...100
|R
+
|RW
|input pin 3 off
+
|brightness level according to current ramp
 
|-
 
|-
|1
+
|off
|R
+
|RW
|input pin 3 on
+
|dimmer off
 
|-
 
|-
 
+
|101...255
|rowspan="2"|i<address>.4
+
|W
|0
+
|command (see MOD2DV commands table)
|R
 
|input pin 4 off
 
|-
 
|1
 
|R
 
|input pin 4 on
 
 
|-
 
|-
  
|rowspan="6"|o<address>.1
+
|rowspan="3"|o<address+1>
|up
+
|0...100
 
|RW
 
|RW
|shutter up command
+
|brightness level according to current ramp
 
|-
 
|-
|down
+
|off
 
|RW
 
|RW
|shutter down command
+
|dimmer off
 
|-
 
|-
|stop
+
|101...255
|RW
+
|W
|shutter stop command
+
|command (see MOD2DV commands table)
|-
 
|unknown
 
|R
 
|unknown state
 
|-
 
|offup
 
|RW
 
|shutter off, up position
 
|-
 
|offdown
 
|RW
 
|shutter off, down position
 
 
|-
 
|-
  
|rowspan="6"|o<address+1>.1
+
|}
|up
+
 
|RW
+
The dimmer level can be set using additional formats besides the standard percent values:
|shutter up command
+
*absolute positive integer number between 0 and 100
 +
*percent number, formatted as x%
 +
*fractional format, formatted as “n/m”, where 0 <= n <= m.
 +
 
 +
----
 +
 
 +
=== MOD8IL ===
 +
 
 +
8 digital input – 8 LED output module for wall box.
 +
 
 +
It uses 1 input address and 1 output address.
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 
|-
 
|-
|down
+
 
|RW
+
|rowspan="2"|i<address>.1
|shutter down command
+
|0
 +
|R
 +
|input pin 1 off
 
|-
 
|-
|stop
+
|1
|RW
 
|shutter stop command
 
|-
 
|unknown
 
 
|R
 
|R
|unknown state
+
|input pin 1 on
|-
 
|offup
 
|RW
 
|shutter off, up position
 
|-
 
|offdown
 
|RW
 
|shutter off, down position
 
 
|-
 
|-
  
|rowspan="2"|o<address>.1
+
|rowspan="2"|i<address>.2
 
|0
 
|0
|RW
+
|R
|output pin 1 off
+
|input pin 2 off
 
|-
 
|-
 
|1
 
|1
|RW
+
|R
|output pin 1 on
+
|input pin 2 on
 
|-
 
|-
  
|rowspan="2"|o<address>.2
+
|rowspan="2"|i<address>.3
 
|0
 
|0
|RW
+
|R
|output pin 2 off
+
|input pin 3 off
 
|-
 
|-
 
|1
 
|1
|RW
+
|R
|output pin 2 on
+
|input pin 3 on
 
|-
 
|-
  
|rowspan="2"|o<address>.3
+
|rowspan="2"|i<address>.4
 
|0
 
|0
|RW
+
|R
|output pin 3 off
+
|input pin 4 off
 
|-
 
|-
 
|1
 
|1
|RW
+
|R
|output pin 3 on
+
|input pin 4 on
 
|-
 
|-
  
|rowspan="2"|o<address>.4
+
|rowspan="2"|i<address>.5
 
|0
 
|0
|RW
+
|R
|output pin 4 off
+
|input pin 5 off
 
|-
 
|-
 
|1
 
|1
|RW
+
|R
|output pin 4 on
+
|input pin 5 on
 
|-
 
|-
|}
 
  
You can also set the value to “on” or “off”, that is equivalent to 1 and 0.
+
|rowspan="2"|i<address>.6
 +
|0
 +
|R
 +
|input pin 6 off
 +
|-
 +
|1
 +
|R
 +
|input pin 6 on
 +
|-
  
----
+
|rowspan="2"|i<address>.7
 
+
|0
=== MOD2-2R ===
+
|R
 
+
|input pin 7 off
2 digital input and 2 power relay output module.
 
 
 
It uses one input address and one output address in the range 1 to 127 of the Contatto bus.
 
 
 
The input and the output addresses may be the same or they can be different each one to the other.
 
 
 
{| class="wikitable"
 
!ID
 
!Value
 
!R/W
 
!Description
 
|-
 
 
 
|rowspan="2"|i<address>.1
 
|0
 
|R
 
|input pin 1 off
 
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 1 on
+
|input pin 7 on
 
|-
 
|-
  
|rowspan="2"|i<address>.2
+
|rowspan="2"|i<address>.8
 
|0
 
|0
 
|R
 
|R
|input pin 2 off
+
|input pin 8 off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 2 on
+
|input pin 8 on
 
|-
 
|-
  
Line 2,604: Line 2,843:
 
|-
 
|-
  
|}
+
|rowspan="2"|o<address>.3
 +
|0
 +
|RW
 +
|output pin 3 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 3 on
 +
|-
  
You can also set the value to “on” or “off”, that is equivalent to 1 and 0.
+
|rowspan="2"|o<address>.4
 +
|0
 +
|RW
 +
|output pin 4 off
 +
|-
 +
|1
 +
|RW
 +
|output pin 4 on
 +
|-
  
----
+
|rowspan="2"|o<address>.5
 
 
=== MOD4-4R ===
 
 
 
4 digital input and 4 digital output module.
 
 
 
It uses one input address and one output address in the range 1 to 127 of the Contatto bus.
 
 
 
The input and the output addresses may be the same or they can be different each one to the other.
 
 
 
{| class="wikitable"
 
!ID
 
!Value
 
!R/W
 
!Description
 
|-
 
 
 
|rowspan="2"|i<address>.1
 
 
|0
 
|0
|R
+
|RW
|input pin 1 off
+
|output pin 5 off
 
|-
 
|-
 
|1
 
|1
|R
+
|RW
|input pin 1 on
+
|output pin 5 on
 
|-
 
|-
  
|rowspan="2"|i<address>.2
+
|rowspan="2"|o<address>.6
 
|0
 
|0
|R
+
|RW
|input pin 2 off
+
|output pin 6 off
 
|-
 
|-
 
|1
 
|1
|R
+
|RW
|input pin 2 on
+
|output pin 6 on
 
|-
 
|-
  
|rowspan="2"|i<address>.3
+
|rowspan="2"|o<address>.7
 
|0
 
|0
|R
+
|RW
|input pin 3 off
+
|output pin 7 off
 
|-
 
|-
 
|1
 
|1
|R
+
|RW
|input pin 3 on
+
|output pin 7 on
 
|-
 
|-
  
|rowspan="2"|i<address>.4
+
|rowspan="2"|o<address>.8
 
|0
 
|0
|R
+
|RW
|input pin 4 off
+
|output pin 8 off
 
|-
 
|-
 
|1
 
|1
|R
 
|input pin 4 on
 
|-
 
 
|rowspan="2"|o<address>.1
 
|0
 
 
|RW
 
|RW
|output pin 1 off
+
|output pin 8 on
|-
 
|1
 
|RW
 
|output pin 1 on
 
 
|-
 
|-
 +
|}
  
|rowspan="2"|o<address>.2
+
You can also set the value to “on” or “off”, that is equivalent to 1 and 0.
|0
 
|RW
 
|output pin 2 off
 
|-
 
|1
 
|RW
 
|output pin 2 on
 
|-
 
  
|rowspan="2"|o<address>.3
+
----
|0
 
|RW
 
|output pin 3 off
 
|-
 
|1
 
|RW
 
|output pin 3 on
 
|-
 
  
|rowspan="2"|o<address>.4
+
=== MOD4DV ===
|0
 
|RW
 
|output pin 4 off
 
|-
 
|1
 
|RW
 
|output pin 4 on
 
|-
 
  
|}
+
Quad 0-10V output module for generic applications or for external dimmers control.
  
----
+
It uses 4 consecutive output addresses (one for each dimmer channel) and 4 input addresses.
  
=== MOD2DM ===
+
HSYCO supports this module only when its dip-switches are set as SW1=ON, SW2=ON, SW3=ON, SW4=ON, SW5=OFF.
 
 
2x300W dimmer module.
 
 
 
It uses 2 output addresses (one for each dimmer channel) and 2 input addresses.
 
 
 
HSYCO supports this module only when its dip-switches are set as SW1=ON, SW2=ON, SW3=ON, SW4=ON.
 
  
 
{| class="wikitable"
 
{| class="wikitable"
Line 2,735: Line 2,934:
  
 
|rowspan="2"|i<address+1>
 
|rowspan="2"|i<address+1>
 +
|0...100
 +
|R
 +
|brightness level according to current ramp
 +
|-
 +
|off
 +
|R
 +
|dimmer off
 +
|-
 +
 +
|rowspan="2"|i<address+2>
 +
|0...100
 +
|R
 +
|brightness level according to current ramp
 +
|-
 +
|off
 +
|R
 +
|dimmer off
 +
|-
 +
 +
|rowspan="2"|i<address+3>
 
|0...100
 
|0...100
 
|R
 
|R
Line 2,755: Line 2,974:
 
|101...255
 
|101...255
 
|W
 
|W
|command (see MOD2DM commands table)
+
|command (see MOD4DV commands table)
 
|-
 
|-
  
Line 2,769: Line 2,988:
 
|101...255
 
|101...255
 
|W
 
|W
|command (see MOD2DM commands table)
+
|command (see MOD4DV commands table)
 
|-
 
|-
  
|}
+
|rowspan="3"|o<address+2>
 +
|0...100
 +
|RW
 +
|brightness level according to current ramp
 +
|-
 +
|off
 +
|RW
 +
|dimmer off
 +
|-
 +
|101...255
 +
|W
 +
|command (see MOD4DV commands table)
 +
|-
  
The dimmer level can be set using additional formats besides the standard percent values:
+
|rowspan="3"|o<address+3>
 +
|0...100
 +
|RW
 +
|brightness level according to current ramp
 +
|-
 +
|off
 +
|RW
 +
|dimmer off
 +
|-
 +
|101...255
 +
|W
 +
|command (see MOD4DV commands table)
 +
|-
 +
 
 +
|}
 +
 
 +
The dimmer level can be set using additional formats besides the standard percent values:
 
*absolute positive integer number between 0 and 100
 
*absolute positive integer number between 0 and 100
 
*percent number, formatted as x%
 
*percent number, formatted as x%
*fractional format, formatted as “n/m”, where 0 <= n <= m.
+
*fractional format, formatted as “x/y”, where 0 <= x <= y
 +
*values in the range 101÷255. Values and commands are described in the MOD4DV Programming Handbook (Operation from the bus, page 3).
  
 
----
 
----
  
=== MOD2DV ===
+
=== MODDMX ===
  
Dual 1-10V output for electronic ballast driving.
+
ModDMX module allows to handle, through the Contatto bus, up to 32 DMX devices. ModDMX module makes possible the communication on the first 64 of 512 DMX channels allowed by this protocol.
  
It uses 2 output addresses (one for each dimmer channel) and 2 input addresses.
+
It uses 1 output address, 1-channel 16-bit.
 
 
HSYCO supports this module only when its dip-switches are set as SW1=ON, SW2=ON, SW3=ON, SW4=ON.
 
  
 
{| class="wikitable"
 
{| class="wikitable"
Line 2,796: Line 3,042:
 
|-
 
|-
  
|rowspan="2"|i<address>
+
|o<address>.<DMX address>
 
|0...100
 
|0...100
|R
+
|RW
|brightness level according to current ramp
+
|Values and commands are described in the MODDMX Programming Handbook
|-
 
|off
 
|R
 
|dimmer off
 
 
|-
 
|-
  
|rowspan="2"|i<address+1>
+
|}
|0...100
+
 
|R
+
----
|brightness level according to current ramp
 
|-
 
|off
 
|R
 
|dimmer off
 
|-
 
  
|rowspan="3"|o<address>
+
=== MODDALI ===
|0...100
+
 
 +
The ModDALI module supports 4 DALI lines, with up to 32 devices for each line.
 +
The ModDALI module with firmware version 6.x supports 2 DALI lines (channels 1 and 2), with up to 64 devices for each line.
 +
 
 +
It uses 1 output address and, if enabled, 1 input address with the same value.
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 +
|-
 +
 
 +
|o<address>.<line>
 +
|refresh
 
|RW
 
|RW
|brightness level according to current ramp
+
|update the state of the DALI devices
 
|-
 
|-
 +
 +
|rowspan="2"|o<address>.<line><br/>o<address>.<line>.all<br/>o<address>.<line>.0
 
|off
 
|off
 
|RW
 
|RW
|dimmer off
+
|switch off all available DALI devices
 
|-
 
|-
|101...255
+
|<level>
|W
+
|RW
|command (see MOD2DV commands table)
+
|set a level for all available devices
 
|-
 
|-
  
|rowspan="3"|o<address+1>
+
|rowspan="2"|o<address>.<line>.group.<DALI group>
|0...100
+
|off
 +
|RW
 +
|switch off all DALI devices on that group
 +
|-
 +
|<level>
 
|RW
 
|RW
|brightness level according to current ramp
+
|set a level for all DALI devices in that group
 
|-
 
|-
 +
 +
|rowspan="5"|o<address>.<line>.<DALI address>
 
|off
 
|off
 
|RW
 
|RW
|dimmer off
+
|switch off a single DALI device
 
|-
 
|-
|101...255
+
|<level>
|W
+
|RW
|command (see MOD2DV commands table)
+
|set a level for a single DALI device
 
|-
 
|-
 
+
|fault
|}
+
|R
 
+
|DALI device fault
The dimmer level can be set using additional formats besides the standard percent values:
 
*absolute positive integer number between 0 and 100
 
*percent number, formatted as x%
 
*fractional format, formatted as “n/m”, where 0 <= n <= m.
 
 
 
----
 
 
 
=== MOD8IL ===
 
 
 
8 digital input – 8 LED output module for wall box.
 
 
 
It uses 1 input address and 1 output address.
 
 
 
{| class="wikitable"
 
!ID
 
!Value
 
!R/W
 
!Description
 
 
|-
 
|-
 
+
|unknown
|rowspan="2"|i<address>.1
 
|0
 
 
|R
 
|R
|input pin 1 off
+
|DALI device unknown state (or connection lost)
 
|-
 
|-
|1
+
|>100
|R
+
|RW
|input pin 1 on
+
|special functions: possible values are described in the MODDALI Programming Handbook
 
|-
 
|-
  
|rowspan="2"|i<address>.2
+
|rowspan="2"|i<address>.<line>.polling
|0
+
|off
 
|R
 
|R
|input pin 2 off
+
|polling disabled
 
|-
 
|-
|1
+
|on
 
|R
 
|R
|input pin 2 on
+
|polling enabled
 
|-
 
|-
  
|rowspan="2"|i<address>.3
+
|rowspan="2"|i<address>.<line>.test
 
|0
 
|0
 
|R
 
|R
|input pin 3 off
+
|test button not pressed
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 3 on
+
|test button pressed
 
|-
 
|-
  
|rowspan="2"|i<address>.4
+
|rowspan="4"|i<address>.<line>.dali
|0
+
|nopower
 
|R
 
|R
|input pin 4 off
+
|DALI bus power supply failure
 
|-
 
|-
|1
+
|open
 
|R
 
|R
|input pin 4 on
+
|DALI line broken
 
|-
 
|-
 
+
|short
|rowspan="2"|i<address>.5
 
|0
 
 
|R
 
|R
|input pin 5 off
+
|DALI line short circuit
 
|-
 
|-
|1
+
|on
 
|R
 
|R
|input pin 5 on
+
|on DALI line
 
|-
 
|-
  
|rowspan="2"|i<address>.6
+
|rowspan="4"|i<address>.<line>.1
|0
+
|off
 
|R
 
|R
|input pin 6 off
+
|ballast 1 off
 
|-
 
|-
|1
+
|<level>
 
|R
 
|R
|input pin 6 on
+
|ballast 1 level
 
|-
 
|-
 
+
|fault
|rowspan="2"|i<address>.7
 
|0
 
 
|R
 
|R
|input pin 7 off
+
|ballast 1 lamp failure
 
|-
 
|-
|1
+
|unknown
 
|R
 
|R
|input pin 7 on
+
|ballast 1 lamp unknown state (or connection lost)
 
|-
 
|-
  
|rowspan="2"|i<address>.8
+
|}
|0
+
 
|R
+
The DALI device level can be set using additional formats besides the standard percent values:
|input pin 8 off
+
*absolute positive integer number between 0 and 100
|-
+
*percent number, formatted as x%
|1
+
*fractional format, formatted as “x/y”, where 0 <= x <= y
|R
+
*values in the range 101÷255. Values and commands are described in the MODDALI Programming Handbook.
|input pin 8 on
 
|-
 
  
|rowspan="2"|o<address>.1
+
----
|0
+
 
|RW
+
=== MODDALI8 ===
|output pin 1 off
+
 
|-
+
The ModDALI8 module allows the management of 8 DALI lines, with up to 16 devices for each line (or channel).
|1
+
 
|RW
+
It uses 2 consecutive input addresses and 1 input address with the same base value.
|output pin 1 on
+
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 
|-
 
|-
  
|rowspan="2"|o<address>.2
+
|rowspan="2"|o<address>.<line>
|0
+
|off
 
|RW
 
|RW
|output pin 2 off
+
|off broadcast command
 
|-
 
|-
|1
+
|<level>
 
|RW
 
|RW
|output pin 2 on
+
|level broadcast command
 
|-
 
|-
  
|rowspan="2"|o<address>.3
+
|rowspan="2"|i<address>.<line>.polling
|0
+
|off
 
|RW
 
|RW
|output pin 3 off
+
|polling disabled
 
|-
 
|-
|1
+
|on
 
|RW
 
|RW
|output pin 3 on
+
|polling enabled
 
|-
 
|-
  
|rowspan="2"|o<address>.4
+
|rowspan="2"|i<address>.<line>.test
 
|0
 
|0
 
|RW
 
|RW
|output pin 4 off
+
|test button not pressed
 
|-
 
|-
 
|1
 
|1
 
|RW
 
|RW
|output pin 4 on
+
|test button pressed
 
|-
 
|-
  
|rowspan="2"|o<address>.5
+
|rowspan="4"|i<address>.<line>.dali
|0
+
|fault
 
|RW
 
|RW
|output pin 5 off
+
|lamp failure
 
|-
 
|-
|1
+
|open
 
|RW
 
|RW
|output pin 5 on
+
|no DALI device connected to this line
 
|-
 
|-
 
+
|short
|rowspan="2"|o<address>.6
 
|0
 
 
|RW
 
|RW
|output pin 6 off
+
|DALI line short circuit
 
|-
 
|-
|1
+
|on
 
|RW
 
|RW
|output pin 6 on
+
|DALI line working correctly
 
|-
 
|-
  
|rowspan="2"|o<address>.7
+
|}
|0
+
 
|RW
+
<line> can be set from 1 to 8 to address a single line, or 0 to send commands to all DALI lines.
|output pin 7 off
 
|-
 
|1
 
|RW
 
|output pin 7 on
 
|-
 
  
|rowspan="2"|o<address>.8
 
|0
 
|RW
 
|output pin 8 off
 
|-
 
|1
 
|RW
 
|output pin 8 on
 
|-
 
|}
 
  
You can also set the value to “on” or “off”, that is equivalent to 1 and 0.
+
The line level can be set using additional formats besides the standard percent values:
 +
*absolute positive integer number between 0 and 100
 +
*percent number, formatted as x%
 +
*fractional format, formatted as “x/y”, where 0 <= x <= y
 +
*values in the range 101÷255. Values and commands are described in the MODDALI8 Programming Handbook.
  
 
----
 
----
  
=== MOD4DV ===
+
=== CLIMA2 ===
  
Quad 0-10V output module for generic applications or for external dimmers control.
+
Module for the regulation of the ambient temperature.
  
It uses 4 consecutive output addresses (one for each dimmer channel) and 4 input addresses.
+
It uses 1 input and 1 output address that are equal each one to the other, so only a base address is needed.
 
 
HSYCO supports this module only when its dip-switches are set as SW1=ON, SW2=ON, SW3=ON, SW4=ON, SW5=OFF.
 
  
 
{| class="wikitable"
 
{| class="wikitable"
Line 3,047: Line 3,268:
  
 
|rowspan="2"|i<address>
 
|rowspan="2"|i<address>
|0...100
+
|on
 
|R
 
|R
|brightness level according to current ramp
+
|zone on
 
|-
 
|-
 
|off
 
|off
 
|R
 
|R
|dimmer off
+
|zone off
 
|-
 
|-
  
|rowspan="2"|i<address+1>
+
|rowspan="2"|i<address>.mode
|0...100
+
|summer
 
|R
 
|R
|brightness level according to current ramp
+
|summer mode
 
|-
 
|-
|off
+
|winter
 
|R
 
|R
|dimmer off
+
|winter mode
 
|-
 
|-
  
|rowspan="2"|i<address+2>
+
|rowspan="3"|i<address>.status
|0...100
+
|off
 
|R
 
|R
|brightness level according to current ramp
+
|off status
 
|-
 
|-
|off
+
|heating
 
|R
 
|R
|dimmer off
+
|heating request
 
|-
 
|-
 
+
|cooling
|rowspan="2"|i<address+3>
 
|0...100
 
 
|R
 
|R
|brightness level according to current ramp
+
|cooling request
 
|-
 
|-
 +
 +
|rowspan="4"|i<address>.fan
 
|off
 
|off
 
|R
 
|R
|dimmer off
+
|fan off
 
|-
 
|-
 
+
|min
|rowspan="3"|o<address>
+
|R
|0...100
+
|min speed
|RW
 
|brightness level according to current ramp
 
 
|-
 
|-
|off
+
|med
|RW
+
|R
|dimmer off
+
|med speed
 
|-
 
|-
|101...255
+
|max
|W
+
|R
|command (see MOD4DV commands table)
+
|max speed
 
|-
 
|-
  
|rowspan="3"|o<address+1>
+
|rowspan="2"|i<address>.temp
|0...100
+
|fault
|RW
+
|R
|brightness level according to current ramp
+
|NTC probe fault
 
|-
 
|-
|off
+
|<temp>
|RW
+
|R
|dimmer off
+
|ambient temperature value, in C/10
 +
|-
 +
 
 +
|i<address>.setpoint.temp
 +
|<temp>
 +
|R
 +
|real setpoint value, in C/10
 
|-
 
|-
|101...255
+
 
|W
+
|i<address>.knob
|command (see MOD4DV commands table)
+
|0 ... 1000
 +
|R
 +
|position of rotary knob
 
|-
 
|-
  
|rowspan="3"|o<address+2>
+
|rowspan="2"|o<address>.mode
|0...100
+
|summer
 
|RW
 
|RW
|brightness level according to current ramp
+
|set summer
 
|-
 
|-
|off
+
|winter
 
|RW
 
|RW
|dimmer off
+
|set winter
|-
 
|101...255
 
|W
 
|command (see MOD4DV commands table)
 
 
|-
 
|-
  
|rowspan="3"|o<address+3>
+
|rowspan="2"|o<address>
|0...100
+
|on
 
|RW
 
|RW
|brightness level according to current ramp
+
|zone on
 
|-
 
|-
 
|off
 
|off
 
|RW
 
|RW
|dimmer off
+
|zone off
|-
 
|101...255
 
|W
 
|command (see MOD4DV commands table)
 
 
|-
 
|-
  
|}
+
|o<address>.setpoint.temp
 
+
|0...400
The dimmer level can be set using additional formats besides the standard percent values:
+
|RW
*absolute positive integer number between 0 and 100
+
|set and read the value of central setpoint (temp in C/10)
*percent number, formatted as x%
 
*fractional format, formatted as “x/y”, where 0 <= x <= y
 
*values in the range 101÷255. Values and commands are described in the MOD4DV Programming Handbook (Operation from the bus, page 3).
 
 
 
----
 
 
 
=== MODDMX ===
 
 
 
ModDMX module allows to handle, through the Contatto bus, up to 32 DMX devices. ModDMX module makes possible the communication on the first 64 of 512 DMX channels allowed by this protocol.
 
 
 
It uses 1 output address, 1-channel 16-bit.
 
 
 
{| class="wikitable"
 
!ID
 
!Value
 
!R/W
 
!Description
 
 
|-
 
|-
  
|o<address>.<DMX address>
+
|o<address>.setpoint.delta.neg
|0...100
+
|<temp>
 
|RW
 
|RW
|Values and commands are described in the MODDMX Programming Handbook
+
|set and read the MAX negative delta
 
|-
 
|-
  
|}
+
|o<address>.setpoint.delta.pos
 
+
|<temp>
----
+
|RW
 
+
|set and read the MAX positive delta
=== MODDALI ===
 
 
 
ModDALI module allows the management, through the Contatto bus, of 4 DALI lines upon it's possible to connect up to 32 devices for line (or channel). In this way it's possible to control and regulate up to 128 DALI ballasts (or other similar devices).
 
 
 
It uses 1 output address and, if enabled, 1 input address with the same value.
 
 
 
{| class="wikitable"
 
!ID
 
!Value
 
!R/W
 
!Description
 
 
|-
 
|-
  
|o<address>.<channel>
+
|rowspan="4"|o<address>.led.1
|refresh
+
|red<br/>r
 
|RW
 
|RW
|update the state of the DALI devices
+
|LED 1 red
 
|-
 
|-
 
+
|green<br/>g
|rowspan="2"|o<address>.<channel><br/>o<address>.<channel>.all<br/>o<address>.<channel>.0
 
|off
 
 
|RW
 
|RW
|switch off all available DALI devices
+
|LED 1 green
 
|-
 
|-
|<level>
+
|yellow<br/>y
 
|RW
 
|RW
|set a level for all available devices
+
|LED 1 yellow
 
|-
 
|-
 
|rowspan="2"|o<address>.<channel>.group.<DALI group>
 
 
|off
 
|off
 
|RW
 
|RW
|switch off all DALI devices on that group
+
|set off
|-
 
|<level>
 
|RW
 
|set a level for all DALI devices in that group
 
 
|-
 
|-
  
|rowspan="4"|o<address>.<channel>.<DALI address>
+
|rowspan="4"|o<address>.led.2
|off
+
|red<br/>r
 
|RW
 
|RW
|switch off a single DALI device
+
|LED 2 red
 
|-
 
|-
|<level>
+
|green<br/>g
 
|RW
 
|RW
|set a level for a single DALI device
+
|LED 2 green
 
|-
 
|-
|fault
+
|yellow<br/>y
|R
 
|DALI device fault
 
|-
 
|>100
 
 
|RW
 
|RW
|special functions: possible values are described in the MODDALI Programming Handbook
+
|LED 2 yellow
 
|-
 
|-
 
|rowspan="2"|i<address>.<channel>.polling
 
 
|off
 
|off
 
|RW
 
|RW
|polling disabled
+
|set off
 
|-
 
|-
|on
+
 
 +
|rowspan="4"|o<address>.led.3
 +
|red<br/>r
 
|RW
 
|RW
|polling enabled
+
|LED 3 red
 
|-
 
|-
 
+
|green<br/>g
|rowspan="2"|i<address>.<channel>.test
 
|0
 
 
|RW
 
|RW
|test button not pressed
+
|LED 3 green
 
|-
 
|-
|1
+
|yellow<br/>y
 
|RW
 
|RW
|test button pressed
+
|LED 3 yellow
 
|-
 
|-
 
+
|off
|rowspan="4"|i<address>.<channel>.dali
 
|nopower
 
 
|RW
 
|RW
|lamp failure
+
|set off
 
|-
 
|-
|open
+
 
 +
|rowspan="4"|o<address>.led.4
 +
|red<br/>r
 
|RW
 
|RW
|DALI line broken
+
|LED 4 red
 
|-
 
|-
|short
+
|green<br/>g
 
|RW
 
|RW
|DALI line short circuit
+
|LED 4 green
 
|-
 
|-
|on
+
|yellow<br/>y
 
|RW
 
|RW
|on DALI line
+
|LED 4 yellow
 
|-
 
|-
 
+
|off
|rowspan="2"|i<address>.<channel>.1
 
|fault
 
 
|RW
 
|RW
|ballast 1 lamp failure
+
|set off
|-
 
|unknown
 
|R
 
|ballast 1 lamp unknown state
 
 
|-
 
|-
  
 
|}
 
|}
  
The channel level can be set using additional formats besides the standard percent values:
+
You can also set the value to “on” or “off”, that is equivalent to 1 and 0.
*absolute positive integer number between 0 and 100
 
*percent number, formatted as x%
 
*fractional format, formatted as “x/y”, where 0 <= x <= y
 
*values in the range 101÷255. Values and commands are described in the MODDALI Programming Handbook.
 
  
 
----
 
----
  
=== CLIMA2 ===
+
=== MODANA ===
  
Module for the regulation of the ambient temperature.
+
Network analyzer module for Contatto bus.
  
It uses 1 input and 1 output address that are equal each one to the other, so only a base address is needed.
+
It uses, in dynamic mode, up to a maximum of 5 consecutive input addresses and, if enabled, 1 output address equal to the base address.
  
{| class="wikitable"
+
{{note|The module's firmware should be version 1.5 or later to support negative values for active power readings.}}
!ID
 
!Value
 
!R/W
 
!Description
 
|-
 
  
|rowspan="2"|i<address>
+
{{tip|The module must be configured with the same base address for input and output.}}
|on
+
 
|R
+
For example:
|zone on
+
<pre>
 +
(I7, O7)
 +
</pre>
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 
|-
 
|-
|off
+
 
 +
|i<address>.v12
 +
|[V]
 
|R
 
|R
|zone off
+
|chained voltage phase 1-2
 
|-
 
|-
  
|rowspan="2"|i<address>.mode
+
|i<address>.v23
|summer
+
|[V]
 
|R
 
|R
|summer mode
+
|chained voltage phase 2-3
 
|-
 
|-
|winter
+
 
 +
|i<address>.v31
 +
|[V]
 
|R
 
|R
|winter mode
+
|chained voltage phase 3-1
 
|-
 
|-
  
|rowspan="3"|i<address>.status
+
|i<address>.vtm
|off
+
|[V]
 
|R
 
|R
|off status
+
|average chained voltage
 
|-
 
|-
|heating
+
 
 +
|i<address>.i1
 +
|[A]
 
|R
 
|R
|heating request
+
|current phase 1
 
|-
 
|-
|cooling
+
 
 +
|i<address>.i2
 +
|[A]
 
|R
 
|R
|cooling request
+
|current phase 2
 
|-
 
|-
  
|rowspan="4"|i<address>.fan
+
|i<address>.i3
|off
+
|[A]
 
|R
 
|R
|fan off
+
|current phase 3
 
|-
 
|-
|min
+
 
 +
|i<address>.itm
 +
|[A]
 
|R
 
|R
|min speed
+
|average current
 
|-
 
|-
|med
+
 
 +
|i<address>.ptot
 +
|[W]
 
|R
 
|R
|med speed
+
|total active power
 
|-
 
|-
|max
+
 
 +
|i<address>.ptotk
 +
|[kW]
 
|R
 
|R
|max speed
+
|total active power
 
|-
 
|-
  
|rowspan="2"|i<address>.temp
+
|i<address>.qtot
|fault
+
|[W]
 
|R
 
|R
|NTC probe fault
+
|total reactive power
 
|-
 
|-
|<temp>  
+
 
 +
|i<address>.qtotk
 +
|[kW]
 
|R
 
|R
|ambient temperature value, in C/10
+
|total reactive power
 
|-
 
|-
  
|i<address>.setpoint.temp
+
|i<address>.pf
|<temp>
+
|[pf]
 
|R
 
|R
|real setpoint value, in C/10
+
|total power factor
 
|-
 
|-
  
|i<address>.knob
+
|i<address>.frequency
|0 ... 1000
+
|[Hz]
 
|R
 
|R
|position of rotary knob
+
|frequency
 
|-
 
|-
  
|rowspan="2"|o<address>.mode
+
|i<address>.v1n
|summer
+
|[V]
|RW
+
|R
|set summer
+
|voltage phase 1
 
|-
 
|-
|winter
+
 
|RW
+
|i<address>.v2n
|set winter
+
|[V]
 +
|R
 +
|voltage phase 2
 
|-
 
|-
  
|rowspan="2"|o<address>
+
|i<address>.v3n
|on
+
|[V]
|RW
+
|R
|zone on
+
|voltage phase 3
 
|-
 
|-
|off
+
 
|RW
+
|i<address>.p1
|zone off
+
|[W]
 +
|R
 +
|active power phase 1
 
|-
 
|-
  
|o<address>.setpoint.temp
+
|i<address>.p1k
|0...400
+
|[kW]
|RW
+
|R
|set and read the value of central setpoint (temp in C/10)
+
|active power phase 1
 
|-
 
|-
  
|o<address>.setpoint.delta.neg
+
|i<address>.p2
|<temp>
+
|[W]
|RW
+
|R
|set and read the MAX negative delta
+
|active power phase 2
 
|-
 
|-
  
|o<address>.setpoint.delta.pos
+
|i<address>.p2k
|<temp>
+
|[kW]
|RW
+
|R
|set and read the MAX positive delta
+
|active power phase 2
 
|-
 
|-
  
|rowspan="4"|o<address>.led.1
+
|i<address>.p3
|red<br/>r
+
|[W]
|RW
+
|R
|LED 1 red
+
|active power phase 3
 
|-
 
|-
|green<br/>g
+
 
|RW
+
|i<address>.p3k
|LED 1 green
+
|[kW]
 +
|R
 +
|active power phase 3
 
|-
 
|-
|yellow<br/>y
+
 
|RW
+
|i<address>.q1
|LED 1 yellow
+
|[W]
 +
|R
 +
|reactive power phase 1
 
|-
 
|-
|off
+
 
|RW
+
|i<address>.q1k
|set off
+
|[kW]
 +
|R
 +
|reactive power phase 1
 
|-
 
|-
  
|rowspan="4"|o<address>.led.2
+
|i<address>.q2
|red<br/>r
+
|[W]
|RW
+
|R
|LED 2 red
+
|reactive power phase 2
 
|-
 
|-
|green<br/>g
+
 
|RW
+
|i<address>.q2k
|LED 2 green
+
|[kW]
 +
|R
 +
|reactive power phase 2
 
|-
 
|-
|yellow<br/>y
+
 
|RW
+
|i<address>.q3
|LED 2 yellow
+
|[W]
 +
|R
 +
|reactive power phase 3
 
|-
 
|-
|off
+
 
|RW
+
|i<address>.q3k
|set off
+
|[kW]
 +
|R
 +
|reactive power phase 3
 
|-
 
|-
  
|rowspan="4"|o<address>.led.3
+
|i<address>.pf1
|red<br/>r
+
|[pf]
|RW
+
|R
|LED 3 red
+
|power factor phase 1
 
|-
 
|-
|green<br/>g
+
 
|RW
+
|i<address>.pf2
|LED 3 green
+
|[pf]
 +
|R
 +
|power factor phase 2
 
|-
 
|-
|yellow<br/>y
+
 
|RW
+
|i<address>.pf3
|LED 3 yellow
+
|[pf]
 +
|R
 +
|power factor phase 3
 
|-
 
|-
|off
+
 
|RW
+
|i<address>.s1
|set off
+
|[VA]
 +
|R
 +
|apparent power phase 1
 
|-
 
|-
  
|rowspan="4"|o<address>.led.4
+
|i<address>.s1k
|red<br/>r
+
|[kVA]
|RW
+
|R
|LED 4 red
+
|apparent power phase 1
 
|-
 
|-
|green<br/>g
+
 
|RW
+
|i<address>.s2
|LED 4 green
+
|[VA]
 +
|R
 +
|apparent power phase 2
 
|-
 
|-
|yellow<br/>y
+
 
|RW
+
|i<address>.s2k
|LED 4 yellow
+
|[kVA]
 +
|R
 +
|apparent power phase 2
 
|-
 
|-
|off
+
 
|RW
+
|i<address>.s3
|set off
+
|[VA]
 +
|R
 +
|apparent power phase 3
 
|-
 
|-
  
|}
+
|i<address>.s3k
 +
|[kVA]
 +
|R
 +
|apparent power phase 3
 +
|-
  
You can also set the value to “on” or “off”, that is equivalent to 1 and 0.
+
|i<address>.stot
 
+
|[VA]
----
+
|R
 +
|total apparent power
 +
|-
  
=== MODANA ===
+
|i<address>.hours
 
+
|[hours]
Network analyzer module for Contatto bus.
+
|R
 
+
|hour-meter
It uses, in dynamic mode, up to a maximum of 5 consecutive input addresses and, if enabled, 1 output address equal to the base address.
 
 
 
{{tip|The module must be configured with the same base address for input and output.}}
 
 
 
For example:
 
<pre>
 
(I7, O7)
 
</pre>
 
 
 
{| class="wikitable"
 
!ID
 
!Value
 
!R/W
 
!Description
 
 
|-
 
|-
  
|i<address>.v12
+
|i<address>.temperature
|[V]
+
|[°C]
 
|R
 
|R
|chained voltage phase 1-2
+
|cabinet temperature
 
|-
 
|-
  
|i<address>.v23
+
|i<address>.energy.active
|[V]
+
|[KWh]
 
|R
 
|R
|chained voltage phase 2-3
+
|positive active energy
 
|-
 
|-
  
|i<address>.v31
+
|i<address>.energy.activeneg
|[V]
+
|[KWh]
 
|R
 
|R
|chained voltage phase 3-1
+
|negative active energy
 
|-
 
|-
  
|i<address>.vtm
+
|i<address>.energy.reactive
|[V]
+
|[KVARh]
 
|R
 
|R
|average chained voltage
+
|positive reactive energy
 
|-
 
|-
  
|i<address>.i1
+
|i<address>.energy.reactiveneg
|[A]
+
|[KVARh]
 
|R
 
|R
|current phase 1
+
|negative reactive energy
 
|-
 
|-
  
|i<address>.i2
+
|i<address>.pm
|[A]
+
|[W]
 
|R
 
|R
|current phase 2
+
|average positive active power
 
|-
 
|-
  
|i<address>.i3
+
|i<address>.qm
|[A]
+
|[VAR]
 
|R
 
|R
|current phase 3
+
|average positive reactive power
 
|-
 
|-
  
|i<address>.itm
+
|rowspan="2"|o<address>.reset.energy
|[A]
+
|1
|R
+
|RW
|average current
+
|reset energies
 
|-
 
|-
 
+
|0
|i<address>.ptot
+
|RW
|[W]
+
| ---
|R
 
|total active power
 
 
|-
 
|-
  
|i<address>.ptotk
+
|rowspan="2"|o<address>.reset.hours
|[kW]
+
|1
|R
+
|RW
|total active power
+
|reset hour-meter
 
|-
 
|-
 
+
|0
|i<address>.qtot
+
|RW
|[W]
+
| ---
|R
 
|total reactive power
 
 
|-
 
|-
  
|i<address>.qtotk
+
|}
|[kW]
+
 
|R
+
----
|total reactive power
+
 
|-
+
=== MODANAM ===
 +
 
 +
Network analyzer module for Contatto bus.
 +
 
 +
It uses, in dynamic mode, up to a maximum of 5 consecutive input addresses and, if enabled, 1 output address equal to the base address.
 +
 
 +
{{tip|The module must be configured with the same base address for input and output.}}
 +
 
 +
For example:
 +
<pre>
 +
(I7, O7)
 +
</pre>
  
|i<address>.pf
+
{| class="wikitable"
|[pf]
+
!ID
|R
+
!Value
|total power factor
+
!R/W
 +
!Description
 
|-
 
|-
  
|i<address>.frequency
+
|i<address>.v12
|[Hz]
+
|[V]
 
|R
 
|R
|frequency
+
|chained voltage phase 1-2
 
|-
 
|-
  
|i<address>.v1n
+
|i<address>.v23
 
|[V]
 
|[V]
 
|R
 
|R
|voltage phase 1
+
|chained voltage phase 2-3
 
|-
 
|-
  
|i<address>.v2n
+
|i<address>.v31
 
|[V]
 
|[V]
 
|R
 
|R
|voltage phase 2
+
|chained voltage phase 3-1
 
|-
 
|-
  
|i<address>.v3n
+
|i<address>.vtm
 
|[V]
 
|[V]
 
|R
 
|R
|voltage phase 3
+
|average chained voltage
 
|-
 
|-
  
|i<address>.p1
+
|i<address>.i1
|[W]
+
|[A]
 
|R
 
|R
|active power phase 1
+
|current phase 1
 
|-
 
|-
  
|i<address>.p1k
+
|i<address>.i2
|[kW]
+
|[A]
 
|R
 
|R
|active power phase 1
+
|current phase 2
 
|-
 
|-
  
|i<address>.p2
+
|i<address>.i3
|[W]
+
|[A]
 
|R
 
|R
|active power phase 2
+
|current phase 3
 
|-
 
|-
  
|i<address>.p2k
+
|i<address>.itm
|[kW]
+
|[A]
 
|R
 
|R
|active power phase 2
+
|average current
 
|-
 
|-
  
|i<address>.p3
+
|i<address>.ptot
 
|[W]
 
|[W]
 
|R
 
|R
|active power phase 3
+
|total active power
 
|-
 
|-
  
|i<address>.p3k
+
|i<address>.ptotk
 
|[kW]
 
|[kW]
 
|R
 
|R
|active power phase 3
+
|total active power
 
|-
 
|-
  
|i<address>.q1
+
|i<address>.qtot
 
|[W]
 
|[W]
 
|R
 
|R
|reactive power phase 1
+
|total reactive power
 
|-
 
|-
  
|i<address>.q1k
+
|i<address>.qtotk
 
|[kW]
 
|[kW]
 
|R
 
|R
|reactive power phase 1
+
|total reactive power
 
|-
 
|-
  
|i<address>.q2
+
|i<address>.pf
|[W]
+
|[pf]
 
|R
 
|R
|reactive power phase 2
+
|total power factor
 
|-
 
|-
  
|i<address>.q2k
+
|i<address>.frequency
|[kW]
+
|[Hz]
 
|R
 
|R
|reactive power phase 2
+
|frequency
 
|-
 
|-
  
|i<address>.q3
+
|i<address>.v1n
|[W]
+
|[V]
 
|R
 
|R
|reactive power phase 3
+
|voltage phase 1
 
|-
 
|-
  
|i<address>.q3k
+
|i<address>.v2n
|[kW]
+
|[V]
 
|R
 
|R
|reactive power phase 3
+
|voltage phase 2
 
|-
 
|-
  
|i<address>.pf1
+
|i<address>.v3n
|[pf]
+
|[V]
 
|R
 
|R
|power factor phase 1
+
|voltage phase 3
 
|-
 
|-
  
|i<address>.pf2
+
|i<address>.p1
|[pf]
+
|[W]
 
|R
 
|R
|power factor phase 2
+
|active power phase 1
 
|-
 
|-
  
|i<address>.pf3
+
|i<address>.p1k
|[pf]
+
|[kW]
 
|R
 
|R
|power factor phase 3
+
|active power phase 1
 
|-
 
|-
  
|i<address>.s1
+
|i<address>.p2
|[VA]
+
|[W]
 
|R
 
|R
|apparent power phase 1
+
|active power phase 2
 
|-
 
|-
  
|i<address>.s1k
+
|i<address>.p2k
|[kVA]
+
|[kW]
 
|R
 
|R
|apparent power phase 1
+
|active power phase 2
 
|-
 
|-
  
|i<address>.s2
+
|i<address>.p3
|[VA]
+
|[W]
 
|R
 
|R
|apparent power phase 2
+
|active power phase 3
 
|-
 
|-
  
|i<address>.s2k
+
|i<address>.p3k
|[kVA]
+
|[kW]
 
|R
 
|R
|apparent power phase 2
+
|active power phase 3
 
|-
 
|-
  
|i<address>.s3
+
|i<address>.q1
|[VA]
+
|[W]
 
|R
 
|R
|apparent power phase 3
+
|reactive power phase 1
 
|-
 
|-
  
|i<address>.s3k
+
|i<address>.q1k
|[kVA]
+
|[kW]
 
|R
 
|R
|apparent power phase 3
+
|reactive power phase 1
 
|-
 
|-
  
|i<address>.stot
+
|i<address>.q2
|[VA]
+
|[W]
 
|R
 
|R
|total apparent power
+
|reactive power phase 2
 
|-
 
|-
  
|i<address>.hours
+
|i<address>.q2k
|[hours]
+
|[kW]
 
|R
 
|R
|hour-meter
+
|reactive power phase 2
 
|-
 
|-
  
|i<address>.temperature
+
|i<address>.q3
|[°C]
+
|[W]
 
|R
 
|R
|cabinet temperature
+
|reactive power phase 3
 
|-
 
|-
  
|i<address>.energy.active
+
|i<address>.q3k
|[KWh]
+
|[kW]
 
|R
 
|R
|positive active energy
+
|reactive power phase 3
 
|-
 
|-
  
|i<address>.energy.activeneg
+
|i<address>.pf1
|[KWh]
+
|[pf]
 
|R
 
|R
|negative active energy
+
|power factor phase 1
 
|-
 
|-
  
|i<address>.energy.reactive
+
|i<address>.pf2
|[KVARh]
+
|[pf]
 
|R
 
|R
|positive reactive energy
+
|power factor phase 2
 
|-
 
|-
  
|i<address>.energy.reactiveneg
+
|i<address>.pf3
|[KVARh]
+
|[pf]
 
|R
 
|R
|negative reactive energy
+
|power factor phase 3
 
|-
 
|-
  
|i<address>.pm
+
|i<address>.s1
|[W]
+
|[VA]
 
|R
 
|R
|average positive active power
+
|apparent power phase 1
 
|-
 
|-
  
|i<address>.qm
+
|i<address>.s1k
|[VAR]
+
|[kVA]
 
|R
 
|R
|average positive reactive power
+
|apparent power phase 1
 
|-
 
|-
  
|rowspan="2"|i<address>.reset.energy
+
|i<address>.s2
|1
+
|[VA]
|RW
+
|R
|reset energies
+
|apparent power phase 2
 
|-
 
|-
|0
+
 
|RW
+
|i<address>.s2k
| ---
+
|[kVA]
 +
|R
 +
|apparent power phase 2
 
|-
 
|-
  
|rowspan="2"|i<address>.reset.hours
+
|i<address>.s3
|1
+
|[VA]
|RW
+
|R
|reset hour-meter
+
|apparent power phase 3
|-
 
|0
 
|RW
 
| ---
 
 
|-
 
|-
  
|}
+
|i<address>.s3k
 
+
|[kVA]
----
+
|R
 
+
|apparent power phase 3
=== MODPQ5 ===
 
 
 
Q5 tags proximity reader and programmer module.
 
 
 
Uses 1 input address on the Contatto bus. Write operations are performed through direct writes to the module’s RAM.
 
 
 
{| class="wikitable"
 
!ID
 
!Value
 
!R/W
 
!Description
 
 
|-
 
|-
  
|i<address>.data
+
|i<address>.stot
|style="white-space:nowrap"|0 <br/> <tag data>
+
|[VA]
 
|R
 
|R
|30 characters hexadecimal representation of the 15 bytes of tag data; “0” if the module is not seeing any tag
+
|total apparent power
 
|-
 
|-
  
|rowspan="2"|i<address>.data.write
+
|i<address>.hours
|0
+
|[hours]
 
|R
 
|R
|the tag has been removed from the programmer after writing, or the module is not seeing any tag
+
|hour-meter
 
|-
 
|-
|1
+
 
 +
|i<address>.temperature
 +
|[°C]
 
|R
 
|R
|the tag write operation was successful
+
|cabinet temperature
 
|-
 
|-
  
|rowspan="2"|i<address>.reader.error
+
|i<address>.energy.active
|0
+
|[KWh]
 
|R
 
|R
|reader/writer normal status
+
|positive active energy
 
|-
 
|-
|1
+
 
 +
|i<address>.energy.activeneg
 +
|[KWh]
 
|R
 
|R
|reader/writer module error (normally occurs when the reader is not connected to the MODPQ5 module)
+
|negative active energy
 
|-
 
|-
  
|rowspan="2"|i<address>.tag.error
+
|i<address>.energy.reactive
|0
+
|[KVARh]
 
|R
 
|R
|the tag is valid
+
|positive reactive energy
 
|-
 
|-
|1
+
 
 +
|i<address>.energy.reactiveneg
 +
|[KVARh]
 
|R
 
|R
|the tag is not valid
+
|negative reactive energy
 
|-
 
|-
  
|rowspan="2"|i<address>.request.error
+
|rowspan="2"|o<address>.reset.energy
|0
 
|R
 
|no request or handshake errors detected
 
|-
 
 
|1
 
|1
|R
+
|RW
|handshake error
+
|reset energies
 
|-
 
|-
 
|rowspan="2"|i<address>.data.error
 
 
|0
 
|0
|R
+
|RW
|tag data ok
+
| ---
 
|-
 
|-
 +
 +
|rowspan="2"|o<address>.reset.hours
 
|1
 
|1
|R
+
|RW
|tag data errors detected
+
|reset hour-meter
 
|-
 
|-
 
|rowspan="2"|i<address>.unknown.error
 
 
|0
 
|0
|R
+
|RW
|no unknown errors
+
| ---
|-
 
|1
 
|R
 
|unknown error detected
 
 
|-
 
|-
  
|rowspan="2"|i<address>.write
+
|}
|<tag data>
+
 
|R
+
----
|tag data write successful
+
 
|-
+
=== MODPQ5 ===
|error
 
|R
 
|tag data write error
 
|-
 
  
|o<address>.write
+
Q5 tags proximity reader and programmer module.
|<tag data>
 
|W
 
|30 characters hexadecimal representation of the 15 bytes data to be written on the tag
 
|-
 
|}
 
  
----
+
Uses 1 input address on the Contatto bus. Write operations are performed through direct writes to the module’s RAM.
 
 
=== MODHT ===
 
 
 
MODHT is the hotel room controller module.
 
 
 
It uses 1 input and 1 output address.  
 
 
 
Tags configuration data are written to the module’s EEPROM (persistent internal memory).
 
  
 
{| class="wikitable"
 
{| class="wikitable"
Line 3,932: Line 4,112:
 
|-
 
|-
  
|rowspan="2"|i<address>.door
+
|i<address>.data
|0  
+
|style="white-space:nowrap"|0 <br/> <tag data>
 
|R
 
|R
|door closed
+
|30 characters hexadecimal representation of the 15 bytes of tag data; “0” if the module is not seeing any tag
|-
 
|1
 
|R
 
|door open
 
 
|-
 
|-
  
|rowspan="2"|i<address>.window
+
|rowspan="2"|i<address>.data.write
 
|0  
 
|0  
 
|R
 
|R
|window closed
+
|the tag has been removed from the programmer after writing, or the module is not seeing any tag
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|window open
+
|the tag write operation was successful
 
|-
 
|-
  
|rowspan="2"|i<address>.panic
+
|rowspan="2"|i<address>.reader.error
 
|0  
 
|0  
 
|R
 
|R
|panic request not active
+
|reader/writer normal status
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|panic request
+
|reader/writer module error (normally occurs when the reader is not connected to the MODPQ5 module)
 
|-
 
|-
  
|rowspan="2"|i<address>.busy
+
|rowspan="2"|i<address>.tag.error
 
|0  
 
|0  
 
|R
 
|R
|room is free
+
|the tag is valid
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|room is occupied
+
|the tag is not valid
 
|-
 
|-
  
|rowspan="2"|i<address>.1
+
|rowspan="2"|i<address>.request.error
|0  
+
|0
 
|R
 
|R
|input pin 1 off
+
|no request or handshake errors detected
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 1 on
+
|handshake error
 
|-
 
|-
  
|rowspan="2"|i<address>.2
+
|rowspan="2"|i<address>.data.error
|0  
+
|0
 
|R
 
|R
|input pin 2 off
+
|tag data ok
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 2 on
+
|tag data errors detected
 
|-
 
|-
  
|rowspan="2"|i<address>.3
+
|rowspan="2"|i<address>.unknown.error
 
|0
 
|0
 
|R
 
|R
|input pin 3 off
+
|no unknown errors
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|input pin 3 on
+
|unknown error detected
 
|-
 
|-
  
|rowspan="2"|i<address>.ev
+
|rowspan="2"|i<address>.write
|0
+
|<tag data>
 
|R
 
|R
|EV output off
+
|tag data write successful
 
|-
 
|-
|1
+
|error
 
|R
 
|R
|EV output on
+
|tag data write error
 
|-
 
|-
  
|rowspan="2"|i<address>.aux
+
|o<address>.write
|0
+
|<tag data>
|R
+
|W
|AUX output off
+
|30 characters hexadecimal representation of the 15 bytes data to be written on the tag
|-
 
|1
 
|R
 
|AUX output on
 
 
|-
 
|-
 +
|}
  
|rowspan="2"|i<address>.dnd
+
----
 +
 
 +
=== MODHT ===
 +
 
 +
MODHT is the hotel room controller module.
 +
 
 +
It uses 1 input and 1 output address.
 +
 
 +
Tags configuration data are written to the module’s EEPROM (persistent internal memory).
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 +
|-
 +
 
 +
|rowspan="2"|i<address>.door
 
|0  
 
|0  
 
|R
 
|R
|do not disturb not active
+
|door closed
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|do not disturb
+
|door open
 
|-
 
|-
  
|rowspan="2"|i<address>.service
+
|rowspan="2"|i<address>.window
 
|0  
 
|0  
 
|R
 
|R
|room service request not active
+
|window closed
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|room service request
+
|window open
 
|-
 
|-
  
|rowspan="2"|i<address>.booked
+
|rowspan="2"|i<address>.panic
 
|0  
 
|0  
 
|R
 
|R
|room is not booked
+
|panic request not active
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|room is booked
+
|panic request
 
|-
 
|-
  
|rowspan="2"|i<address>.mode
+
|rowspan="2"|i<address>.busy
|summer
+
|0
 
|R
 
|R
|summer mode
+
|room is free
 
|-
 
|-
|winter
+
|1
 
|R
 
|R
|winter mode
+
|room is occupied
 
|-
 
|-
  
|rowspan="5"|i<address>.fan
+
|rowspan="2"|i<address>.1
|off
+
|0
 
|R
 
|R
|fan set to off
+
|input pin 1 off
 
|-
 
|-
|auto
+
|1
 
|R
 
|R
|fan speed set to auto
+
|input pin 1 on
 
|-
 
|-
|min
+
 
 +
|rowspan="2"|i<address>.2
 +
|0
 
|R
 
|R
|fan speed set to minimum
+
|input pin 2 off
 
|-
 
|-
|med
+
|1
 
|R
 
|R
|fan speed set to medium
+
|input pin 2 on
|-
 
|max
 
|R
 
|fan speed set to max
 
 
|-
 
|-
  
|rowspan="2"|i<address>.fan.status
+
|rowspan="2"|i<address>.ev
|0  
+
|0
 
|R
 
|R
|fan is off
+
|EV output off
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|fan is on (cooling or heating)
+
|EV output on
 
|-
 
|-
  
|i<address>.temp
+
|rowspan="2"|i<address>.aux
|<temp>
+
|0
 +
|R
 +
|AUX output off
 +
|-
 +
|1
 
|R
 
|R
|ambient temperature value (in C/10)
+
|AUX output on
 
|-
 
|-
  
|i<address>.setpoint.temp
+
|rowspan="2"|i<address>.dnd
|<temp>
+
|0
 
|R
 
|R
|setpoint value (in C/10)
+
|do not disturb not active
 
|-
 
|-
 
+
|1
|i<address>.tag.door
 
|1...5
 
 
|R
 
|R
|type of tag that is opening the door (1 to 4 are service tags; 5 is a customer tag). After 5 seconds the value is reset to 0
+
|do not disturb
 
|-
 
|-
  
|rowspan="2"|i<address>.tag.room
+
|rowspan="2"|i<address>.service
|0
+
|0  
 
|R
 
|R
|no tag present in room’s reader
+
|room service request not active
 
|-
 
|-
|1...5
+
|1
 
|R
 
|R
|type of tag inserted in the room’s reader (1 to 4 are service tags; 5 is a customer tag)
+
|room service request
 
|-
 
|-
  
|i<address>.tag.<n>
+
|rowspan="2"|i<address>.booked
|<tag data>
+
|0
 
|R
 
|R
|24 characters hexadecimal representation of the 12 bytes data matching service N tags (N from 1 to 5) stored in module’s EEPROM
+
|room is not booked
|-
 
 
 
|rowspan="2"|i<address>.pcam.error
 
|0
 
|R
 
|PCAM module ok
 
 
|-
 
|-
 
|1
 
|1
 
|R
 
|R
|PCAM module error
+
|room is booked
 
|-
 
|-
  
|rowspan="2"|i<address>.tpr.error
+
|rowspan="2"|i<address>.mode
|0
+
|summer
 
|R
 
|R
|TPR/H module ok
+
|summer mode
 
|-
 
|-
|1
+
|winter
 
|R
 
|R
|TPR/H module error
+
|winter mode
 
|-
 
|-
  
|i<address>.mask
+
|rowspan="5"|i<address>.fan
|style="white-space:nowrap"|<mask data>
+
|off
 
|R
 
|R
|24 characters hexadecimal representation of the 12 bytes tag mask stored in module’s EEPROM
+
|fan set to off
 
|-
 
|-
 
+
|auto
|i<address>.data.door
 
|0<br/><tag data>
 
 
|R
 
|R
|30 characters hexadecimal representation of the 15 bytes of tag data being read from the door reader; “0” if the module is not seeing any tag (this data point is available with MODHT firmware 5.3 or newer)
+
|fan speed set to auto
 
|-
 
|-
 
+
|min
|i<address>.data.room
 
|0<br/><tag data>
 
 
|R
 
|R
|30 characters hexadecimal representation of the 15 bytes of tag data being read from the room reader; “0” if the module is not seeing any tag (this data point is available with MODHT firmware 5.3 or newer)
+
|fan speed set to minimum
 
|-
 
|-
 
+
|med
|i<address>.setpoint.summer.<n> <br/> i<address>.setpoint.winter.<n>
 
|<temp>
 
 
|R
 
|R
|winter/summer setpoint <n> (1...3) current value (in C/10)
+
|fan speed set to medium
 
|-
 
|-
 
+
|max
|i<address>.setpoint.delta.summer.low <br/> i<address>.setpoint.delta.summer.high <br/> i<address>.setpoint.delta.winter.low <br/>  i<address>.setpoint.delta.winter.high
 
|style="white-space:nowrap"|<temp delta limit> <br/> 1...9
 
 
|R
 
|R
|the current temperature setpoint low/high limits for winter and summer modes (in C)
+
|fan speed set to max
 
|-
 
|-
  
|rowspan="2"|o<address>.tag.<n>
+
|rowspan="2"|i<address>.fan.status
|<tag data>
+
|0
 
|R
 
|R
|tag data write successful
+
|fan is off
 
|-
 
|-
|error
+
|1
 
|R
 
|R
|tag data write error
+
|fan is on (cooling or heating)
 
|-
 
|-
  
|rowspan="2"|o<address>.mask
+
|i<address>.temp
|<mask data>
+
|<temp>
 
|R
 
|R
|mask data write successful
+
|ambient temperature value (in C/10)
|-
 
|error
 
|R
 
|mask data write error
 
 
|-
 
|-
  
|rowspan="2"|o<address>.setpoint.summer.<n> <br/> o<address>.setpoint.winter.<n>
+
|i<address>.setpoint.temp
 
|<temp>
 
|<temp>
 
|R
 
|R
|winter/summer setpoint N (1-3) write successful (in C/10)
+
|setpoint value (in C/10)
 
|-
 
|-
|error
+
 
 +
|i<address>.tag.door
 +
|1...5
 
|R
 
|R
|setpoint write error
+
|type of tag that is opening the door (1 to 4 are service tags; 5 is a customer tag). After 5 seconds the value is reset to 0
 
|-
 
|-
  
|rowspan="2"|o<address>.setpoint.delta.summer.low <br/> o<address>.setpoint.delta.summer.high <br/> o<address>.setpoint.delta.winter.low <br/>  o<address>.setpoint.delta.winter.high
+
|rowspan="2"|i<address>.tag.room
|<temp delta limit> <br/> 1...9
+
|0
 
|R
 
|R
|setpoint min/max limit for winter/summer write successful (in C)
+
|no tag present in room’s reader
 
|-
 
|-
|error
+
|1...5
 
|R
 
|R
|setpoint limit write error
+
|type of tag inserted in the room’s reader (1 to 4 are service tags; 5 is a customer tag)
 +
|-
 +
 
 +
|i<address>.tag.<n>
 +
|<tag data>
 +
|R
 +
|24 characters hexadecimal representation of the 12 bytes data matching service N tags (N from 1 to 5) stored in module’s EEPROM. Updated on o<address>.tag.<n>=read command
 
|-
 
|-
  
|rowspan="2"|o<address>.ev.enable
+
|rowspan="2"|i<address>.pcam.error
 
|0
 
|0
|W
+
|R
|EV output disabled
+
|PCAM module ok
 
|-
 
|-
 
|1
 
|1
|W
+
|R
|EV output enabled
+
|PCAM module error
 
|-
 
|-
  
|rowspan="2"|o<address>.aux.enable
+
|rowspan="2"|i<address>.tpr.error
 
|0
 
|0
|W
+
|R
|AUX output disabled
+
|TPR/H module ok
 
|-
 
|-
 
|1
 
|1
|W
+
|R
|AUX output enabled
+
|TPR/H module error
 
|-
 
|-
  
|o<address>.panic.reset
+
|i<address>.mask
|1
+
|style="white-space:nowrap"|<mask data>
|W
+
|R
|panic request reset
+
|24 characters hexadecimal representation of the 12 bytes tag mask stored in module’s EEPROM. Updated on o<address>.mask=read command
 
|-
 
|-
  
|rowspan="2"|o<address>.busy
+
|i<address>.data.door
|0
+
|0<br/><tag data>
|W
+
|R
|set room status to free
+
|30 characters hexadecimal representation of the 15 bytes of tag data being read from the door reader; “0” if the module is not seeing any tag (this data point is available with MODHT firmware 5.3 or newer)
 
|-
 
|-
|1
+
 
|W
+
|i<address>.data.room
|set room status to occupied
+
|0<br/><tag data>
 +
|R
 +
|30 characters hexadecimal representation of the 15 bytes of tag data being read from the room reader; “0” if the module is not seeing any tag (this data point is available with MODHT firmware 5.3 or newer)
 
|-
 
|-
  
|rowspan="2"|o<address>.ev
+
|i<address>.setpoint.summer.<n> <br/> i<address>.setpoint.winter.<n>
|0
+
|<temp>
|W
+
|R
|EV output off
+
|winter/summer setpoint <n> (1...3) current value (in C/10). Updated on o<address>.setpoint.summer.<n>=read and  o<address>.setpoint.winter.<n>=read commands
 
|-
 
|-
|1
+
 
|W
+
|i<address>.setpoint.delta.summer.low <br/> i<address>.setpoint.delta.summer.high <br/> i<address>.setpoint.delta.winter.low <br/>  i<address>.setpoint.delta.winter.high
|EV output on
+
|style="white-space:nowrap"|<temp delta limit> <br/> 1...9
 +
|R
 +
|the current temperature setpoint low/high limits for winter and summer modes (in C). Updated on o<address>.setpoint.delta=read command
 
|-
 
|-
  
|rowspan="2"|o<address>.aux
+
|rowspan="2"|o<address>.tag.<n>
|0
+
|<tag data>
|W
+
|R
|AUX output off
+
|tag data write successful
 
|-
 
|-
|1
+
|error
|W
+
|R
|AUX output on
+
|tag data write error
 
|-
 
|-
  
|o<address>.dnd.reset
+
|rowspan="2"|o<address>.mask
|1
+
|<mask data>
|W
+
|R
|do not disturb reset
+
|mask data write successful
 
|-
 
|-
 
+
|error
|o<address>.service.reset
+
|R
|1
+
|mask data write error
|W
 
|do not disturb reset
 
 
|-
 
|-
  
|rowspan="2"|o<address>.booked
+
|rowspan="2"|o<address>.setpoint.summer.<n> <br/> o<address>.setpoint.winter.<n>
|0
+
|<temp>
|W
+
|R
|set room as not booked
+
|winter/summer setpoint N (1-3) write successful (in C/10)
 
|-
 
|-
|1
+
|error
|W
+
|R
|set room as booked
+
|setpoint write error
 
|-
 
|-
  
|rowspan="2"|o<address>.mode
+
|rowspan="2"|o<address>.setpoint.delta.summer.low <br/> o<address>.setpoint.delta.summer.high <br/> o<address>.setpoint.delta.winter.low <br/>  o<address>.setpoint.delta.winter.high
|summer
+
|<temp delta limit> <br/> 1...9
|W
+
|R
|set room to summer mode
+
|setpoint min/max limit for winter/summer write successful (in C)
 
|-
 
|-
|winter
+
|error
|W
+
|R
|set room to winter mode
+
|setpoint limit write error
 
|-
 
|-
  
|rowspan="2"|o<address>.fan
+
|rowspan="2"|o<address>.ev.enable
|off
+
|0
 
|W
 
|W
|set fan off
+
|EV output disabled
 
|-
 
|-
|auto
+
|1
 
|W
 
|W
|set fan to auto mode
+
|EV output enabled
 
|-
 
|-
  
|rowspan="2"|o<address>.comfort
+
|rowspan="2"|o<address>.aux.enable
 
|0
 
|0
 
|W
 
|W
|output 3 off
+
|AUX output disabled
 
|-
 
|-
 
|1
 
|1
 
|W
 
|W
|output 3 on
+
|AUX output enabled
 
|-
 
|-
  
|rowspan="2"|o<address>.fan.heating.min
+
|o<address>.panic.reset
|0
 
|W
 
|reset heating speed limit
 
|-
 
 
|1
 
|1
 
|W
 
|W
|limit heating speed to min
+
|panic request reset
 
|-
 
|-
  
|rowspan="2"|o<address>.fan.cooling.min
+
|rowspan="2"|o<address>.busy
 
|0
 
|0
 
|W
 
|W
|reset cooling speed limit
+
|set room status to free
 
|-
 
|-
 
|1
 
|1
 
|W
 
|W
|limit cooling speed to min
+
|set room status to occupied
 
|-
 
|-
  
|rowspan="2"|o<address>.tag.<n>
+
|rowspan="2"|o<address>.ev
|read
+
|0
 
|W
 
|W
|read the 12 bytes stored in module’s EEPROM for service N tags (<n> from 1 to 5)
+
|EV output off
 
|-
 
|-
|<tag data>
+
|1
 
|W
 
|W
|24 characters hexadecimal representation of the 12 bytes data matching service N tags (N from 1 to 5), to be stored in module’s EEPROM. After writing data, you should wait approximately 150ms before sending a read command
+
|EV output on
 
|-
 
|-
  
|rowspan="2"|o<address>.mask
+
|rowspan="2"|o<address>.aux
|read
+
|0
 
|W
 
|W
|read the 12 bytes mask stored in module’s EEPROM
+
|AUX output off
 
|-
 
|-
|<mask data>
+
|1
 
|W
 
|W
|24 characters hexadecimal representation of the 12 bytes tag mask, to be stored in module’s EEPROM. After writing data, you should wait approximately 150ms before sending a read command
+
|AUX output on
 
|-
 
|-
  
|rowspan="2"|o<address>.setpoint.summer.<n> <br/> o<address>.setpoint.winter.<n>
+
|o<address>.dnd.reset
|read
+
|1
 
|W
 
|W
|read winter/summer setpoint <n> (1-3)
+
|do not disturb reset
 
|-
 
|-
|<temp>
+
 
 +
|o<address>.service.reset
 +
|1
 
|W
 
|W
|set winter/summer setpoint <n> (1-3)
+
|do not disturb reset
 
|-
 
|-
  
|o<address>.setpoint.delta
+
|rowspan="2"|o<address>.booked
|read
+
|0
 
|W
 
|W
|read winter and summer, low and high setpoint limits
+
|set room as not booked
 
|-
 
|-
 
+
|1
|o<address>.setpoint.delta.summer.low <br/> o<address>.setpoint.delta.summer.high <br/> o<address>.setpoint.delta.winter.low <br/> o<address>.setpoint.delta.winter.high
 
|<temp delta limit>
 
 
|W
 
|W
|set winter/summer, low/high setpoint limit (in C)
+
|set room as booked
 
|-
 
|-
  
|}
+
|rowspan="2"|o<address>.mode
 
+
|summer
----
+
|W
 
+
|set room to summer mode
=== MODCA ===
+
|-
 
+
|winter
MODCA is the access control module.
+
|W
 
+
|set room to winter mode
It uses 1 input and 1 output address.  
 
 
 
Tags configuration data are written to the module’s EEPROM (persistent external memory).
 
 
 
Site codes and the tags mask are written to the internal EEPROM.
 
 
 
{| class="wikitable"
 
!ID
 
!Value
 
!R/W
 
!Description
 
 
|-
 
|-
  
|rowspan="2"|i<address>.1
+
|rowspan="2"|o<address>.fan
|0
+
|off
|R
+
|W
|input pin 1 off
+
|set fan off
 
|-
 
|-
|1
+
|auto
|R
+
|W
|input pin 1 on
+
|set fan to auto mode
 
|-
 
|-
  
|rowspan="2"|i<address>.2
+
|rowspan="2"|o<address>.comfort
|0  
+
|0
|R
+
|W
|input pin 2 off
+
|force comfort set-point off
 
|-
 
|-
 
|1
 
|1
|R
+
|W
|input pin 2 on
+
|force comfort set-point on
 
|-
 
|-
  
|rowspan="2"|i<address>.blocked
+
|rowspan="2"|o<address>.3
|0  
+
|0
|R
+
|W
|access control enabled
+
|output pin 3 off
 
|-
 
|-
 
|1
 
|1
|R
+
|W
|access blocked
+
| output pin 3 on
 
|-
 
|-
  
|rowspan="2"|i<address>.tpr.error
+
 
|0  
+
|rowspan="2"|o<address>.fan.heating.min
|R
+
|0
|TPR module ok
+
|W
 +
|reset heating speed limit
 
|-
 
|-
 
|1
 
|1
|R
+
|W
|TPR module error
+
|limit heating speed to min
 
|-
 
|-
  
|rowspan="2"|i<address>.access.granted.1
+
|rowspan="2"|o<address>.fan.cooling.min
|0  
+
|0
|R
+
|W
|no tag present at antenna 1
+
|reset cooling speed limit
 
|-
 
|-
 
|1
 
|1
|R
+
|W
|access granted to tag at antenna 1
+
|limit cooling speed to min
 
|-
 
|-
  
|rowspan="2"|i<address>.access.granted.2
+
|rowspan="2"|o<address>.tag.<n>
|0
+
|read
|R
+
|W
|no tag present at antenna 2
+
|read the 12 bytes stored in module’s EEPROM for service N tags (<n> from 1 to 5)
 
|-
 
|-
|1
+
|<tag data>
|R
+
|W
|access granted to tag at antenna 2
+
|24 characters hexadecimal representation of the 12 bytes data matching service N tags (N from 1 to 5), to be stored in module’s EEPROM. After writing data, you should wait approximately 150ms before sending a read command
 
|-
 
|-
  
|rowspan="8"|i<address>.access.denied
+
|rowspan="2"|o<address>.mask
|0
+
|read
|R
+
|W
|access denied flags reset
+
|read the 12 bytes mask stored in module’s EEPROM
 
|-
 
|-
|site
+
|<mask data>
|R
+
|W
|access denied due to site code error
+
|24 characters hexadecimal representation of the 12 bytes tag mask, to be stored in module’s EEPROM. After writing data, you should wait approximately 150ms before sending a read command
 
|-
 
|-
|code
+
 
|R
+
|rowspan="2"|o<address>.setpoint.summer.<n> <br/> o<address>.setpoint.winter.<n>
|access denied due to user code error
+
|read
 +
|W
 +
|read winter/summer setpoint <n> (1-3)
 
|-
 
|-
|total.limit
+
|<temp>
|R
+
|W
|access denied due to exceeded total number of access grants
+
|set winter/summer setpoint <n> (1-3)
 
|-
 
|-
|daily.limit
+
 
|R
+
|o<address>.setpoint.delta
|access denied due to exceeded daily number of access grants
+
|read
 +
|W
 +
|read winter and summer, low and high setpoint limits
 
|-
 
|-
|time
+
 
|R
+
|o<address>.setpoint.delta.summer.low <br/> o<address>.setpoint.delta.summer.high <br/> o<address>.setpoint.delta.winter.low <br/> o<address>.setpoint.delta.winter.high
|access denied due to time range violation
+
|<temp delta limit>
 +
|W
 +
|set winter/summer, low/high setpoint limit (in C)
 
|-
 
|-
|day
+
 
|R
+
|}
|access denied due to weekday violation
+
 
 +
----
 +
 
 +
=== MODCA ===
 +
 
 +
MODCA is the access control module.
 +
 
 +
It uses 1 input and 1 output address.
 +
 
 +
Tags configuration data are written to the module’s EEPROM (persistent external memory).
 +
 
 +
Site codes and the tags mask are written to the internal EEPROM.
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 
|-
 
|-
|expired
+
 
 +
|rowspan="2"|i<address>.1
 +
|0
 
|R
 
|R
|access denied due expired tag
+
|input pin 1 off
 
|-
 
|-
 
+
|1
|i<address>.denied.code
 
|<tag code>
 
 
|R
 
|R
|the tag code (decimal value of selected two bytes of the tag data) that was denied access
+
|input pin 1 on
 
|-
 
|-
  
|i<address>.granted.1.code
+
|rowspan="2"|i<address>.2
|<tag code>
+
|0
 
|R
 
|R
|the tag code (decimal value of selected two bytes of the tag data) that was granted access at antenna 1
+
|input pin 2 off
 
|-
 
|-
 
+
|1
|i<address>.granted.2.code
 
|<tag code>
 
 
|R
 
|R
|the tag code (decimal value of selected two bytes of the tag data) that was granted access at antenna 2
+
|input pin 2 on
 
|-
 
|-
  
|i<address>.site.<n>
+
|rowspan="2"|i<address>.blocked
|style="white-space:nowrap"|<site data>
+
|0
 
|R
 
|R
|16 characters hexadecimal representation of the 8 bytes data representing the Nth site code (N from 1 to 4) stored in module’s EEPROM
+
|access control enabled
 
|-
 
|-
 
+
|1
|i<address>.mask
 
|style="white-space:nowrap"|<mask data>
 
 
|R
 
|R
|16 characters hexadecimal representation of the 8 bytes site code mask stored in module’s EEPROM
+
|access blocked
 
|-
 
|-
  
|i<address>.mask
+
|rowspan="2"|i<address>.tpr.error
|<mask data>
+
|0
 
|R
 
|R
|16 characters hexadecimal representation of the 8 bytes site code mask stored in module’s EEPROM
+
|TPR module ok
 
|-
 
|-
 
+
|1
|i<address>.user.<n>
 
|<user data>
 
 
|R
 
|R
|32 characters hexadecimal representation of the 16 bytes data for user <n> (N from 1 to 2000) stored in module’s EEPROM
+
|TPR module error
 
|-
 
|-
  
|rowspan="2"|o<address>.site.<n>
+
|rowspan="2"|i<address>.access.granted.1
|<site data>
+
|0
 
|R
 
|R
|site data write successful
+
|no tag present at antenna 1
 
|-
 
|-
|error
+
|1
 
|R
 
|R
|site data write error
+
|access granted to tag at antenna 1
 
|-
 
|-
  
|rowspan="2"|o<address>.mask
+
|rowspan="2"|i<address>.access.granted.2
|<mask data>
+
|0
 
|R
 
|R
|mask data write successful
+
|no tag present at antenna 2
 
|-
 
|-
|error
+
|1
 
|R
 
|R
|mask data write error
+
|access granted to tag at antenna 2
 
|-
 
|-
  
|rowspan="2"|o<address>.user.<n>
+
|rowspan="8"|i<address>.access.denied
|<user data>
+
|0
 
|R
 
|R
|user data write successful
+
|access denied flags reset
 
|-
 
|-
|error
+
|site
 
|R
 
|R
|user data write error
+
|access denied due to site code error
 
|-
 
|-
 
+
|code
|rowspan="2"|o<address>.relay
+
|R
|0
+
|access denied due to user code error
|W
 
|relay output off
 
 
|-
 
|-
|1
+
|total.limit
|W
+
|R
|relay output pulse on, with pulse length according to the MODCA configuration (with firmware versions before 1.3 this data point remains at 1 and should be reset to 0 with an explicit command; with firmware 1.3 the data point value follows the relay state, and is automatically reset to 0 at the end of the pulse period)
+
|access denied due to exceeded total number of access grants
 
|-
 
|-
 
+
|daily.limit
|rowspan="2"|o<address>.relay.forced
+
|R
|0
+
|access denied due to exceeded daily number of access grants
|W
 
|forced relay mode not set (default behaviour)
 
 
|-
 
|-
|1
+
|time
|W
+
|R
|forced relay mode set: the relay remains closed until the relay.forced command is reset (available with MODCA firmware version 2.0 or later)
+
|access denied due to time range violation
 
|-
 
|-
 
+
|day
|rowspan="2"|o<address>.block
+
|R
|0
+
|access denied due to weekday violation
|W
 
|enable access control
 
 
|-
 
|-
|1
+
|expired
|W
+
|R
|block access control
+
|access denied due expired tag
 
|-
 
|-
  
|rowspan="2"|o<address>.access.granted.code
+
|i<address>.denied.code
|0
+
|<tag code>
|W
+
|R
|reset
+
|the tag code (decimal value of selected two bytes of the tag data) that was denied access
 
|-
 
|-
|1
+
 
|W
+
|i<address>.granted.1.code
|allow access even when site code is not valid
+
|<tag code>
 +
|R
 +
|the tag code (decimal value of selected two bytes of the tag data) that was granted access at antenna 1
 
|-
 
|-
  
|rowspan="2"|o<address>.access.granted.total.limit
+
|i<address>.granted.2.code
|0
+
|<tag code>
|W
+
|R
|reset
+
|the tag code (decimal value of selected two bytes of the tag data) that was granted access at antenna 2
 
|-
 
|-
|1
+
 
|W
+
|i<address>.site.<n>
|allow access even when the total limit of access grants has been exceeded
+
|style="white-space:nowrap"|<site data>
 +
|R
 +
|16 characters hexadecimal representation of the 8 bytes data representing the Nth site code (N from 1 to 4) stored in module’s EEPROM
 
|-
 
|-
  
|rowspan="2"|o<address>.access.granted.daily.limit
+
|i<address>.mask
|0
+
|style="white-space:nowrap"|<mask data>
|W
+
|R
|reset
+
|16 characters hexadecimal representation of the 8 bytes site code mask stored in module’s EEPROM
 
|-
 
|-
|1
+
 
|W
+
|i<address>.mask
|allow access even when the daily limit of access grants has been exceeded
+
|<mask data>
 +
|R
 +
|16 characters hexadecimal representation of the 8 bytes site code mask stored in module’s EEPROM
 
|-
 
|-
  
|rowspan="2"|o<address>.access.granted.time
+
|i<address>.user.<n>
|0
+
|<user data>
|W
+
|R
|reset
+
|32 characters hexadecimal representation of the 16 bytes data for user <n> (N from 1 to 2000) stored in module’s EEPROM
 
|-
 
|-
|1
+
 
|W
+
|rowspan="2"|o<address>.site.<n>
|allow access even outside of the allowed timeframe
+
|<site data>
 +
|R
 +
|site data write successful
 +
|-
 +
|error
 +
|R
 +
|site data write error
 +
|-
 +
 
 +
|rowspan="2"|o<address>.mask
 +
|<mask data>
 +
|R
 +
|mask data write successful
 +
|-
 +
|error
 +
|R
 +
|mask data write error
 +
|-
 +
 
 +
|rowspan="2"|o<address>.user.<n>
 +
|<user data>
 +
|R
 +
|user data write successful
 +
|-
 +
|error
 +
|R
 +
|user data write error
 
|-
 
|-
  
|rowspan="2"|o<address>.access.granted.day
+
|rowspan="2"|o<address>.relay
 
|0
 
|0
 
|W
 
|W
|reset
+
|relay output off
 
|-
 
|-
 
|1
 
|1
 
|W
 
|W
|allow access even outside of the allowed weekdays
+
|relay output pulse on, with pulse length according to the MODCA configuration (with firmware versions before 1.3 this data point remains at 1 and should be reset to 0 with an explicit command; with firmware 1.3 the data point value follows the relay state, and is automatically reset to 0 at the end of the pulse period)
 
|-
 
|-
  
|rowspan="2"|o<address>.access.granted.expired
+
|rowspan="2"|o<address>.relay.forced
 
|0
 
|0
 
|W
 
|W
|reset
+
|forced relay mode not set (default behaviour)
 
|-
 
|-
 
|1
 
|1
 
|W
 
|W
|allow access even when the tag is expired
+
|forced relay mode set: the relay remains closed until the relay.forced command is reset (available with MODCA firmware version 2.0 or later)
 
|-
 
|-
  
|rowspan="2"|o<address>.site.<n>
+
|rowspan="2"|o<address>.block
|read
+
|0
 
|W
 
|W
|read the 8 bytes stored in module’s EEPROM for site N code (<n> from 1 to 4)
+
|enable access control
 
|-
 
|-
|<site data>
+
|1
 
|W
 
|W
|16 characters hexadecimal representation of the 8 bytes data of site N code (N from 1 to 4), to be stored in module’s EEPROM. After writing data, you should wait approximately 100ms before sending a read command
+
|block access control
 
|-
 
|-
  
|rowspan="2"|o<address>.mask
+
|rowspan="2"|o<address>.access.granted.code
|read
+
|0
 
|W
 
|W
|read the 8 bytes mask stored in module’s EEPROM
+
|reset
 
|-
 
|-
|<mask data>
+
|1
 
|W
 
|W
|16 characters hexadecimal representation of the 8 bytes site code mask, to be stored in module’s EEPROM. After writing data, you should wait approximately 100ms before sending a read command
+
|allow access even when site code is not valid
 
|-
 
|-
  
|rowspan="3"|o<address>.user.<n>
+
|rowspan="2"|o<address>.access.granted.total.limit
|read
+
|0
 +
|W
 +
|reset
 +
|-
 +
|1
 
|W
 
|W
|read the 16 bytes stored in module’s EEPROM for user N (<n> from 1 to 2000)
+
|allow access even when the total limit of access grants has been exceeded
 
|-
 
|-
|<user data>
+
 
 +
|rowspan="2"|o<address>.access.granted.daily.limit
 +
|0
 
|W
 
|W
|16 characters hexadecimal representation of the first 8 bytes of access control data for user N (N from 1 to 2000) , to be stored in module’s EEPROM
+
|reset
 
|-
 
|-
|<reset>
+
|1
 
|W
 
|W
|reset to 0 the total and daily counters for user <n>
+
|allow access even when the daily limit of access grants has been exceeded
 
|-
 
|-
  
|o<address>.users
+
|rowspan="2"|o<address>.access.granted.time
|erase
+
|0
 +
|W
 +
|reset
 +
|-
 +
|1
 
|W
 
|W
|deletes all users data. This action requires up to about 27 seconds to be completed. It also deletes all i<address>.user.<n> and o<address>.user.<n> data points
+
|allow access even outside of the allowed timeframe
 
|-
 
|-
|}
 
  
----
+
|rowspan="2"|o<address>.access.granted.day
 
+
|0
=== MODKB ===
+
|W
 
+
|reset
MODKB is the keypad access control module.
 
 
 
It uses 1 input and 1 output address.
 
 
 
PIN configuration data are written to the module’s EEPROM (persistent memory).
 
 
 
{| class="wikitable"
 
!ID
 
!Value
 
!R/W
 
!Description
 
|-
 
 
 
|rowspan="2"|i<address>.1
 
|0  
 
|R
 
|input pin 1 off
 
 
|-
 
|-
 
|1
 
|1
|R
+
|W
|input pin 1 on
+
|allow access even outside of the allowed weekdays
 
|-
 
|-
  
|rowspan="2"|i<address>.2
+
|rowspan="2"|o<address>.access.granted.expired
|0  
+
|0
|R
+
|W
|input pin 2 off
+
|reset
 
|-
 
|-
 
|1
 
|1
|R
+
|W
|input pin 2 on
+
|allow access even when the tag is expired
 
|-
 
|-
  
|rowspan="2" style="white-space:nowrap"|i<address>.access.granted.<n>
+
|rowspan="2"|o<address>.site.<n>
|0
+
|read
|R
+
|W
|reset
+
|read the 8 bytes stored in module’s EEPROM for site N code (<n> from 1 to 4)
 
|-
 
|-
|1
+
|<site data>
|R
+
|W
|access granted to PIN <n> (<n> from 1 to 30)
+
|16 characters hexadecimal representation of the 8 bytes data of site N code (N from 1 to 4), to be stored in module’s EEPROM. After writing data, you should wait approximately 100ms before sending a read command
 
|-
 
|-
  
|i<address>.access.pin
+
|rowspan="2"|o<address>.mask
|style="white-space:nowrap"|<pin code>
+
|read
|R
+
|W
|the last pin code entered on the keypad (from 1 to 65535). Reset to 0 after programmed code persistence time
+
|read the 8 bytes mask stored in module’s EEPROM
 +
|-
 +
|<mask data>
 +
|W
 +
|16 characters hexadecimal representation of the 8 bytes site code mask, to be stored in module’s EEPROM. After writing data, you should wait approximately 100ms before sending a read command
 
|-
 
|-
  
|rowspan="5"|i<address>.access.granted.<n>
+
|rowspan="3"|o<address>.user.<n>
|0
+
|read
|R
+
|W
|access denied flags reset
+
|read the 16 bytes stored in module’s EEPROM for user N (<n> from 1 to 2000)
 
|-
 
|-
|site
+
|<user data>
|R
+
|W
|access denied due to site code error
+
|16 characters hexadecimal representation of the first 8 bytes of access control data for user N (N from 1 to 2000) , to be stored in module’s EEPROM
 
|-
 
|-
|code
+
|<reset>
|R
+
|W
|access denied due to user code error
+
|reset to 0 the total and daily counters for user <n>
|-
 
|time
 
|R
 
|access denied due to time range violation
 
|-
 
|day
 
|R
 
|access denied due to weekday violation
 
 
|-
 
|-
  
|i<address>.pin.<n>
+
|o<address>.users
|style="white-space:nowrap"|<pin data>
+
|erase
|R
+
|W
|16 characters hexadecimal representation of the 8 bytes data for PIN <n> (<n> from 1 to 30) stored in module’s EEPROM
+
|deletes all users data. This action requires up to about 27 seconds to be completed. It also deletes all i<address>.user.<n> and o<address>.user.<n> data points
 
|-
 
|-
 +
|}
  
|rowspan="2"|o<address>.pin.<n>
+
----
|<pin data>
+
 
 +
=== MODKB ===
 +
 
 +
MODKB is the keypad access control module.
 +
 
 +
It uses 1 input and 1 output address.
 +
 
 +
PIN configuration data are written to the module’s EEPROM (persistent memory).
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 +
|-
 +
 
 +
|rowspan="2"|i<address>.1
 +
|0
 
|R
 
|R
|pin data write successful
+
|input pin 1 off
 
|-
 
|-
|error
+
|1
 
|R
 
|R
|pin data write error
+
|input pin 1 on
 
|-
 
|-
  
|rowspan="2"|o<address>.relay
+
|rowspan="2"|i<address>.2
 
|0  
 
|0  
|W
+
|R
|relay output off
+
|input pin 2 off
 
|-
 
|-
 
|1
 
|1
|W
+
|R
|relay output on (pulse output, resets to 0 immediately after the relay is closed, usually before the relay closure time)
+
|input pin 2 on
 
|-
 
|-
  
|rowspan="2"|o<address>.lock.all
+
|rowspan="2" style="white-space:nowrap"|i<address>.access.granted.<n>
 
|0  
 
|0  
|W
+
|R
 
|reset
 
|reset
 
|-
 
|-
 
|1
 
|1
|W
+
|R
|disables access to all PINs
+
|access granted to PIN <n> (<n> from 1 to 30)
 
|-
 
|-
  
|rowspan="2"|o<address>.lock.<n>
+
|i<address>.pin
|0  
+
|style="white-space:nowrap"|<pin code>
|W
+
|R
|reset
+
|the last pin code entered on the keypad (from 1 to 65535). Reset to 0 after programmed code persistence time
 +
|-
 +
 
 +
|rowspan="5"|i<address>.access.granted.<n>
 +
|0  
 +
|R
 +
|access denied flags reset
 +
|-
 +
|site
 +
|R
 +
|access denied due to site code error
 +
|-
 +
|code
 +
|R
 +
|access denied due to user code error
 +
|-
 +
|time
 +
|R
 +
|access denied due to time range violation
 +
|-
 +
|day
 +
|R
 +
|access denied due to weekday violation
 
|-
 
|-
|1
+
 
|W
+
|i<address>.pin.<n>
|disables access to PIN <n> (<n> from 1 to 30)
+
|style="white-space:nowrap"|<pin data>
 +
|R
 +
|16 characters hexadecimal representation of the 8 bytes data for PIN <n> (<n> from 1 to 30) stored in module’s EEPROM
 
|-
 
|-
  
 
|rowspan="2"|o<address>.pin.<n>
 
|rowspan="2"|o<address>.pin.<n>
|read
+
|<pin data>
|W
+
|R
|read the 8 bytes stored in module’s EEPROM for PIN <n> (<n> from 1 to 30)
+
|pin data write successful
 
|-
 
|-
|<pin data>
+
|error
|W
+
|R
|16 characters hexadecimal representation of the 8 bytes data for PIN <n> (<n> from 1 to 30), to be stored in module’s EEPROM
+
|pin data write error
 
|-
 
|-
  
|}
+
|rowspan="2"|o<address>.relay
 +
|0
 +
|W
 +
|relay output off
 +
|-
 +
|1
 +
|W
 +
|relay output on (pulse output, resets to 0 immediately after the relay is closed, usually before the relay closure time)
 +
|-
 +
 
 +
|rowspan="2"|o<address>.lock.all
 +
|0
 +
|W
 +
|reset
 +
|-
 +
|1
 +
|W
 +
|disables access to all PINs
 +
|-
 +
 
 +
|rowspan="2"|o<address>.lock.<n>
 +
|0
 +
|W
 +
|reset
 +
|-
 +
|1
 +
|W
 +
|disables access to PIN <n> (<n> from 1 to 30)
 +
|-
 +
 
 +
|rowspan="2"|o<address>.pin.<n>
 +
|read
 +
|W
 +
|read the 8 bytes stored in module’s EEPROM for PIN <n> (<n> from 1 to 30)
 +
|-
 +
|<pin data>
 +
|W
 +
|16 characters hexadecimal representation of the 8 bytes data for PIN <n> (<n> from 1 to 30), to be stored in module’s EEPROM
 +
|-
 +
 
 +
|}
  
 
----
 
----
Line 5,117: Line 5,398:
 
----
 
----
  
== User Interface ==
+
=== MOD4TP/I ===
  
All CONTATTO devices data points that have been defined in the systemtopo.txt database are automatically listed in the Project Editor. Adding a button to control a device output point requires just a few clicks and no additional EVENTS logic.
+
8 digital input and 4 roller shutters or blinds with detection of travel time.
  
  
[[File:IO_Servers_Contatto_Project_Editor.png|center|border|600px]]
+
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 +
|-
  
 +
|rowspan="2"|i<address>.<N>
 +
|0
 +
|R
 +
|input pin N off
 +
|-
 +
|1
 +
|R
 +
|input pin N on
 +
|-
  
Besides the direct association of control buttons and data points, the CONTATTO driver also automatically updates graphical objects that represent values or states of complex devices, like the CLIMA2 temperature control unit. It will also automatically intercept buttons to manually set operation modes and temperature set-points.
+
|rowspan="10"|o<address>.<N>
 
+
|up
----
+
|RW
 +
|shutter N up command
 +
|-
 +
|down
 +
|RW
 +
|shutter N down command
 +
|-
 +
|stop
 +
|rowspan="2"|W
 +
|rowspan="2"|shutter N stop command
 +
|-
 +
|off
 +
|-
 +
|up1
 +
|W
 +
|shutter N up one step command
 +
|-
 +
|down1
 +
|W
 +
|shutter N down one step command
 +
|-
 +
|unknown
 +
|R
 +
|shutter N unknown state
 +
|-
 +
|offup
 +
|R
 +
|shutter N off, up position
 +
|-
 +
|offdown
 +
|R
 +
|shutter N off, down position
 +
|-
 +
|0-100
 +
|R
 +
|shutter N current position
 +
|-
  
=== CLIMA2 ===
+
|rowspan="2"|o<address>.calibration.<N>
 +
|0
 +
|R
 +
|shutter N normal operations
 +
|-
 +
|1
 +
|RW
 +
|shutter N calibration command
 +
|-
  
You can use the [[temp]] and [[tempmini]] objects to control CLIMA2 devices.
+
|-
 +
|o<address>.position.<N>
 +
|0-100
 +
|RW
 +
|shutter N position command
  
 +
|-
 +
|o<address>.slats.<N>
 +
|0-100
 +
|W
 +
|shutter N slats position command (no feedback available)
 +
|-
  
[[File:UI Object clima2.png|border]]
+
|}
  
 +
----
  
The fan button, in the bottom right-hand corner, is not enabled because the manual control of the fan speed is not available. The M button, in the top right-hand corner, allows to switch the module on or off.
+
=== MODRHT ===
  
You can also easily create customized controls for the CLIMA2, using standard graphic objects that are automatically set to show the device’s status and intercepted to send user commands.
+
Temperature, relative humidity and dew point sensor.
 
+
 
==== UISET Actions ====
+
It uses one input address and, if enabled by the configuration panel of MCP IDE, one output address.
{| class="wikitable"
+
 
!ID
+
{| class="wikitable"
!Attribute
+
!ID
!Set to
+
!Value
!Description
+
!R/W
|-
+
!Description
 
+
|-
|rowspan="2"|<address>.mode
+
 
|value
+
|i<address>.temp
|SUMMER
+
|<temp>
|summer mode (cooling)
+
|R
|-
+
|temperature value (in C/10)
|value
+
|-
|WINTER
+
 
|winter mode (heating)
+
|i<address>.rh
|-
+
|<%RH>
 
+
|R
|<address>.mode.label.summer
+
|relative humidity percentage (0-100)
|visible
+
|-
|true
+
 
|if CLIMA2 is in summer mode
+
|i<address>.dewpoint
|-
+
|<temp>
 
+
|R
|<address>.mode.label.winter
+
|dew point (in C/10)
|visible
+
|-
|true
+
 
|if CLIMA2 is in winter mode
+
|rowspan="2"|i<address>.dewpoint.1
|-
+
|0
 
+
|R
|rowspan="2"|<address>.status
+
|dew point lower than dew point threshold 1
|value
+
|-
|OFF
+
|1
|zone off
+
|R
|-
+
|dew point equal or greater than dew point threshold 1
|value
+
|-
|ON
+
 
|zone on
+
|rowspan="2"|i<address>.dewpoint.2
|-
+
|0
 
+
|R
|<address>.status.label.off
+
|dew point lower than dew point threshold 2
|visible
+
|-
|true
+
|1
|if the zone is not cooling or heating
+
|R
|-
+
|dew point equal or greater than dew point threshold 2
 
+
|-
|<address>.status.label.cooling
+
 
|visible
+
|o<address>.dewpoint.1
|true
+
|<temp>
|if the zone is cooling
+
|RW
|-
+
|dew point threshold 1 (in C/10)
 
+
|-
|<address>.status.label.heating
+
 
|visible
+
|o<address>.dewpoint.2
|true
+
|<temp>
|if the zone is heating
+
|RW
 +
|dew point threshold 2 (in C/10)
 +
|-
 +
 
 +
|}
 +
 
 +
----
 +
 
 +
=== MODAM2 ===
 +
 
 +
Multi-function, 2 inputs analog module.
 +
 
 +
Uses one input address.
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 +
|-
 +
 
 +
|i<address>.1
 +
|<value>
 +
|R
 +
|input 1 value (-32768 to +32767)
 +
|-
 +
 
 +
|i<address>.2
 +
|<value>
 +
|R
 +
|input 2 value (-32768 to +32767)
 +
|-
 +
|}
 +
 
 +
----
 +
 
 +
=== MODIGLASS and MODIGLASS3 ===
 +
 
 +
MODIGLASS is an input/output module with 6 touch buttons with addressable LEDs and a buzzer for audio feedback.
 +
 
 +
It uses 1 input and 1 output address.
 +
 
 +
{| class="wikitable"
 +
!ID
 +
!Value
 +
!R/W
 +
!Description
 +
|-
 +
 
 +
|rowspan="2"|i<address>.1
 +
|0
 +
|R
 +
|button 1 off
 +
|-
 +
|1
 +
|R
 +
|button 1 on
 +
|-
 +
 
 +
|rowspan="2"|i<address>.2
 +
|0
 +
|R
 +
|button 2 off
 +
|-
 +
|1
 +
|R
 +
|button 2 on
 +
|-
 +
 
 +
|rowspan="2"|i<address>.3
 +
|0
 +
|R
 +
|button 3 off
 +
|-
 +
|1
 +
|R
 +
|button 3 on
 +
|-
 +
 
 +
|rowspan="2"|i<address>.4
 +
|0
 +
|R
 +
|button 4 off
 +
|-
 +
|1
 +
|R
 +
|button 4 on
 +
|-
 +
 
 +
|rowspan="2"|i<address>.5
 +
|0
 +
|R
 +
|button 5 off
 +
|-
 +
|1
 +
|R
 +
|button 5 on
 +
|-
 +
 
 +
|rowspan="2"|i<address>.6
 +
|0
 +
|R
 +
|button 6 off
 +
|-
 +
|1
 +
|R
 +
|button 6 on
 +
|-
 +
 
 +
|rowspan="2"|i<address>.led.1
 +
|0
 +
|R
 +
|led 1 off
 +
|-
 +
|1
 +
|R
 +
|led 1 on
 +
|-
 +
 
 +
|rowspan="2"|i<address>.led.2
 +
|0
 +
|R
 +
|led 2 off
 +
|-
 +
|1
 +
|R
 +
|led 2 on
 +
|-
 +
 
 +
|rowspan="2"|i<address>.led.3
 +
|0
 +
|R
 +
|led 3 off
 +
|-
 +
|1
 +
|R
 +
|led 3 on
 +
|-
 +
 
 +
|rowspan="2"|i<address>.led.4
 +
|0
 +
|R
 +
|led 4 off
 +
|-
 +
|1
 +
|R
 +
|led 4 on
 +
|-
 +
 
 +
|rowspan="2"|i<address>.led.5
 +
|0
 +
|R
 +
|led 5 off
 +
|-
 +
|1
 +
|R
 +
|led 5 on
 +
|-
 +
 
 +
|rowspan="2"|i<address>.led.6
 +
|0
 +
|R
 +
|led 6 off
 +
|-
 +
|1
 +
|R
 +
|led 6 on
 +
|-
 +
 
 +
|rowspan="2"|i<address>.proximity
 +
|0
 +
|R
 +
|no proximity detected
 +
|-
 +
|1
 +
|R
 +
|proximity detected
 +
|-
 +
 
 +
 
 +
|rowspan="2"|o<address>.led.1
 +
|0
 +
|W
 +
|led 1 off
 +
|-
 +
|1
 +
|W
 +
|led 1 on
 +
|-
 +
 
 +
|rowspan="2"|o<address>.led.2
 +
|0
 +
|W
 +
|led 2 off
 +
|-
 +
|1
 +
|W
 +
|led 2 on
 +
|-
 +
 
 +
|rowspan="2"|o<address>.led.3
 +
|0
 +
|W
 +
|led 3 off
 +
|-
 +
|1
 +
|W
 +
|led 3 on
 +
|-
 +
 
 +
|rowspan="2"|o<address>.led.4
 +
|0
 +
|W
 +
|led 4 off
 +
|-
 +
|1
 +
|W
 +
|led 4 on
 +
|-
 +
 
 +
|rowspan="2"|o<address>.led.5
 +
|0
 +
|W
 +
|led 5 off
 +
|-
 +
|1
 +
|W
 +
|led 5 on
 +
|-
 +
 
 +
|rowspan="2"|o<address>.led.6
 +
|0
 +
|W
 +
|led 6 off
 +
|-
 +
|1
 +
|W
 +
|led 6 on
 +
|-
 +
 
 +
|rowspan="2"|o<address>.disable
 +
|0
 +
|RW
 +
|not disabled (normal mode)
 +
|-
 +
|1
 +
|RW
 +
|disabled (cleaning mode)
 +
|-
 +
 
 +
|rowspan="2"|o<address>.dim
 +
|0
 +
|RW
 +
|high intensity backlight
 +
|-
 +
|1
 +
|RW
 +
|low intensity backlight
 +
|-
 +
 
 +
|rowspan="2"|o<address>.proximity
 +
|0
 +
|RW
 +
|disable proximity backlight
 +
|-
 +
|1
 +
|RW
 +
|enable proximity backlight
 +
|-
 +
 
 +
|rowspan="2"|o<address>.backlight
 +
|0
 +
|RW
 +
|backlight off
 +
|-
 +
|1
 +
|RW
 +
|backlight on
 +
|-
 +
 
 +
|rowspan="2"|o<address>.buzzer
 +
|0
 +
|RW
 +
|buzzer disabled
 +
|-
 +
|1
 +
|RW
 +
|buzzer enabled
 +
|-
 +
 
 +
|}
 +
 
 +
You can also set the value to “on” or “off”, that is equivalent to 1 and 0.
 +
 
 +
----
 +
 
 +
== User Interface ==
 +
 
 +
All CONTATTO devices data points that have been defined in the systemtopo.txt database are automatically listed in the Project Editor. Adding a button to control a device output point requires just a few clicks and no additional EVENTS logic.
 +
 
 +
 
 +
[[File:IO_Servers_Contatto_Project_Editor.png|center|border|600px]]
 +
 
 +
 
 +
Besides the direct association of control buttons and data points, the CONTATTO driver also automatically updates graphical objects that represent values or states of complex devices, like the CLIMA2 temperature control unit. It will also automatically intercept buttons to manually set operation modes and temperature set-points.
 +
 
 +
----
 +
 
 +
=== CLIMA2 ===
 +
 
 +
You can use the [[temp]] and [[tempmini]] objects to control CLIMA2 devices.
 +
 
 +
 
 +
[[File:UI Object clima2.png|border]]
 +
 
 +
 
 +
The fan button, in the bottom right-hand corner, is not enabled because the manual control of the fan speed is not available. The M button, in the top right-hand corner, allows to switch the module on or off.
 +
 
 +
You can also easily create customized controls for the CLIMA2, using standard graphic objects that are automatically set to show the device’s status and intercepted to send user commands.
 +
 
 +
==== UISET Actions ====
 +
{| class="wikitable"
 +
!ID
 +
!Attribute
 +
!Set to
 +
!Description
 +
|-
 +
 
 +
|rowspan="2"|<address>.mode
 +
|value
 +
|SUMMER
 +
|summer mode (cooling)
 +
|-
 +
|value
 +
|WINTER
 +
|winter mode (heating)
 +
|-
 +
 
 +
|<address>.mode.label.summer
 +
|visible
 +
|true
 +
|if CLIMA2 is in summer mode
 +
|-
 +
 
 +
|<address>.mode.label.winter
 +
|visible
 +
|true
 +
|if CLIMA2 is in winter mode
 +
|-
 +
 
 +
|rowspan="2"|<address>.status
 +
|value
 +
|OFF
 +
|zone off
 +
|-
 +
|value
 +
|ON
 +
|zone on
 +
|-
 +
 
 +
|<address>.status.label.off
 +
|visible
 +
|true
 +
|if the zone is not cooling or heating
 +
|-
 +
 
 +
|<address>.status.label.cooling
 +
|visible
 +
|true
 +
|if the zone is cooling
 +
|-
 +
 
 +
|<address>.status.label.heating
 +
|visible
 +
|true
 +
|if the zone is heating
 
|-
 
|-
  
Line 5,552: Line 6,277:
  
 
|}
 
|}
 +
 +
----
 +
 +
=== MOD4TP/I ===
 +
 +
==== Using slider objects for MOD4TP/I shutter's position ====
 +
 +
You can use the slider objects, [[slider|sliderv]] and [[slider|sliderh]], to display and control the position. Set both the slider's ''ID'' and ''address'' to <server_name>.<address>.<N>, with N from 1 to 4.
 +
 +
{{tip|Note that you can set the ''inverse'' attribute of the [[slider|sliderv]] object to ''true'', in order to have the cursor at the top instead of bottom of the slider when the position is 0.}}
  
 
== Release Notes ==
 
== Release Notes ==
 +
 +
=== 3.7.0 ===
 +
*support of MODRHT
 +
*support of MODAM2
 +
*support of MODIGLASS, MODIGLASS3
 +
*support of MODLC firmware version 3.2
 +
*support of MODDALI firmware version 6.x
 +
*support of MCP counters
 +
*bus and modules fault detection
 +
*fixes to the MODDALI ballast 1 status data point
 +
 +
=== 3.6.0 ===
 +
*added support for MOD32IL
 +
*added support for MOD4TP/I
 +
*added support for MODDALI8
 +
*added support for MODANAM
 +
*fixed a bug that could cause erroneous readings of MODANA's ptotk datapoint when total active power is negative
 +
 +
=== 3.5.1 ===
 +
*MODANA updated to support negative active energy values  (fw. 1.5 or later)
  
 
=== 3.5.0 ===
 
=== 3.5.0 ===
**added support for MCP4
+
*added support for MCP4
**added support for MODCA firmware version 2.0, with new "relay.forced" datapoint
+
*added support for MODCA firmware version 2.0, with new "relay.forced" datapoint
**MODPQ5 is now identified with its unique ID. Use MCPIDE 3.2.3 or later to program the MCPXT/MCP4 to allow HSYCO to correctly identify this module
+
*added support for MOD32IN
 +
*MODPQ5 is now identified with its unique ID. Use MCPIDE 3.2.3 or later to program the MCPXT/MCP4 to allow HSYCO to correctly identify this module
  
 
=== 3.4.0 ===
 
=== 3.4.0 ===

Latest revision as of 09:40, 1 October 2020

The CONTATTO system is DUEMMEGI’s proprietary bus architecture for building automation. HSYCO fully integrates with this system through the MCP control and gateway module, and its FXP-XT serial communication protocol.

A serial connection between the MCPXT and the HSYCO SERVER is required for the integration, either directly through the server’s RS-232 port or via the RS-232 port of a supported serial to IP gateway, including the WEBS module.

The MCP4 can be connected via the integrated serial to IP gateway.

The Contatto I/O Server requires MCP-XT firmware version 3.0 or later. The MCPIDE configuration tools pass-through support for secure access to the MCP via HSYCO requires MCPIDE version 3.2.3 or later.

Communication

Use a DE-9 (often called DB-9) male-female RS-232 straight cable to connect the RS-232 MCPXT port to the serial port on HSYCO SERVER or serial gateway. You can also connect the MCPXT using the RS-485 port. The MCP4 can also be connected via the integrated serial to IP gateway.

RS-232 parameters:

Baud rate 9600, 38400, 57600 or 115200 bps (according to the MCP serial port setting)
Data bits 8
Stop bit 1
Parity none
Flow control none

Note A speed of 115200 bps is recommended to achieve good performance, particularly when the number of devices connected to the bus is large.


High Availability

  • Shutdown when inactive: defaults to false.

HSYCO Configuration

You can define and connect to more than one CONTATTO bus using several MCP gateways.

The CONTATTO I/O Server also supports dual, redundant connections between HSYCO and MCP.

If the main connection fails, HSYCO automatically re-routes the communication with MCP through the fail-over connection.

Options

ID Default Values Description
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
inputdiscovery false true auto-detects CONTATTO’s input devices as configured in the MCP, and automatically creates the list of all detected devices and individual data points in the systemtopo.txt file. Should be enabled to allow the automatic update of (button) objects’ states
false auto-detect for input devices is disabled
outputdiscovery true true auto-detects CONTATTO’s output devices as configured in the MCP, and automatically creates the list of all detected devices and individual data points in the systemtopo.txt file. Should be enabled to allow the automatic update of (button) objects’ states
false auto-detect for output devices is disabled
virtualdiscovery false true auto-detects CONTATTO’s virtual points for input and output devices as configured in the MCP, and automatically creates the list of all detected virtual data points in the systemtopo.txt file. Should be enabled to allow the automatic update of (button) objects’ states
false auto-detect for devices’ virtual data points is disabled
virtualpoints false 1 ... 2032 enables polling for the first n virtual points of the MCP. Enable this option only if you need to generate I/O events based on these virtual points
true enables polling for all the 2032 virtual points of the MCP
false polling of the MCP virtual data points is disabled
registers false 1 ... 1024 enables polling for registers R0-Rn of the MCP. Enable this option only if you need to generate I/O events based on these registers
true enables polling for registers R0-R127 of the MCP
false polling of the MCP registers is disabled
powerdisplay false ≥ 0 (MODANA address) enables the automatic display in the GUI of the total real power measured by a MODANA or MODANAM module connected to this MCP. Note that, if you have more than one MCP gateway, you should enable this option for one gateway only
false power display disabled for this MCP
powersensivity 50 ≥ 0 measured power changes are reported only if the difference from last reading is equal or greater than the power sensivity option, in Watts
detectevents false true generate forced events when a device is detected at start-up
false do not generate events when a device is detected at start-up
toolspassword string set this option with a long string (only letters and numbers) password to allow the remote connection of MCP-IDE and other configuration tools to the MCP gateways that are connected to HSYCO. For additional security, it is recommended to set this option only when required
language english en it fr language for all messages from the CONTATTO system: English, Italian or French

Initialization and Connection Events

Event name Value Description
connection online connection established to the MCP module
offline HSYCO can’t connect to the MCP module
detected.input.<n>. model name an input device of the type passed as value has been detected at address <n>, using addresses
detected.output.<n>. model name an output device of the type passed as value has been detected at address <n>, using addresses

The Device Configuration Database

The systemtopo.txt file contains the list of all devices and their individual input, output and virtual data points that could be directly associated to graphic object in the Web-based user interface. This file can be filled manually or automatically by HSYCO at start-up.

To enable automatic discovery and automatic generation of devices’ information in the systemtopo file, use the inputdiscovery, outputdiscovery and virtualdiscovery options in Settings. The default behavior is to only discover devices with output data points.

This is an example of an automatically generated systemtopo.txt file:

(devices)
contatto.o10.1 : LIGHT ; LIGHT
contatto.o6.1 : LIGHT ; DIMMER
contatto.o7.2 : LIGHT ; LIGHT
contatto.o7.1 : LIGHT ; DIMMER
contatto.o9.2 : AUTOM ; VSHUT
contatto.o5.4 : LIGHT ; LIGHT
contatto.o9.1 : AUTOM ; VSHUT
contatto.o5.3 : LIGHT ; LIGHT
contatto.o5.2 : LIGHT ; LIGHT
contatto.o5.1 : LIGHT ; LIGHT

You should then manually add comments and other optional parameters:

(devices)
contatto.o10.1 : LIGHT ; LIGHT; main entrance light
contatto.o6.1 : LIGHT ; DIMMER; lobby dimmer
contatto.o7.2 : LIGHT ; LIGHT; kitchen workbench
contatto.o7.1 : LIGHT ; DIMMER; kitchen main dimmer

MCP Data Points

The MCP implements 2032 virtual points for binary (on/off) data and 1024 registers and counters for positive scalar values (0-65535). All virtual points, registers and counters can optionally generate I/O events. You can also write to the virtual data points, registers and counters using the IO action in EVENTS or ioSet() method in Java.

You cannot directly control the MCP virtual data points, registers or counters using GUI objects.

To enable polling of the current state of the MCP’s virtual data points, enable the virtualpoints options in hsyco.ini.

To enable polling of the current state of the MCP’s registers, enable the registers options in hsyco.ini.

To enable polling of the current state of the MCP’s counters, enable the counters options in hsyco.ini.

If you only have to write to virtual points, registers or counters, enabling polling is not strictly required.

ID Value R/W Description
busfault 0 R no bus fault detected
1 R bus fault detected
modulefault 0 R no modules fault detected
1 R modules fault detected
v0.<n> 0 RW virtual data point <n> off (<n>: 1-2032)
1 RW virtual data point <n> on (<n>: 1-2032)
r0.<n> <x> RW register <n> (<n>: 0-1023) set to value <x> (<x>: 0-65535)
c0.<n> <x> RW counter <n> (<n>: 0-1023) set to value <x> (<x>: 0-65535)

MCP Internal Clock

The MCP module has an integrated real-time clock. You can use the clock datapoint to read the MCP date and time, and set the MCP clock to HSYCO’s current time.

ID Value R/W Description
clock yyyy-mm-dd hh:mm:ss R the MCP clock current time
read W read the MCP clock, and the delta with HSYCO’s time
sync W set the MCP clock to HSYCO’s current time
clock.delta integer number R the delta time in seconds between the MCP and HSYCO clocks. A positive number means that the MCP clock is ahead of HSYCO

CONTATTO Modules Events and Control

Each CONTATTO module has its own set of read-only or read-write data points, mapping the specific set of features.

All modules also have a read-only "fault" data point, set to 1 if the MCP has detected a module fault condition, or 0 if the module is working normally.

ID Value R/W Description
i<address>.fault 0 R input module working normally
1 R input module fault detected
o<address>.fault 0 R output module working normally
1 R output module fault detected


Module Code Description
MOD8I/A 8 digital input module for NO contacts in modular housing
MOD32I/A 32 digital input module for NO contacts in modular housing
MOD32IL 32 digital input module for NO contacts in modular housing
MOD32IN 32 digital input module for NO contacts in modular housing
MOD8INP2/A 8 digital input module for NO contacts
MOD8INP2/C 8 digital input module for NC contacts
MOAN/I 0÷10V analog input module
MOAN/I4 quad 0÷10V analog input module
MI420 4÷20mA analog input module
MI420-X4 quad 4÷20mA analog input module
MOD4AM12/V/I 4-channel 0÷10V or 4÷20mA (0÷21mA) analog input module
MOD2PT input module for two PT100 temperature probes
MODCNT 4-channel counter module in modular housing
MODNTC input module for ambient temperature sensors and potentiometers
MOD4I/A 4-digital input module for NO contacts in modular housing
MOD4I/S 4-digital input module for NO contacts in 2M modular housing
MODLUX ambient light measurement module with sensor for ceiling mounting
MODMETEO meteorological data detection module for Contatto bus
MOD8R 8 power relay output module
MODPNP 8 positive logic (PNP) “open collector” digital output module
MODREL 8 relay output compact module in DIN 3M housing
MOAN/U 0÷10V analog output module
MO420 4÷20mA analog output module
MODLC, MODLC-P ambient light regulator module with integrated sensor
MOD4-4S 4 digital input and 4 power relay output multifunction module
MOD2-2R 2 digital input and 2 power relay output module
MOD4-4 4 digital input and 4 digital output module
MOD2DM 2x300W dimmer module
MOD2DV dual 1-10V output for electronic ballast driving
MOD8IL 8 digital input – 8 LED output module for wall box
MOD4DV quad 0-10V output module for generic applications or for external dimmers control
MODDMX DMX gateway
MODDALI 4-channel DALI gateway
MODDALI8 8-channel broadcast DALI gateway
CLIMA2 module for the regulation of the ambient temperature
MODANA network analyzer module
MODANAM network analyzer module
MODPQ5 tags proximity reader and programmer
MODHT hotel room controller
MODCA access control module
MODKB keypad access control module
MODDI 500W IGBT dimmer module
MODCL temperature control module
MOD4TP/I 8 digital input and 4 roller shutters or blinds with detection of travel time
MODRHT Temperature, relative humidity and dew point sensor
MODAM2 Multi-function, 2 inputs analog module
MODIGLASS, MODIGLASS3 6 button touch keypad

MOD8I/A

8 digital input module for NO contacts in modular housing.

It uses one input address in the CONTATTO bus.

ID Value R/W Description
i<address>.1 0 R input pin 1 off
1 R input pin 1 on
i<address>.2 0 R input pin 2 off
1 R input pin 2 on
i<address>.3 0 R input pin 3 off
1 R input pin 3 on
i<address>.4 0 R input pin 4 off
1 R input pin 4 on
i<address>.5 0 R input pin 5 off
1 R input pin 5 on
i<address>.6 0 R input pin 6 off
1 R input pin 6 on
i<address>.7 0 R input pin 7 off
1 R input pin 7 on
i<address>.8 0 R input pin 8 off
1 R input pin 8 on

MOD32I/A

32 digital input module for NO contacts in modular housing.

It uses four addresses of the Contatto bus, one for each group of 8 inputs.

ID Value R/W Description
i<address>.1 0 R input pin 1 off
1 R input pin 1 on
i<address>.2 0 R input pin 2 off
1 R input pin 2 on
i<address>.3 0 R input pin 3 off
1 R input pin 3 on
i<address>.4 0 R input pin 4 off
1 R input pin 4 on
i<address>.5 0 R input pin 5 off
1 R input pin 5 on
i<address>.6 0 R input pin 6 off
1 R input pin 6 on
i<address>.7 0 R input pin 7 off
1 R input pin 7 on
i<address>.8 0 R input pin 8 off
1 R input pin 8 on
i<address+1>.1 0 R input pin 1 off
1 R input pin 1 on
i<address+1>.2 0 R input pin 2 off
1 R input pin 2 on
i<address+1>.3 0 R input pin 3 off
1 R input pin 3 on
i<address+1>.4 0 R input pin 4 off
1 R input pin 4 on
i<address+1>.5 0 R input pin 5 off
1 R input pin 5 on
i<address+1>.6 0 R input pin 6 off
1 R input pin 6 on
i<address+1>.7 0 R input pin 7 off
1 R input pin 7 on
i<address+1>.8 0 R input pin 8 off
1 R input pin 8 on
i<address+2>.1 0 R input pin 1 off
1 R input pin 1 on
i<address+2>.2 0 R input pin 2 off
1 R input pin 2 on
i<address+2>.3 0 R input pin 3 off
1 R input pin 3 on
i<address+2>.4 0 R input pin 4 off
1 R input pin 4 on
i<address+2>.5 0 R input pin 5 off
1 R input pin 5 on
i<address+2>.6 0 R input pin 6 off
1 R input pin 6 on
i<address+2>.7 0 R input pin 7 off
1 R input pin 7 on
i<address+2>.8 0 R input pin 8 off
1 R input pin 8 on
i<address+3>.1 0 R input pin 1 off
1 R input pin 1 on
i<address+3>.2 0 R input pin 2 off
1 R input pin 2 on
i<address+3>.3 0 R input pin 3 off
1 R input pin 3 on
i<address+3>.4 0 R input pin 4 off
1 R input pin 4 on
i<address+3>.5 0 R input pin 5 off
1 R input pin 5 on
i<address+3>.6 0 R input pin 6 off
1 R input pin 6 on
i<address+3>.7 0 R input pin 7 off
1 R input pin 7 on
i<address+3>.8 0 R input pin 8 off
1 R input pin 8 on

MOD32IL

32 digital input module for NO contacts in modular housing.

It uses one addresses of the Contatto bus and four channels, one for each group of 8 inputs.

ID Value R/W Description
i<address>.N

N=1-32

0 R input pin N off
1 R input pin N on

MOD32IN

32 digital input module for NO contacts in modular housing.

It uses one addresses of the Contatto bus and four channels, one for each group of 8 inputs.

ID Value R/W Description
i<address>.N

N=1-32

0 R input pin N off
1 R input pin N on

MOD8INP2/A

8 digital input module for NO contacts.

It uses one input address of the Contatto bus.

ID Value R/W Description
i<address>.1 0 R input pin 1 off
1 R input pin 1 on
i<address>.2 0 R input pin 2 off
1 R input pin 2 on
i<address>.3 0 R input pin 3 off
1 R input pin 3 on
i<address>.4 0 R input pin 4 off
1 R input pin 4 on
i<address>.5 0 R input pin 5 off
1 R input pin 5 on
i<address>.6 0 R input pin 6 off
1 R input pin 6 on
i<address>.7 0 R input pin 7 off
1 R input pin 7 on
i<address>.8 0 R input pin 8 off
1 R input pin 8 on

MOD8INP2/C

8 digital input module for NC contacts.

It uses one input address of the Contatto bus.

ID Value R/W Description
i<address>.1 0 R input pin 1 off
1 R input pin 1 on
i<address>.2 0 R input pin 2 off
1 R input pin 2 on
i<address>.3 0 R input pin 3 off
1 R input pin 3 on
i<address>.4 0 R input pin 4 off
1 R input pin 4 on
i<address>.5 0 R input pin 5 off
1 R input pin 5 on
i<address>.6 0 R input pin 6 off
1 R input pin 6 on
i<address>.7 0 R input pin 7 off
1 R input pin 7 on
i<address>.8 0 R input pin 8 off
1 R input pin 8 on

MOAN/I

0÷10V analog input module.

It uses one input address in the range 1 to 127 of the Contatto bus.

ID Value R/W Description
i<address>.1 0 ... 255 R voltage value divided in 255 steps

MOAN/I4

Quad 0÷10V analog input module.

It uses four consecutive addresses of the Contatto bus, one for each input.

ID Value R/W Description
i<address>.1 0 ... 255 R voltage value divided in 255 steps
i<address+1>.1 0 ... 255 R voltage value divided in 255 steps
i<address+2>.1 0 ... 255 R voltage value divided in 255 steps
i<address+3>.1 0 ... 255 R voltage value divided in 255 steps

MI420

4÷20mA analog input module.

It uses one input address in the range 1 to 127 of the Contatto bus.

ID Value R/W Description
i<address>.1 0 ... 255 R current value divided in 255 steps

MI420-X4

Quad 4÷20mA analog input module.

It uses four consecutive addresses of the Contatto bus, one for each input.

ID Value R/W Description
i<address>.1 0 ... 255 R current value divided in 255 steps
i<address+1>.1 0 ... 255 R current value divided in 255 steps
i<address+2>.1 0 ... 255 R current value divided in 255 steps
i<address+3>.1 0 ... 255 R current value divided in 255 steps

MOD4AM12/V/I

4-channel 0÷10V or 4÷20mA (0÷21mA) analog input module.

It uses one input address of the Contatto bus.

ID Value R/W Description
i<address>.1 0 ... 4095 R measurement range divided in 4095 steps
i<address>.2 0 ... 4095 R measurement range divided in 4095 steps
i<address>.3 0 ... 4095 R measurement range divided in 4095 steps
i<address>.4 0 ... 4095 R measurement range divided in 4095 steps

MOD2PT

Input module for two PT100 temperature probes.

It uses one or two addresses according to how the dip-switch is set.

If both channels are enabled (IN1 and IN2), setting the n “base” address through the FXPRO programmer, the input address and address+1 (consecutive) will be automatically assigned to the module.

ID Value R/W Description
i<address>.1 0 ... 255 R range –40 ÷ +87.5°C: code 0 corresponds to –40°C and code 255 corresponds to +87.5°C
i<address+1>.1 0 ... 255 R range –40 ÷ +87.5°C: code 0 corresponds to –40°C and code 255 corresponds to +87.5°C

MODCNT

4-channel counter module in modular housing.

It uses one input address of the Contatto bus.

ID Value R/W Description
i<address>.1 0 ... 65535 R number of pulses
i<address>.2 0 ... 65535 R number of pulses
i<address>.3 0 ... 65535 R number of pulses
i<address>.4 0 ... 65535 R number of pulses

MODNTC

Input module for ambient temperature sensors and potentiometers.

It uses one input address of the Contatto bus.

The temperature values measured by MODNTC module are reported as Kelvin degrees multiplied by 10; in other words, 0°C will be reported as 2730, 0.1°C will be reported as 2731 and so on.

Concerning the potentiometer channels, the values read from the module will be 0 with the potentiometer at its minimum position and it will be 1000 with the potentiometer at its maximum position.

ID Value R/W Description
i<address>.1 0 ... 4095 R temperature value
i<address>.2 0 ... 4095 R temperature value
i<address>.3 0 ... 4095 R temperature value
i<address>.4 0 ... 4095 R temperature value

MOD4I/A

4-digital input module for NO contacts in modular housing.

It uses one input address in the range 1 to 127 of the Contatto bus.

ID Value R/W Description
i<address> 0 R input pin 1 off
1 R input pin 1 on
i<address+1> 0 R input pin 1 off
1 R input pin 1 on
i<address+2> 0 R input pin 1 off
1 R input pin 1 on
i<address+3> 0 R input pin 1 off
1 R input pin 1 on

MOD4I/S

4-digital input module for NO contacts in 2M modular housing.

It uses one address of the Contatto bus.

ID Value R/W Description
i<address> 0 R input pin 1 off
1 R input pin 1 on
i<address+1> 0 R input pin 1 off
1 R input pin 1 on
i<address+2> 0 R input pin 1 off
1 R input pin 1 on
i<address+3> 0 R input pin 1 off
1 R input pin 1 on

MODLUX

Ambient light measurement module with sensor for ceiling mounting.

It uses one address of the Contatto bus.

ID Value R/W Description
i<address>.1 0 ... 1023 R ambient brightness value

MODMETEO

Meteorological data detection module for Contatto bus.

It uses one input address and, if enabled by the configuration panel of MCP IDE, one output address with the same value.

ID Value R/W Description
i<address>.temp <temp> R temperature value (in C/10)
i<address>.lux <lux*10> R daylight value in tens of LUX
i<address>.wind 1 m/s / 10 R wind speed value
i<address>.rain 0 R no rain
1 R rain
i<address>.night 0 R day
1 R night
i<address>.temp.limit 0 R measured temperature < threshold
1 R measured temperature > threshold
i<address>.lux.limit 0 R measured daylight < threshold
1 R measured daylight > threshold
i<address>.wind.limit 0 R measured wind speed < threshold
1 R measured wind speed > threshold
i<address>.light.south 0 R light not from South
1 R light from South
i<address>.light.west 0 R light not from West
1 R light from West
i<address>.light.east 0 R light not from East
1 R light from East
i<address>.fault 0 R sensor works correctly
1 R sensor failure
o<address>.temp <temp> RW temperature threshold (in C/10)
off RW temperature threshold off
o<address>.lux <lux*10> RW daylight threshold
off RW daylight threshold off
o<address>.wind 1 m/s / 10 RW wind speed threshold
off RW wind speed threshold off

MOD8R

8 power relay output module.

It uses one output address of the Contatto bus.

ID Value R/W Description
o<address>.1 0 RW output pin 1 off
1 RW output pin 1 on
o<address>.2 0 RW output pin 2 off
1 RW output pin 2 on
o<address>.3 0 RW output pin 3 off
1 RW output pin 3 on
o<address>.4 0 RW output pin 4 off
1 RW output pin 4 on
o<address>.5 0 RW output pin 5 off
1 RW output pin 5 on
o<address>.6 0 RW output pin 6 off
1 RW output pin 6 on
o<address>.7 0 RW output pin 7 off
1 RW output pin 7 on
o<address>.8 0 RW output pin 8 off
1 RW output pin 8 on

You can also set the value to “on” or “off”, that is equivalent to 1 and 0.


MODPNP

8 positive logic (PNP) “open collector” digital output module.

It uses one output address in the range 1 to 127 of the Contatto bus.

ID Value R/W Description
o<address>.1 0 RW output pin 1 off
1 RW output pin 1 on
o<address>.2 0 RW output pin 2 off
1 RW output pin 2 on
o<address>.3 0 RW output pin 3 off
1 RW output pin 3 on
o<address>.4 0 RW output pin 4 off
1 RW output pin 4 on
o<address>.5 0 RW output pin 5 off
1 RW output pin 5 on
o<address>.6 0 RW output pin 6 off
1 RW output pin 6 on
o<address>.7 0 RW output pin 7 off
1 RW output pin 7 on
o<address>.8 0 RW output pin 8 off
1 RW output pin 8 on

You can also set the value to “on” or “off”, that is equivalent to 1 and 0.


MODREL

8 relay output compact module in DIN 3M housing.

It uses one output address in the range 1 to 127 of the Contatto bus.

ID Value R/W Description
o<address>.1 0 RW output pin 1 off
1 RW output pin 1 on
o<address>.2 0 RW output pin 2 off
1 RW output pin 2 on
o<address>.3 0 RW output pin 3 off
1 RW output pin 3 on
o<address>.4 0 RW output pin 4 off
1 RW output pin 4 on
o<address>.5 0 RW output pin 5 off
1 RW output pin 5 on
o<address>.6 0 RW output pin 6 off
1 RW output pin 6 on
o<address>.7 0 RW output pin 7 off
1 RW output pin 7 on
o<address>.8 0 RW output pin 8 off
1 RW output pin 8 on

You can also set the value to “on” or “off”, that is equivalent to 1 and 0.


MOAN/U

0÷10V analog output module.

It uses one output address in the range 1 to 127 of the Contatto bus.

ID Value R/W Description
o<address> x/255 R value in fractional format, where 0 ≤ x ≤ 255
o<address> <x%> W the percentage of signal (0÷100%) applied to the output
0...255 W convert the 8 bits digital code received through the bus in the proper analog level.
x/y W fractional format, formatted as “x/y”, where 0 ≤ x ≤ y

MO420

4÷20mA analog output module.

It uses one output address in the range 1 to 127 of the Contatto bus.

ID Value R/W Description
o<address> <x%> RW the percentage of signal (0÷100%) applied to the output
0...255 RW convert the 8 bits digital code received through the bus in the proper analog level
x/y RW fractional format, formatted as “x/y”, where 0 ≤ x ≤ y

MODLC and MODLC-P

Ambient light regulator module with integrated sensor.

It uses one input address and, if enabled by the configuration panel of MCP IDE, one output address with the same value.

ID Value R/W Description
i<address>.lux value equivalent to three times the brightness in lux detected by the sensor R the brightness value in lux detected by the MODLC
i<address>.level calculated value for the automatic brightness regulation R the value to be sent to the dimmer in order to execute the automatic regulation
i<address>.mode auto R automatic regulation
man R manual regulation
i<address>.in 0 R digital input 2 (including presence delay) OFF
1 R digital input 2 (including presence delay) ON
i<address>.in1 0 R digital input 1 OFF
1 R digital input 1 ON
i<address>.in2 0 R digital input 2 OFF
1 R digital input 2 ON
o<address>.setpoint setpoint value RW set the setpoint for the automatic brightness regulation
o<address>.preset setpoint value RW set the preset dimmer value (SMART mode only)
o<address>.delay setpoint value RW set the presence detector delay in seconds
o<address>.mode auto RW set automatic control
man RW set manual control
o<address>.in.reset 0 R not active
1 RW force the expiring of the deactivation delay time of the digital input
o<address>.mode.reset 0 RW not active
1 RW disable automatic control
o<address>.full.reset 0 RW not active
1 RW perform a full reset
o<address>.v 0 RW virtual point off
1 RW virtual point on
o<address>.in.disable 0 RW normal presence detector operation (SMART mode)
1 RW disable light ON control from presence detector (SMART mode)
o<address>.presence 0 RW not active
1 RW presence forced

MOD4-4S

4 digital input and 4 power relay output multifunction module.

HSYCO supports two configurations only: four independent outputs, or two shutters.

When set as four independent outputs, the module must be configured with the same base address for input and output.

For example:

(I20, O20)

The input address must be enabled. Configuration switches must be set as SW1=OFF, SW2=OFF and SW5=ON.

When set as two shutters, the module must be configured with the same base address for input and output.

For example:

(I20, O20, O21)

The input address must be enabled. Configuration switches must be set as SW1=ON, SW2=ON and SW5=ON.

ID Value R/W Description
i<address>.1 0 R input pin 1 off
1 R input pin 1 on
i<address>.2 0 R input pin 2 off
1 R input pin 2 on
i<address>.3 0 R input pin 3 off
1 R input pin 3 on
i<address>.4 0 R input pin 4 off
1 R input pin 4 on
o<address>.1 up RW shutter up command
down RW shutter down command
stop RW shutter stop command
unknown R unknown state
offup R shutter off, up position
offdown R shutter off, down position
o<address+1>.1 up RW shutter up command
down RW shutter down command
stop RW shutter stop command
unknown R unknown state
offup R shutter off, up position
offdown R shutter off, down position
o<address>.1 0 RW output pin 1 off
1 RW output pin 1 on
o<address>.2 0 RW output pin 2 off
1 RW output pin 2 on
o<address>.3 0 RW output pin 3 off
1 RW output pin 3 on
o<address>.4 0 RW output pin 4 off
1 RW output pin 4 on

You can also set the value to “on” or “off”, that is equivalent to 1 and 0.


MOD2-2R

2 digital input and 2 power relay output module.

It uses one input address and one output address in the range 1 to 127 of the Contatto bus.

The input and the output addresses may be the same or they can be different each one to the other.

ID Value R/W Description
i<address>.1 0 R input pin 1 off
1 R input pin 1 on
i<address>.2 0 R input pin 2 off
1 R input pin 2 on
o<address>.1 0 RW output pin 1 off
1 RW output pin 1 on
o<address>.2 0 RW output pin 2 off
1 RW output pin 2 on

You can also set the value to “on” or “off”, that is equivalent to 1 and 0.


MOD4-4R

4 digital input and 4 digital output module.

It uses one input address and one output address in the range 1 to 127 of the Contatto bus.

The input and the output addresses may be the same or they can be different each one to the other.

ID Value R/W Description
i<address>.1 0 R input pin 1 off
1 R input pin 1 on
i<address>.2 0 R input pin 2 off
1 R input pin 2 on
i<address>.3 0 R input pin 3 off
1 R input pin 3 on
i<address>.4 0 R input pin 4 off
1 R input pin 4 on
o<address>.1 0 RW output pin 1 off
1 RW output pin 1 on
o<address>.2 0 RW output pin 2 off
1 RW output pin 2 on
o<address>.3 0 RW output pin 3 off
1 RW output pin 3 on
o<address>.4 0 RW output pin 4 off
1 RW output pin 4 on

MOD2DM

2x300W dimmer module.

It uses 2 output addresses (one for each dimmer channel) and 2 input addresses.

HSYCO supports this module only when its dip-switches are set as SW1=ON, SW2=ON, SW3=ON, SW4=ON.

ID Value R/W Description
i<address> 0...100 R brightness level according to current ramp
off R dimmer off
i<address+1> 0...100 R brightness level according to current ramp
off R dimmer off
o<address> 0...100 RW brightness level according to current ramp
off RW dimmer off
101...255 W command (see MOD2DM commands table)
o<address+1> 0...100 RW brightness level according to current ramp
off RW dimmer off
101...255 W command (see MOD2DM commands table)

The dimmer level can be set using additional formats besides the standard percent values:

  • absolute positive integer number between 0 and 100
  • percent number, formatted as x%
  • fractional format, formatted as “n/m”, where 0 <= n <= m.

MOD2DV

Dual 1-10V output for electronic ballast driving.

It uses 2 output addresses (one for each dimmer channel) and 2 input addresses.

HSYCO supports this module only when its dip-switches are set as SW1=ON, SW2=ON, SW3=ON, SW4=ON.

ID Value R/W Description
i<address> 0...100 R brightness level according to current ramp
off R dimmer off
i<address+1> 0...100 R brightness level according to current ramp
off R dimmer off
o<address> 0...100 RW brightness level according to current ramp
off RW dimmer off
101...255 W command (see MOD2DV commands table)
o<address+1> 0...100 RW brightness level according to current ramp
off RW dimmer off
101...255 W command (see MOD2DV commands table)

The dimmer level can be set using additional formats besides the standard percent values:

  • absolute positive integer number between 0 and 100
  • percent number, formatted as x%
  • fractional format, formatted as “n/m”, where 0 <= n <= m.

MOD8IL

8 digital input – 8 LED output module for wall box.

It uses 1 input address and 1 output address.

ID Value R/W Description
i<address>.1 0 R input pin 1 off
1 R input pin 1 on
i<address>.2 0 R input pin 2 off
1 R input pin 2 on
i<address>.3 0 R input pin 3 off
1 R input pin 3 on
i<address>.4 0 R input pin 4 off
1 R input pin 4 on
i<address>.5 0 R input pin 5 off
1 R input pin 5 on
i<address>.6 0 R input pin 6 off
1 R input pin 6 on
i<address>.7 0 R input pin 7 off
1 R input pin 7 on
i<address>.8 0 R input pin 8 off
1 R input pin 8 on
o<address>.1 0 RW output pin 1 off
1 RW output pin 1 on
o<address>.2 0 RW output pin 2 off
1 RW output pin 2 on
o<address>.3 0 RW output pin 3 off
1 RW output pin 3 on
o<address>.4 0 RW output pin 4 off
1 RW output pin 4 on
o<address>.5 0 RW output pin 5 off
1 RW output pin 5 on
o<address>.6 0 RW output pin 6 off
1 RW output pin 6 on
o<address>.7 0 RW output pin 7 off
1 RW output pin 7 on
o<address>.8 0 RW output pin 8 off
1 RW output pin 8 on

You can also set the value to “on” or “off”, that is equivalent to 1 and 0.


MOD4DV

Quad 0-10V output module for generic applications or for external dimmers control.

It uses 4 consecutive output addresses (one for each dimmer channel) and 4 input addresses.

HSYCO supports this module only when its dip-switches are set as SW1=ON, SW2=ON, SW3=ON, SW4=ON, SW5=OFF.

ID Value R/W Description
i<address> 0...100 R brightness level according to current ramp
off R dimmer off
i<address+1> 0...100 R brightness level according to current ramp
off R dimmer off
i<address+2> 0...100 R brightness level according to current ramp
off R dimmer off
i<address+3> 0...100 R brightness level according to current ramp
off R dimmer off
o<address> 0...100 RW brightness level according to current ramp
off RW dimmer off
101...255 W command (see MOD4DV commands table)
o<address+1> 0...100 RW brightness level according to current ramp
off RW dimmer off
101...255 W command (see MOD4DV commands table)
o<address+2> 0...100 RW brightness level according to current ramp
off RW dimmer off
101...255 W command (see MOD4DV commands table)
o<address+3> 0...100 RW brightness level according to current ramp
off RW dimmer off
101...255 W command (see MOD4DV commands table)

The dimmer level can be set using additional formats besides the standard percent values:

  • absolute positive integer number between 0 and 100
  • percent number, formatted as x%
  • fractional format, formatted as “x/y”, where 0 <= x <= y
  • values in the range 101÷255. Values and commands are described in the MOD4DV Programming Handbook (Operation from the bus, page 3).

MODDMX

ModDMX module allows to handle, through the Contatto bus, up to 32 DMX devices. ModDMX module makes possible the communication on the first 64 of 512 DMX channels allowed by this protocol.

It uses 1 output address, 1-channel 16-bit.

ID Value R/W Description
o<address>.<DMX address> 0...100 RW Values and commands are described in the MODDMX Programming Handbook

MODDALI

The ModDALI module supports 4 DALI lines, with up to 32 devices for each line. The ModDALI module with firmware version 6.x supports 2 DALI lines (channels 1 and 2), with up to 64 devices for each line.

It uses 1 output address and, if enabled, 1 input address with the same value.

ID Value R/W Description
o<address>.<line> refresh RW update the state of the DALI devices
o<address>.<line>
o<address>.<line>.all
o<address>.<line>.0
off RW switch off all available DALI devices
<level> RW set a level for all available devices
o<address>.<line>.group.<DALI group> off RW switch off all DALI devices on that group
<level> RW set a level for all DALI devices in that group
o<address>.<line>.<DALI address> off RW switch off a single DALI device
<level> RW set a level for a single DALI device
fault R DALI device fault
unknown R DALI device unknown state (or connection lost)
>100 RW special functions: possible values are described in the MODDALI Programming Handbook
i<address>.<line>.polling off R polling disabled
on R polling enabled
i<address>.<line>.test 0 R test button not pressed
1 R test button pressed
i<address>.<line>.dali nopower R DALI bus power supply failure
open R DALI line broken
short R DALI line short circuit
on R on DALI line
i<address>.<line>.1 off R ballast 1 off
<level> R ballast 1 level
fault R ballast 1 lamp failure
unknown R ballast 1 lamp unknown state (or connection lost)

The DALI device level can be set using additional formats besides the standard percent values:

  • absolute positive integer number between 0 and 100
  • percent number, formatted as x%
  • fractional format, formatted as “x/y”, where 0 <= x <= y
  • values in the range 101÷255. Values and commands are described in the MODDALI Programming Handbook.

MODDALI8

The ModDALI8 module allows the management of 8 DALI lines, with up to 16 devices for each line (or channel).

It uses 2 consecutive input addresses and 1 input address with the same base value.

ID Value R/W Description
o<address>.<line> off RW off broadcast command
<level> RW level broadcast command
i<address>.<line>.polling off RW polling disabled
on RW polling enabled
i<address>.<line>.test 0 RW test button not pressed
1 RW test button pressed
i<address>.<line>.dali fault RW lamp failure
open RW no DALI device connected to this line
short RW DALI line short circuit
on RW DALI line working correctly

<line> can be set from 1 to 8 to address a single line, or 0 to send commands to all DALI lines.


The line level can be set using additional formats besides the standard percent values:

  • absolute positive integer number between 0 and 100
  • percent number, formatted as x%
  • fractional format, formatted as “x/y”, where 0 <= x <= y
  • values in the range 101÷255. Values and commands are described in the MODDALI8 Programming Handbook.

CLIMA2

Module for the regulation of the ambient temperature.

It uses 1 input and 1 output address that are equal each one to the other, so only a base address is needed.

ID Value R/W Description
i<address> on R zone on
off R zone off
i<address>.mode summer R summer mode
winter R winter mode
i<address>.status off R off status
heating R heating request
cooling R cooling request
i<address>.fan off R fan off
min R min speed
med R med speed
max R max speed
i<address>.temp fault R NTC probe fault
<temp> R ambient temperature value, in C/10
i<address>.setpoint.temp <temp> R real setpoint value, in C/10
i<address>.knob 0 ... 1000 R position of rotary knob
o<address>.mode summer RW set summer
winter RW set winter
o<address> on RW zone on
off RW zone off
o<address>.setpoint.temp 0...400 RW set and read the value of central setpoint (temp in C/10)
o<address>.setpoint.delta.neg <temp> RW set and read the MAX negative delta
o<address>.setpoint.delta.pos <temp> RW set and read the MAX positive delta
o<address>.led.1 red
r
RW LED 1 red
green
g
RW LED 1 green
yellow
y
RW LED 1 yellow
off RW set off
o<address>.led.2 red
r
RW LED 2 red
green
g
RW LED 2 green
yellow
y
RW LED 2 yellow
off RW set off
o<address>.led.3 red
r
RW LED 3 red
green
g
RW LED 3 green
yellow
y
RW LED 3 yellow
off RW set off
o<address>.led.4 red
r
RW LED 4 red
green
g
RW LED 4 green
yellow
y
RW LED 4 yellow
off RW set off

You can also set the value to “on” or “off”, that is equivalent to 1 and 0.


MODANA

Network analyzer module for Contatto bus.

It uses, in dynamic mode, up to a maximum of 5 consecutive input addresses and, if enabled, 1 output address equal to the base address.

The module's firmware should be version 1.5 or later to support negative values for active power readings.


Note The module must be configured with the same base address for input and output.

For example:

(I7, O7)
ID Value R/W Description
i<address>.v12 [V] R chained voltage phase 1-2
i<address>.v23 [V] R chained voltage phase 2-3
i<address>.v31 [V] R chained voltage phase 3-1
i<address>.vtm [V] R average chained voltage
i<address>.i1 [A] R current phase 1
i<address>.i2 [A] R current phase 2
i<address>.i3 [A] R current phase 3
i<address>.itm [A] R average current
i<address>.ptot [W] R total active power
i<address>.ptotk [kW] R total active power
i<address>.qtot [W] R total reactive power
i<address>.qtotk [kW] R total reactive power
i<address>.pf [pf] R total power factor
i<address>.frequency [Hz] R frequency
i<address>.v1n [V] R voltage phase 1
i<address>.v2n [V] R voltage phase 2
i<address>.v3n [V] R voltage phase 3
i<address>.p1 [W] R active power phase 1
i<address>.p1k [kW] R active power phase 1
i<address>.p2 [W] R active power phase 2
i<address>.p2k [kW] R active power phase 2
i<address>.p3 [W] R active power phase 3
i<address>.p3k [kW] R active power phase 3
i<address>.q1 [W] R reactive power phase 1
i<address>.q1k [kW] R reactive power phase 1
i<address>.q2 [W] R reactive power phase 2
i<address>.q2k [kW] R reactive power phase 2
i<address>.q3 [W] R reactive power phase 3
i<address>.q3k [kW] R reactive power phase 3
i<address>.pf1 [pf] R power factor phase 1
i<address>.pf2 [pf] R power factor phase 2
i<address>.pf3 [pf] R power factor phase 3
i<address>.s1 [VA] R apparent power phase 1
i<address>.s1k [kVA] R apparent power phase 1
i<address>.s2 [VA] R apparent power phase 2
i<address>.s2k [kVA] R apparent power phase 2
i<address>.s3 [VA] R apparent power phase 3
i<address>.s3k [kVA] R apparent power phase 3
i<address>.stot [VA] R total apparent power
i<address>.hours [hours] R hour-meter
i<address>.temperature [°C] R cabinet temperature
i<address>.energy.active [KWh] R positive active energy
i<address>.energy.activeneg [KWh] R negative active energy
i<address>.energy.reactive [KVARh] R positive reactive energy
i<address>.energy.reactiveneg [KVARh] R negative reactive energy
i<address>.pm [W] R average positive active power
i<address>.qm [VAR] R average positive reactive power
o<address>.reset.energy 1 RW reset energies
0 RW ---
o<address>.reset.hours 1 RW reset hour-meter
0 RW ---

MODANAM

Network analyzer module for Contatto bus.

It uses, in dynamic mode, up to a maximum of 5 consecutive input addresses and, if enabled, 1 output address equal to the base address.

Note The module must be configured with the same base address for input and output.

For example:

(I7, O7)
ID Value R/W Description
i<address>.v12 [V] R chained voltage phase 1-2
i<address>.v23 [V] R chained voltage phase 2-3
i<address>.v31 [V] R chained voltage phase 3-1
i<address>.vtm [V] R average chained voltage
i<address>.i1 [A] R current phase 1
i<address>.i2 [A] R current phase 2
i<address>.i3 [A] R current phase 3
i<address>.itm [A] R average current
i<address>.ptot [W] R total active power
i<address>.ptotk [kW] R total active power
i<address>.qtot [W] R total reactive power
i<address>.qtotk [kW] R total reactive power
i<address>.pf [pf] R total power factor
i<address>.frequency [Hz] R frequency
i<address>.v1n [V] R voltage phase 1
i<address>.v2n [V] R voltage phase 2
i<address>.v3n [V] R voltage phase 3
i<address>.p1 [W] R active power phase 1
i<address>.p1k [kW] R active power phase 1
i<address>.p2 [W] R active power phase 2
i<address>.p2k [kW] R active power phase 2
i<address>.p3 [W] R active power phase 3
i<address>.p3k [kW] R active power phase 3
i<address>.q1 [W] R reactive power phase 1
i<address>.q1k [kW] R reactive power phase 1
i<address>.q2 [W] R reactive power phase 2
i<address>.q2k [kW] R reactive power phase 2
i<address>.q3 [W] R reactive power phase 3
i<address>.q3k [kW] R reactive power phase 3
i<address>.pf1 [pf] R power factor phase 1
i<address>.pf2 [pf] R power factor phase 2
i<address>.pf3 [pf] R power factor phase 3
i<address>.s1 [VA] R apparent power phase 1
i<address>.s1k [kVA] R apparent power phase 1
i<address>.s2 [VA] R apparent power phase 2
i<address>.s2k [kVA] R apparent power phase 2
i<address>.s3 [VA] R apparent power phase 3
i<address>.s3k [kVA] R apparent power phase 3
i<address>.stot [VA] R total apparent power
i<address>.hours [hours] R hour-meter
i<address>.temperature [°C] R cabinet temperature
i<address>.energy.active [KWh] R positive active energy
i<address>.energy.activeneg [KWh] R negative active energy
i<address>.energy.reactive [KVARh] R positive reactive energy
i<address>.energy.reactiveneg [KVARh] R negative reactive energy
o<address>.reset.energy 1 RW reset energies
0 RW ---
o<address>.reset.hours 1 RW reset hour-meter
0 RW ---

MODPQ5

Q5 tags proximity reader and programmer module.

Uses 1 input address on the Contatto bus. Write operations are performed through direct writes to the module’s RAM.

ID Value R/W Description
i<address>.data 0
<tag data>
R 30 characters hexadecimal representation of the 15 bytes of tag data; “0” if the module is not seeing any tag
i<address>.data.write 0 R the tag has been removed from the programmer after writing, or the module is not seeing any tag
1 R the tag write operation was successful
i<address>.reader.error 0 R reader/writer normal status
1 R reader/writer module error (normally occurs when the reader is not connected to the MODPQ5 module)
i<address>.tag.error 0 R the tag is valid
1 R the tag is not valid
i<address>.request.error 0 R no request or handshake errors detected
1 R handshake error
i<address>.data.error 0 R tag data ok
1 R tag data errors detected
i<address>.unknown.error 0 R no unknown errors
1 R unknown error detected
i<address>.write <tag data> R tag data write successful
error R tag data write error
o<address>.write <tag data> W 30 characters hexadecimal representation of the 15 bytes data to be written on the tag

MODHT

MODHT is the hotel room controller module.

It uses 1 input and 1 output address.

Tags configuration data are written to the module’s EEPROM (persistent internal memory).

ID Value R/W Description
i<address>.door 0 R door closed
1 R door open
i<address>.window 0 R window closed
1 R window open
i<address>.panic 0 R panic request not active
1 R panic request
i<address>.busy 0 R room is free
1 R room is occupied
i<address>.1 0 R input pin 1 off
1 R input pin 1 on
i<address>.2 0 R input pin 2 off
1 R input pin 2 on
i<address>.ev 0 R EV output off
1 R EV output on
i<address>.aux 0 R AUX output off
1 R AUX output on
i<address>.dnd 0 R do not disturb not active
1 R do not disturb
i<address>.service 0 R room service request not active
1 R room service request
i<address>.booked 0 R room is not booked
1 R room is booked
i<address>.mode summer R summer mode
winter R winter mode
i<address>.fan off R fan set to off
auto R fan speed set to auto
min R fan speed set to minimum
med R fan speed set to medium
max R fan speed set to max
i<address>.fan.status 0 R fan is off
1 R fan is on (cooling or heating)
i<address>.temp <temp> R ambient temperature value (in C/10)
i<address>.setpoint.temp <temp> R setpoint value (in C/10)
i<address>.tag.door 1...5 R type of tag that is opening the door (1 to 4 are service tags; 5 is a customer tag). After 5 seconds the value is reset to 0
i<address>.tag.room 0 R no tag present in room’s reader
1...5 R type of tag inserted in the room’s reader (1 to 4 are service tags; 5 is a customer tag)
i<address>.tag.<n> <tag data> R 24 characters hexadecimal representation of the 12 bytes data matching service N tags (N from 1 to 5) stored in module’s EEPROM. Updated on o<address>.tag.<n>=read command
i<address>.pcam.error 0 R PCAM module ok
1 R PCAM module error
i<address>.tpr.error 0 R TPR/H module ok
1 R TPR/H module error
i<address>.mask <mask data> R 24 characters hexadecimal representation of the 12 bytes tag mask stored in module’s EEPROM. Updated on o<address>.mask=read command
i<address>.data.door 0
<tag data>
R 30 characters hexadecimal representation of the 15 bytes of tag data being read from the door reader; “0” if the module is not seeing any tag (this data point is available with MODHT firmware 5.3 or newer)
i<address>.data.room 0
<tag data>
R 30 characters hexadecimal representation of the 15 bytes of tag data being read from the room reader; “0” if the module is not seeing any tag (this data point is available with MODHT firmware 5.3 or newer)
i<address>.setpoint.summer.<n>
i<address>.setpoint.winter.<n>
<temp> R winter/summer setpoint <n> (1...3) current value (in C/10). Updated on o<address>.setpoint.summer.<n>=read and o<address>.setpoint.winter.<n>=read commands
i<address>.setpoint.delta.summer.low
i<address>.setpoint.delta.summer.high
i<address>.setpoint.delta.winter.low
i<address>.setpoint.delta.winter.high
<temp delta limit>
1...9
R the current temperature setpoint low/high limits for winter and summer modes (in C). Updated on o<address>.setpoint.delta=read command
o<address>.tag.<n> <tag data> R tag data write successful
error R tag data write error
o<address>.mask <mask data> R mask data write successful
error R mask data write error
o<address>.setpoint.summer.<n>
o<address>.setpoint.winter.<n>
<temp> R winter/summer setpoint N (1-3) write successful (in C/10)
error R setpoint write error
o<address>.setpoint.delta.summer.low
o<address>.setpoint.delta.summer.high
o<address>.setpoint.delta.winter.low
o<address>.setpoint.delta.winter.high
<temp delta limit>
1...9
R setpoint min/max limit for winter/summer write successful (in C)
error R setpoint limit write error
o<address>.ev.enable 0 W EV output disabled
1 W EV output enabled
o<address>.aux.enable 0 W AUX output disabled
1 W AUX output enabled
o<address>.panic.reset 1 W panic request reset
o<address>.busy 0 W set room status to free
1 W set room status to occupied
o<address>.ev 0 W EV output off
1 W EV output on
o<address>.aux 0 W AUX output off
1 W AUX output on
o<address>.dnd.reset 1 W do not disturb reset
o<address>.service.reset 1 W do not disturb reset
o<address>.booked 0 W set room as not booked
1 W set room as booked
o<address>.mode summer W set room to summer mode
winter W set room to winter mode
o<address>.fan off W set fan off
auto W set fan to auto mode
o<address>.comfort 0 W force comfort set-point off
1 W force comfort set-point on
o<address>.3 0 W output pin 3 off
1 W output pin 3 on
o<address>.fan.heating.min 0 W reset heating speed limit
1 W limit heating speed to min
o<address>.fan.cooling.min 0 W reset cooling speed limit
1 W limit cooling speed to min
o<address>.tag.<n> read W read the 12 bytes stored in module’s EEPROM for service N tags (<n> from 1 to 5)
<tag data> W 24 characters hexadecimal representation of the 12 bytes data matching service N tags (N from 1 to 5), to be stored in module’s EEPROM. After writing data, you should wait approximately 150ms before sending a read command
o<address>.mask read W read the 12 bytes mask stored in module’s EEPROM
<mask data> W 24 characters hexadecimal representation of the 12 bytes tag mask, to be stored in module’s EEPROM. After writing data, you should wait approximately 150ms before sending a read command
o<address>.setpoint.summer.<n>
o<address>.setpoint.winter.<n>
read W read winter/summer setpoint <n> (1-3)
<temp> W set winter/summer setpoint <n> (1-3)
o<address>.setpoint.delta read W read winter and summer, low and high setpoint limits
o<address>.setpoint.delta.summer.low
o<address>.setpoint.delta.summer.high
o<address>.setpoint.delta.winter.low
o<address>.setpoint.delta.winter.high
<temp delta limit> W set winter/summer, low/high setpoint limit (in C)

MODCA

MODCA is the access control module.

It uses 1 input and 1 output address.

Tags configuration data are written to the module’s EEPROM (persistent external memory).

Site codes and the tags mask are written to the internal EEPROM.

ID Value R/W Description
i<address>.1 0 R input pin 1 off
1 R input pin 1 on
i<address>.2 0 R input pin 2 off
1 R input pin 2 on
i<address>.blocked 0 R access control enabled
1 R access blocked
i<address>.tpr.error 0 R TPR module ok
1 R TPR module error
i<address>.access.granted.1 0 R no tag present at antenna 1
1 R access granted to tag at antenna 1
i<address>.access.granted.2 0 R no tag present at antenna 2
1 R access granted to tag at antenna 2
i<address>.access.denied 0 R access denied flags reset
site R access denied due to site code error
code R access denied due to user code error
total.limit R access denied due to exceeded total number of access grants
daily.limit R access denied due to exceeded daily number of access grants
time R access denied due to time range violation
day R access denied due to weekday violation
expired R access denied due expired tag
i<address>.denied.code <tag code> R the tag code (decimal value of selected two bytes of the tag data) that was denied access
i<address>.granted.1.code <tag code> R the tag code (decimal value of selected two bytes of the tag data) that was granted access at antenna 1
i<address>.granted.2.code <tag code> R the tag code (decimal value of selected two bytes of the tag data) that was granted access at antenna 2
i<address>.site.<n> <site data> R 16 characters hexadecimal representation of the 8 bytes data representing the Nth site code (N from 1 to 4) stored in module’s EEPROM
i<address>.mask <mask data> R 16 characters hexadecimal representation of the 8 bytes site code mask stored in module’s EEPROM
i<address>.mask <mask data> R 16 characters hexadecimal representation of the 8 bytes site code mask stored in module’s EEPROM
i<address>.user.<n> <user data> R 32 characters hexadecimal representation of the 16 bytes data for user <n> (N from 1 to 2000) stored in module’s EEPROM
o<address>.site.<n> <site data> R site data write successful
error R site data write error
o<address>.mask <mask data> R mask data write successful
error R mask data write error
o<address>.user.<n> <user data> R user data write successful
error R user data write error
o<address>.relay 0 W relay output off
1 W relay output pulse on, with pulse length according to the MODCA configuration (with firmware versions before 1.3 this data point remains at 1 and should be reset to 0 with an explicit command; with firmware 1.3 the data point value follows the relay state, and is automatically reset to 0 at the end of the pulse period)
o<address>.relay.forced 0 W forced relay mode not set (default behaviour)
1 W forced relay mode set: the relay remains closed until the relay.forced command is reset (available with MODCA firmware version 2.0 or later)
o<address>.block 0 W enable access control
1 W block access control
o<address>.access.granted.code 0 W reset
1 W allow access even when site code is not valid
o<address>.access.granted.total.limit 0 W reset
1 W allow access even when the total limit of access grants has been exceeded
o<address>.access.granted.daily.limit 0 W reset
1 W allow access even when the daily limit of access grants has been exceeded
o<address>.access.granted.time 0 W reset
1 W allow access even outside of the allowed timeframe
o<address>.access.granted.day 0 W reset
1 W allow access even outside of the allowed weekdays
o<address>.access.granted.expired 0 W reset
1 W allow access even when the tag is expired
o<address>.site.<n> read W read the 8 bytes stored in module’s EEPROM for site N code (<n> from 1 to 4)
<site data> W 16 characters hexadecimal representation of the 8 bytes data of site N code (N from 1 to 4), to be stored in module’s EEPROM. After writing data, you should wait approximately 100ms before sending a read command
o<address>.mask read W read the 8 bytes mask stored in module’s EEPROM
<mask data> W 16 characters hexadecimal representation of the 8 bytes site code mask, to be stored in module’s EEPROM. After writing data, you should wait approximately 100ms before sending a read command
o<address>.user.<n> read W read the 16 bytes stored in module’s EEPROM for user N (<n> from 1 to 2000)
<user data> W 16 characters hexadecimal representation of the first 8 bytes of access control data for user N (N from 1 to 2000) , to be stored in module’s EEPROM
<reset> W reset to 0 the total and daily counters for user <n>
o<address>.users erase W deletes all users data. This action requires up to about 27 seconds to be completed. It also deletes all i<address>.user.<n> and o<address>.user.<n> data points

MODKB

MODKB is the keypad access control module.

It uses 1 input and 1 output address.

PIN configuration data are written to the module’s EEPROM (persistent memory).

ID Value R/W Description
i<address>.1 0 R input pin 1 off
1 R input pin 1 on
i<address>.2 0 R input pin 2 off
1 R input pin 2 on
i<address>.access.granted.<n> 0 R reset
1 R access granted to PIN <n> (<n> from 1 to 30)
i<address>.pin <pin code> R the last pin code entered on the keypad (from 1 to 65535). Reset to 0 after programmed code persistence time
i<address>.access.granted.<n> 0 R access denied flags reset
site R access denied due to site code error
code R access denied due to user code error
time R access denied due to time range violation
day R access denied due to weekday violation
i<address>.pin.<n> <pin data> R 16 characters hexadecimal representation of the 8 bytes data for PIN <n> (<n> from 1 to 30) stored in module’s EEPROM
o<address>.pin.<n> <pin data> R pin data write successful
error R pin data write error
o<address>.relay 0 W relay output off
1 W relay output on (pulse output, resets to 0 immediately after the relay is closed, usually before the relay closure time)
o<address>.lock.all 0 W reset
1 W disables access to all PINs
o<address>.lock.<n> 0 W reset
1 W disables access to PIN <n> (<n> from 1 to 30)
o<address>.pin.<n> read W read the 8 bytes stored in module’s EEPROM for PIN <n> (<n> from 1 to 30)
<pin data> W 16 characters hexadecimal representation of the 8 bytes data for PIN <n> (<n> from 1 to 30), to be stored in module’s EEPROM

MODDI

500W IGBT dimmer module.

It uses 1 output address.

ID Value R/W Description
o<address> 0...100 RW brightness level according to current ramp
off RW dimmer off
101...173 W command (see MODDI commands table)
o<address>.noline 0 R AC line detected
1 R AC line fault
o<address>.overcurrent 0 R normal
1 R overcurrent protection
o<address>.overvoltage 0 R normal
1 R overvoltage protection
o<address>.overtemperature 0 R normal
1 R overtemperature protection

The dimmer level can be set using additional formats besides the standard percent values:

  • absolute positive integer number between 0 and 100
  • percent number, formatted as x%
  • fractional format, formatted as “n/m”, where 0 <= n <= m.

MODCL

Temperature control module.

It uses 1 input and one output address.

ID Value R/W Description
i<address> on R zone on
off R zone off
i<address>.mode winter R winter mode
summer R summer mode
i<address>.fan min R min fan speed
med R medium fan speed
max R max fan speed
off R fan off
i<address>.fan.mode man R manual fan mode
auto R auto fan mode
i<address>.setpoint 1 R setpoint 1
2 R setpoint 2
3 R setpoint 3
off R off
man R manual setpoint
i<address>.setpoint.mode man R manual setpoint mode
auto R auto setpoint mode
i<address>.temp <temp> R temperature value (in C/10)
fault R temperature sensor fault
i<address>.status off R off
cooling R cooling status mode
heating R heating status mode
o<address> on RW zone on (writing on to this datapoint doesn't turn the zone on, it simply resets the off command)
off RW zone off
o<address>.mode winter RW winter mode
summer RW summer mode
o<address>.setpoint.mode man RW manual mode
auto RW auto mode
off RW zone off
o<address>.setpoint 1 RW setpoint 1
2 RW setpoint 2
3 RW setpoint 3
0 RW setpoint off
man RW manual setpoint
o<address>.setpoint.temp.1 <temp> RW temperature setpoint 1 value (in C/10)
o<address>.setpoint.temp.2 <temp> RW temperature setpoint 2 value (in C/10)
o<address>.setpoint.temp.3 <temp> RW temperature setpoint 3 value (in C/10)
o<address>.setpoint.temp.man <temp> RW temperature manual setpoint value (in C/10)

MOD4TP/I

8 digital input and 4 roller shutters or blinds with detection of travel time.


ID Value R/W Description
i<address>.<N> 0 R input pin N off
1 R input pin N on
o<address>.<N> up RW shutter N up command
down RW shutter N down command
stop W shutter N stop command
off
up1 W shutter N up one step command
down1 W shutter N down one step command
unknown R shutter N unknown state
offup R shutter N off, up position
offdown R shutter N off, down position
0-100 R shutter N current position
o<address>.calibration.<N> 0 R shutter N normal operations
1 RW shutter N calibration command
o<address>.position.<N> 0-100 RW shutter N position command
o<address>.slats.<N> 0-100 W shutter N slats position command (no feedback available)

MODRHT

Temperature, relative humidity and dew point sensor.

It uses one input address and, if enabled by the configuration panel of MCP IDE, one output address.

ID Value R/W Description
i<address>.temp <temp> R temperature value (in C/10)
i<address>.rh <%RH> R relative humidity percentage (0-100)
i<address>.dewpoint <temp> R dew point (in C/10)
i<address>.dewpoint.1 0 R dew point lower than dew point threshold 1
1 R dew point equal or greater than dew point threshold 1
i<address>.dewpoint.2 0 R dew point lower than dew point threshold 2
1 R dew point equal or greater than dew point threshold 2
o<address>.dewpoint.1 <temp> RW dew point threshold 1 (in C/10)
o<address>.dewpoint.2 <temp> RW dew point threshold 2 (in C/10)

MODAM2

Multi-function, 2 inputs analog module.

Uses one input address.

ID Value R/W Description
i<address>.1 <value> R input 1 value (-32768 to +32767)
i<address>.2 <value> R input 2 value (-32768 to +32767)

MODIGLASS and MODIGLASS3

MODIGLASS is an input/output module with 6 touch buttons with addressable LEDs and a buzzer for audio feedback.

It uses 1 input and 1 output address.

ID Value R/W Description
i<address>.1 0 R button 1 off
1 R button 1 on
i<address>.2 0 R button 2 off
1 R button 2 on
i<address>.3 0 R button 3 off
1 R button 3 on
i<address>.4 0 R button 4 off
1 R button 4 on
i<address>.5 0 R button 5 off
1 R button 5 on
i<address>.6 0 R button 6 off
1 R button 6 on
i<address>.led.1 0 R led 1 off
1 R led 1 on
i<address>.led.2 0 R led 2 off
1 R led 2 on
i<address>.led.3 0 R led 3 off
1 R led 3 on
i<address>.led.4 0 R led 4 off
1 R led 4 on
i<address>.led.5 0 R led 5 off
1 R led 5 on
i<address>.led.6 0 R led 6 off
1 R led 6 on
i<address>.proximity 0 R no proximity detected
1 R proximity detected
o<address>.led.1 0 W led 1 off
1 W led 1 on
o<address>.led.2 0 W led 2 off
1 W led 2 on
o<address>.led.3 0 W led 3 off
1 W led 3 on
o<address>.led.4 0 W led 4 off
1 W led 4 on
o<address>.led.5 0 W led 5 off
1 W led 5 on
o<address>.led.6 0 W led 6 off
1 W led 6 on
o<address>.disable 0 RW not disabled (normal mode)
1 RW disabled (cleaning mode)
o<address>.dim 0 RW high intensity backlight
1 RW low intensity backlight
o<address>.proximity 0 RW disable proximity backlight
1 RW enable proximity backlight
o<address>.backlight 0 RW backlight off
1 RW backlight on
o<address>.buzzer 0 RW buzzer disabled
1 RW buzzer enabled

You can also set the value to “on” or “off”, that is equivalent to 1 and 0.


User Interface

All CONTATTO devices data points that have been defined in the systemtopo.txt database are automatically listed in the Project Editor. Adding a button to control a device output point requires just a few clicks and no additional EVENTS logic.


IO Servers Contatto Project Editor.png


Besides the direct association of control buttons and data points, the CONTATTO driver also automatically updates graphical objects that represent values or states of complex devices, like the CLIMA2 temperature control unit. It will also automatically intercept buttons to manually set operation modes and temperature set-points.


CLIMA2

You can use the temp and tempmini objects to control CLIMA2 devices.


UI Object clima2.png


The fan button, in the bottom right-hand corner, is not enabled because the manual control of the fan speed is not available. The M button, in the top right-hand corner, allows to switch the module on or off.

You can also easily create customized controls for the CLIMA2, using standard graphic objects that are automatically set to show the device’s status and intercepted to send user commands.

UISET Actions

ID Attribute Set to Description
<address>.mode value SUMMER summer mode (cooling)
value WINTER winter mode (heating)
<address>.mode.label.summer visible true if CLIMA2 is in summer mode
<address>.mode.label.winter visible true if CLIMA2 is in winter mode
<address>.status value OFF zone off
value ON zone on
<address>.status.label.off visible true if the zone is not cooling or heating
<address>.status.label.cooling visible true if the zone is cooling
<address>.status.label.heating visible true if the zone is heating
<address>.fan value OFF fan off
value MIN minimum fan speed
value MED medium fan speed
value MAX maximum fan speed
<address>.fan.label.min visible true minimum fan speed
<address>.fan.label.med visible true medium fan speed
<address>.fan.label.max visible true maximum fan speed
<address>.setpoint.label.on visible true zone is on
<address>.setpoint.label.off visible true zone is off
<address>.setpoint.mode value ON zone is on
value OFF zone is off
<address>.setpoint.temp value <value> the active setpoint temperature, in Celsius degrees with one decimal digit, followed by " °C"
<address>.temp value <temp> the measured temperature, in Celsius degrees with one decimal digit, followed by " °C"
FAULT fault/error condition

USER Commands

Name Param Action
<address> on module on
off module off
mode.summer set summer mode (cooling)
mode.winter set winter mode (heating)
<address>.setpoint temp.up increase setpoint temperature in 0.5C steps
temp.down decrease setpoint temperature in 0.5C steps
0...400 set the setpoint to the defined value (in C/10)
mode cycle through on and off modes
mode.on module on
mode.off module off



MODCL

You can use the temp and tempmini objects to control MODCL devices.


The fan button, in the bottom right-hand corner, is not enabled because the manual control of the fan speed is not available. The M button, in the top right-hand corner, allows to switch the module to auto or manual mode, or off.

You can also easily create customized controls for the MODCL, using standard graphic objects that are automatically set to show the device’s status and intercepted to send user commands.

UISET Actions

ID Attribute Set to Description
<address>.mode value SUMMER summer mode (cooling)
WINTER winter mode (heating)
<address>.mode.label.summer visible true if MODCL is in summer mode
<address>.mode.label.winter visible true if MODCL is in winter mode
<address>.status value OFF zone off
ON zone on
<address>.status.label.off visible true if the zone is not cooling or heating
<address>.status.label.cooling visible true if the zone is cooling
<address>.status.label.heating visible true if the zone is heating
<address>.fan value OFF fan off
MIN minimum fan speed
MED medium fan speed
MAX maximum fan speed
<address>.fan.label.min visible true minimum fan speed
<address>.fan.label.med visible true medium fan speed
<address>.fan.label.max visible true maximum fan speed
<address>.setpoint value 1, 2, 3 setpoint N is active
MAN manual setpoint is active
OFF zone is off
<address>.setpoint.label.1 visible true setpoint 1 is active
<address>.setpoint.label.2 visible true setpoint 3 is active
<address>.setpoint.label.3 visible true setpoint 3 is active
<address>.setpoint.label.man visible true manual setpoint is active
<address>.setpoint.label.off visible true zone is off
<address>.setpoint.mode value AUTO automatic mode
MAN manual mode
OFF zone is off
<address>.setpoint.temp value <value> the active setpoint temperature, in Celsius degrees with one decimal digit, followed by " °C"
<address>.temp value <temp> the measured temperature, in Celsius degrees with one decimal digit, followed by " °C"
FAULT fault/error condition

USER Commands

Name Param Action
<address> mode cycle summer/winter modes
<address>.mode mode.summer set summer mode (cooling)
mode.winter set winter mode (heating)
<address>.setpoint.temp up increase current setpoint temperature in 0.5C steps
down decrease current setpoint temperature in 0.5C steps
<address>.setpoint.temp.N up increase setpoint N temperature in 0.5C steps
down decrease setpoint N temperature in 0.5C steps
0...400 set setpoint N to the given value (in C/10)
<address>.setpoint.temp.man up increase manual setpoint temperature in 0.5C steps
down decrease manual setpoint temperature in 0.5C steps
0...400 set manual setpoint to the given value (in C/10)
<address>.setpoint mode cycle through auto, manual and off modes
<address>.setpoint.mode auto set auto mode
man set manual mode
off zone off

MOD4TP/I

Using slider objects for MOD4TP/I shutter's position

You can use the slider objects, sliderv and sliderh, to display and control the position. Set both the slider's ID and address to <server_name>.<address>.<N>, with N from 1 to 4.

Note Note that you can set the inverse attribute of the sliderv object to true, in order to have the cursor at the top instead of bottom of the slider when the position is 0.

Release Notes

3.7.0

  • support of MODRHT
  • support of MODAM2
  • support of MODIGLASS, MODIGLASS3
  • support of MODLC firmware version 3.2
  • support of MODDALI firmware version 6.x
  • support of MCP counters
  • bus and modules fault detection
  • fixes to the MODDALI ballast 1 status data point

3.6.0

  • added support for MOD32IL
  • added support for MOD4TP/I
  • added support for MODDALI8
  • added support for MODANAM
  • fixed a bug that could cause erroneous readings of MODANA's ptotk datapoint when total active power is negative

3.5.1

  • MODANA updated to support negative active energy values (fw. 1.5 or later)

3.5.0

  • added support for MCP4
  • added support for MODCA firmware version 2.0, with new "relay.forced" datapoint
  • added support for MOD32IN
  • MODPQ5 is now identified with its unique ID. Use MCPIDE 3.2.3 or later to program the MCPXT/MCP4 to allow HSYCO to correctly identify this module

3.4.0

  • improved communication error logging
  • improved support of tools remote access
  • events generated during startup if startupevents=true are now executed sequentially
  • support for MODDI
  • support for MODCL

3.2.2

bug fixes:

  • the toolspassword optional parameter was incorrectly converted to lower case
  • fixed a bug that prevented reading the last 3 addresses of MOAN/I4 and MI420-X4 modules

3.2.1

  • added support for MODHT set-point delta limits read and write
  • the lux datapoint name was incorrectly set to ID.i<addr>.1 instead of ID.i<addr>.lux

3.2.0

  • support for MODCA, MODHT, MODKB, MODPQ5
  • new "detectevents" option, generates forced events when a device is detected at start-up
  • support for the toolspassword option, to allow MCP-IDE and other tools secure remote access to the MCP via HSYCO
  • new clock datapoint to read the MXP-XT internal clock and set it to HSYCO's time

3.0.3

  • optimized performance of MCP’s registers status polling
  • the server failed to initialized when an unsupported device was configured in the MCP

3.0.1

  • you can now limit the number of virtual points and registers read and written by HSYCO, and have access to all of the 1024 registers; defaults are unchanged

3.0.0

  • initial release


HSYCO and Home Systems Consulting are registered trademarks of Home Systems Consulting SpA. Java and JavaScript are registered trademarks of Oracle and/or its affiliates. CONTATTO and DUEMMEGI are registered trademarks of DUEMMEGI SRL. Other products or company names can be trademarks or registered trademarks of other companies and are used for demonstrative purposes only, with no violation intent.