Kilsen
KILSEN KFP-A are multi-area fire panels. The integration with HSYCO can be accomplished via a standard Modbus TCP/IP connection. This I/O server was developed following the MODBUS documentation P/N 00-3243-505-1603-01 • ISS 14DEC15
Contents
Communication
KILSEN panels can be connected via ethernet. A valid IP address must be assigned to the panel. MODBUS PROTOCOL must be enabled. Please refer to the manual for detailed instruction about MODBUS protocol configuration.
HSYCO Configuration
Add a KILSEN I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- Address: IP address of the KILSEN panel
- Port: TCP/IP port for MODBUS communication (default 502)
High Availability
- Shutdown when inactive: defaults to false.
Options
ID | Default | Values | Description |
---|---|---|---|
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
unitid | 1 | > 0 | MODBUS unit ID of the KILSEN panel |
nodes | 1 | nodes list. Multiple nodes should be separated by semicolons | |
loopsnumber | 1 | > 0 | total number of loops |
sensorsnsumber | 1 | 0 ... 128 | set to the highest sensor number configured in the panel |
modulesnumber | 1 | 0 ... 128 | set to the highest module number configured in the panel |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
reset | 1 | W | panel reset |
reset | 1 | W | panel reset |
panel.silence | 1 | W | silence panel |
sounders.set | 0 | W | stop sounders |
1 | W | start sounders | |
global.alarm | 0 | R | no alarm |
1 | R | at lest one sensor of module on alarm | |
global.fault | 0 | R | no faults |
1 | R | at lest one sensor of module on fault status | |
global.disable | 0 | R | no sensors of modules disabled |
1 | R | at lest one sensor of module is disabled | |
global.test | 0 | R | panel in not in test mode |
1 | R | panel is in test mode | |
global.daynight | 0 | R | panel in day mode |
1 | R | panel is night mode | |
global.mcpalarm | 0 | R | mcp alarm off |
1 | R | mcp alarm on | |
global.sounder.delay.enabled | 0 | R | sounders delay disabled |
1 | R | sounders delay enabled | |
global.sounder.delay.in.progress | 0 | R | sounders delay not in progress |
1 | R | sounders delay in progress | |
global.sounder.outputs.activated | 0 | R | sounders outputs not active |
1 | R | sounders outputs active | |
global.sounder.outputs.silenced | 0 | R | sounders outputs not silenced |
1 | R | sounders outputs silenced | |
global.sounder.disabled | 0 | R | sounders are enabled |
1 | R | sounders are disabled | |
global.sounder.override.time.elapsed | 0 | R | override sounders time is not elapsed |
1 | R | ovveride sounders time elapsed | |
global.sounder.in.test | 0 | R | sounders not in test |
1 | R | sounders in test | |
global.fire.routing.delay.enabled | 0 | R | fire routing delay not enabled |
1 | R | fire routing delay enabled | |
global.fire.routing.delay.in.progress | 0 | R | fire routing delay not in progress |
1 | R | fire routing in progress | |
global.fire.routing.ouputs.activated | 0 | R | fire routing outputs not activated |
1 | R | fire routing outputs activated | |
global.fire.routing.ack | 0 | R | fire routing not in ack |
1 | R | fire routing ack | |
global.fire.routing.disabled | 0 | R | fire routing enabled |
1 | R | fire routing disabled | |
global.fire.routing.test.on | 0 | R | fire routing test is off |
1 | R | fire routing test on | |
global.fire.routing.ext.delay.in.progress | 0 | R | fire routing ext delay not in progress |
1 | R | fire routing ext delay in progress | |
node.<n>.loop.<l>.sensor.<s>.prelarm | 0 | R | not in prealarm |
1 | R | prealarm |