CSx75

From HSYCO
Revision as of 16:19, 23 December 2013 by Hsyco (talk | contribs) (→‎csx75.ini)
Jump to navigation Jump to search

Aritech CSx75 is a multi-area security system. The integration with HSYCO can be accomplished via direct control through the RS-232 port on its panel.

Communication

Use the Aritech CS590 RS232 cable to connect the panel directly to HSYCO or to an Ethernet/RS-232 gateway.

RS-232 parameters:

Baud rate same as configured on panel (default 9600)
Data bits 8
Stop bit 1
Parity none
Flow control none

CSx75 Configuration

The panel must be previously configured to have the serial port enabled and to use the binary control protocol. Refer to its configuration manual for more details.


HSYCO Configuration

Options

ID Default Values Description
pin <code> 4 or 6-digits code. Use the specified PIN code to perform operations that require user authentication. If this option is not specified it will be required to manually insert the pin every time such operations are performed
gui true true enable support for the UI object, UISET actions and USER commands
false disable UI support
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
pollinterval 3 n > 0 the data acquisition interval, in seconds
logsize 20 n ≥ 0 the number of log lines to display in the UI object

csx75.ini

The csx75.ini file is a specific configuration file located in the root directory. Here you can define the names of the users so that they will be automatically added to the user interface. Add a new line for each user using this format:

<io_server_id>.user.<n> = <name>

For instance:

cs.user.1 = Bob
cs.user.2 = Alice