The Honeywell Galaxy Dimension panels are multi-area intrusion detection systems. The integration with HSYCO can be accomplished via RS-232 serial communication.

Communication

Employ a RS-232 straight cable to connect the panel directly to HSYCO or to an Ethernet/RS-232 gateway.

RS-232 parameters:

Baud rate 9600
Data bits 8
Stop bit 1
Parity none
Flow control none

Configuration

It is required to configure the panel for HSYCO to be able to communicate with it. Follow these instructions:

  • Enable the engineer access
    Menu 48.1.1 - set to 1 (Enabled)
  • Enable engineer mode
    Enter engineer PIN, followed by ENT
  • Enable remote access and events reporting
    Menu 56.6.2 - set to 1 (SIA)
    Set SIA level to 4
    Enable (set to ON) all the events to be sent to HSYCO
    Menu 56.6.3 - set an account number (e.g. “0001”)

Options

ID Default Values Description
gui true true enable automatic support of UI objects to show the system status and intercept control buttons
false disable support for the UI
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
offlinelogs true false at startup request the log of all the events occurred while HSYCO was disconnected from the panel
false log only events occurred while HSYCO was connected to the panel
pollinterval 1 n > 0 the data acquisition interval, in seconds
logsize 20 n ≥ 0 the number of log lines to display in the UI object