Difference between revisions of "RACKPDU"

From HSYCO
Jump to navigation Jump to search
 
(7 intermediate revisions by the same user not shown)
Line 32: Line 32:
 
|-
 
|-
  
|rowspan="2"|gui
+
|rowspan="2"|startupevents
 
|rowspan="2"|false
 
|rowspan="2"|false
 
|true
 
|true
|enable support for the UISET actions
+
|generate IO events also during the driver’s start-up phase
 
|-
 
|-
 
|false
 
|false
|disable UI support
+
|start generating events only after HSYCO is aligned with the current status of the system
 
 
 
|-
 
|-
  
|altitude
 
|0
 
|integer number
 
|the station's installation altitude above mean sea level.
 
 
This optional parameter is used to convert the measured local atmospheric pressure to mean sea level pressure (MSLP).
 
 
The conversion function takes into account the altitude and local temperature.
 
 
If this paramter is not set or set to 0, the measured pressure value will be returned unmodified.
 
 
|-
 
 
|}
 
|}
  
 
== Datapoints ==
 
== Datapoints ==
  
All measured values returned as datapoints use the units as set in the WXT520. The unit is not returned in the datapoint value.
+
All measured values returned as datapoints use the units as set in the PDU. The unit is not returned in the datapoint value.
  
  
Line 68: Line 55:
 
|-
 
|-
  
|rowspan="2"|status
+
|rowspan="2"|connection
 
|online
 
|online
 
|R
 
|R
Line 75: Line 62:
 
|offline
 
|offline
 
|R
 
|R
|HSYCO can’t connect to the WXT520
+
|not connected to the PDU
 
|-
 
|-
  
|sn
+
|bklowload.<N>
 
|<value>
 
|<value>
 
|R
 
|R
|wind speed minimum (m/s, km/h, mph, knots)
+
|bank N low-load threshold current in amps
 
|-
 
|-
  
|sm
+
|bknearover.<N>
 
|<value>
 
|<value>
 
|R
 
|R
|wind speed average (m/s, km/h, mph, knots)
+
|bank N near-overload threshold current in amps
 
|-
 
|-
  
|sx
+
|bkoverload.<N>
 
|<value>
 
|<value>
 
|R
 
|R
|wind speed maximum (m/s, km/h, mph, knots)
+
|bank N overload threshold current in amps
 
|-
 
|-
  
|dn
+
|devlowload
 
|<value>
 
|<value>
 
|R
 
|R
|wind direction minimum (deg)
+
|low-load threshold in kilowatts for the device
 
|-
 
|-
  
|dm
+
|devnearover
 
|<value>
 
|<value>
 
|R
 
|R
|wind direction average (deg)
+
|near-overload threshold in kilowatts for the device
 
|-
 
|-
  
|dx
+
|devoverload
 
|<value>
 
|<value>
 
|R
 
|R
|wind direction maximum (deg)
+
|overload threshold in kilowatts for the device
 
|-
 
|-
  
|pa
+
|humreading
 
|<value>
 
|<value>
 
|R
 
|R
|air pressure (hPa, Pa, bar, mmHg, inHg), converted to mean sea level pressure if the altitude option is set
+
|humidity value from the sensor (%RH)
 
|-
 
|-
  
|ta
+
|phlowload.<N>
 
|<value>
 
|<value>
 
|R
 
|R
|air temperature (C, F)
+
|phase N low-load threshold (amps)
 
|-
 
|-
  
|tp
+
|phnearover.<N>
 
|<value>
 
|<value>
 
|R
 
|R
|internal temperature (C, F)
+
|phase N near-overload threshold (amps)
 
|-
 
|-
  
|ua
+
|phoverload.<N>
 
|<value>
 
|<value>
 
|R
 
|R
|relative humidity (%RH)
+
|phase N overload threshold (amps)
 
|-
 
|-
  
|rc
+
|tempReading
 
|<value>
 
|<value>
 
|R
 
|R
|rain accumulation (mm, in)
+
|temperature value in Celsius
 
|-
 
|-
  
|rd
+
|bkpeakcurr.<N>
 
|<value>
 
|<value>
 
|R
 
|R
|rain duration (s)
+
|bank N peak current measurement in amps
 
|-
 
|-
  
|ri
+
|bkreading.<N>
 
|<value>
 
|<value>
 
|R
 
|R
|rain intensity (mm/h, in/h)
+
|bank N current reading (measurement) in amps
 
|-
 
|-
  
|rp
+
|devpeakload
 
|<value>
 
|<value>
 
|R
 
|R
|rain peak intensity (mm/h, in/h)
+
|peak power measurement in kilowatts from the device
 
|-
 
|-
  
|hc
+
|devreading.power
 
|<value>
 
|<value>
 
|R
 
|R
|hail accumulation (hits/cm2, hits/in2, hits)
+
|total power in kilowatts for the device
 
|-
 
|-
  
|hd
+
|devreading.energy
 
|<value>
 
|<value>
 
|R
 
|R
|hail duration (s)
+
|total energy in kilowatt-hours for the device
 
|-
 
|-
  
|hi
+
|devreading.appower
 
|<value>
 
|<value>
 
|R
 
|R
|hail intensity (hits/cm2h, hits/in2h, hits/ h)
+
|total apparent power in kilovolt amperes for the device
 
|-
 
|-
  
|hp
+
|devreading.pf
 
|<value>
 
|<value>
 
|R
 
|R
|hail peak intensity (hits/cm2h, hits/in2h, hits/ h)
+
|total power factor for the device
 
|-
 
|-
  
|th
+
|phpeakcurr.<N>
 
|<value>
 
|<value>
 
|R
 
|R
|heating temperature (C, F)
+
|peak current measurement from phase N (amps)
 
|-
 
|-
  
|vh
+
|phreading.current.<N>
 
|<value>
 
|<value>
 
|R
 
|R
|heating voltage (V)
+
|measured current for phase N (amps)
 
|-
 
|-
  
|vs
+
|phreading.voltage.<N>
 
|<value>
 
|<value>
 
|R
 
|R
|supply voltage (V)
+
|measured voltage for phase N (volts)
 
|-
 
|-
  
|vr
+
|phreading.power.<N>
 
|<value>
 
|<value>
 
|R
 
|R
|3.5 V ref. voltage (V)
+
|measured power for phase N (watts)
 
|-
 
|-
  
|id
+
|phreading.appower.<N>
 
|<value>
 
|<value>
 
|R
 
|R
|information field
+
|measured apparent power for phase N(va)
 
|-
 
|-
  
|}
+
|phreading.pf.<N>
 
+
|<value>
== UISET Actions ==
+
|R
{| class="wikitable"
+
|measured power factor for phase N
!ID
 
!Attribute
 
!Set to
 
!Description
 
|-
 
 
 
|sn
 
|value
 
|<value> <unit>
 
|wind speed minimum (m/s, km/h, mph, knots)
 
|-
 
 
 
|sm
 
|value
 
|<value> <unit>
 
|wind speed average (m/s, km/h, mph, knots)
 
|-
 
 
 
|sx
 
|value
 
|<value> <unit>
 
|wind speed maximum (m/s, km/h, mph, knots)
 
|-
 
 
 
|dn
 
|value
 
|<value> <unit>
 
|wind direction minimum (deg)
 
|-
 
 
 
|dm
 
|value
 
|<value> <unit>
 
|wind direction average (deg)
 
|-
 
 
 
|dn
 
|value
 
|<value> <unit>
 
|wind direction minimum (deg)
 
|-
 
 
 
|dx
 
|value
 
|<value> <unit>
 
|wind direction maximum (deg)
 
|-
 
 
 
|pa
 
|value
 
|<value> <unit>
 
|air pressure (hPa, Pa, bar, mmHg, inHg), converted to mean sea level pressure if the altitude option is set
 
|-
 
 
 
|ta
 
|value
 
|<value> <unit>
 
|air temperature (C, F)
 
|-
 
 
 
|tp
 
|value
 
|<value> <unit>
 
|internal temperature (C, F)
 
|-
 
 
 
|ua
 
|value
 
|<value> <unit>
 
|relative humidity (%RH)
 
|-
 
 
 
|rc
 
|value
 
|<value> <unit>
 
|rain accumulation (mm, in)
 
|-
 
 
 
|rd
 
|value
 
|<value> <unit>
 
|rain duration (s)
 
|-
 
 
 
|ri
 
|value
 
|<value> <unit>
 
|rain intensity (mm/h, in/h)
 
|-
 
 
 
|rp
 
|value
 
|<value> <unit>
 
|rain peak intensity (mm/h, in/h)
 
|-
 
 
 
|hc
 
|value
 
|<value> <unit>
 
|hail accumulation (hits/cm2, hits/in2, hits)
 
|-
 
 
 
|hd
 
|value
 
|<value> <unit>
 
|hail duration (s)
 
|-
 
 
 
|hi
 
|value
 
|<value> <unit>
 
|hail intensity (hits/cm2h, hits/in2h, hits/ h)
 
|-
 
 
 
|hp
 
|value
 
|<value> <unit>
 
|hail peak intensity (hits/cm2h, hits/in2h, hits/ h)
 
|-
 
 
 
|th
 
|value
 
|<value> <unit>
 
|heating temperature (C, F)
 
 
|-
 
|-
  
|vh
+
|rowspan="2"|lcd
|value
+
|on
|<value> <unit>
+
|W
|heating voltage (V)
+
|turn the LCD on
 
|-
 
|-
 
+
|off
|vs
+
|W
|value
+
|turn the LCD off
|<value> <unit>
 
|supply voltage (V)
 
|-
 
 
 
|vr
 
|value
 
|<value> <unit>
 
|3.5 V ref. voltage (V)
 
 
|-
 
|-
  
|id
+
|lcdblink
|value
+
|<1-10>
|<value> <unit>
+
|W
|information field
+
|blink the LCD for 1 to 10 minutes
 
|-
 
|-
  
Line 374: Line 229:
 
== Release Notes ==
 
== Release Notes ==
  
=== 3.4.0 ===
+
=== 3.6.0 ===
 
*initial version release
 
*initial version release
  
Line 380: Line 235:
  
  
''Vaisala is a registered trademarks of Vaisala Oyj.''
+
''APC, StruxureWare, and PowerNet are trademarks owned by Schneider Electric Industries, S.A.S., or its affiliated companies. All other trademarks are property of their respective owners.''

Latest revision as of 18:47, 14 June 2017

The APC by Schneider Electric Rack Power Distribution Unit (PDU) may be used as a stand-alone, network- manageable power distribution device or up to four devices can be connected together using one network connection. The Rack PDU provides real-time remote monitoring of connected loads.

The HSYCO RACKPDU driver supports the AP88XX and AP78XXB Metered models.

IO Server RACKPDU.jpg

PDU Configuration

In order to be able to control the device with HSYCO SERVER, remote access to the command line interface via SSH must be enabled.

HSYCO Configuration

Add a RACKPDU I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • IP Address: the IP address of the device
  • IP Port: TCP/IP port to use (defaults to 22)
  • User: the SSH user (defaults to "apc")
  • Password: the SSH password (defaults to "apc").


High Availability

  • Shutdown when inactive: defaults to false.

Options

ID Default Values Description
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system

Datapoints

All measured values returned as datapoints use the units as set in the PDU. The unit is not returned in the datapoint value.


ID Value R/W Description
connection online R connection established
offline R not connected to the PDU
bklowload.<N> <value> R bank N low-load threshold current in amps
bknearover.<N> <value> R bank N near-overload threshold current in amps
bkoverload.<N> <value> R bank N overload threshold current in amps
devlowload <value> R low-load threshold in kilowatts for the device
devnearover <value> R near-overload threshold in kilowatts for the device
devoverload <value> R overload threshold in kilowatts for the device
humreading <value> R humidity value from the sensor (%RH)
phlowload.<N> <value> R phase N low-load threshold (amps)
phnearover.<N> <value> R phase N near-overload threshold (amps)
phoverload.<N> <value> R phase N overload threshold (amps)
tempReading <value> R temperature value in Celsius
bkpeakcurr.<N> <value> R bank N peak current measurement in amps
bkreading.<N> <value> R bank N current reading (measurement) in amps
devpeakload <value> R peak power measurement in kilowatts from the device
devreading.power <value> R total power in kilowatts for the device
devreading.energy <value> R total energy in kilowatt-hours for the device
devreading.appower <value> R total apparent power in kilovolt amperes for the device
devreading.pf <value> R total power factor for the device
phpeakcurr.<N> <value> R peak current measurement from phase N (amps)
phreading.current.<N> <value> R measured current for phase N (amps)
phreading.voltage.<N> <value> R measured voltage for phase N (volts)
phreading.power.<N> <value> R measured power for phase N (watts)
phreading.appower.<N> <value> R measured apparent power for phase N(va)
phreading.pf.<N> <value> R measured power factor for phase N
lcd on W turn the LCD on
off W turn the LCD off
lcdblink <1-10> W blink the LCD for 1 to 10 minutes

Release Notes

3.6.0

  • initial version release


APC, StruxureWare, and PowerNet are trademarks owned by Schneider Electric Industries, S.A.S., or its affiliated companies. All other trademarks are property of their respective owners.