Difference between revisions of "Redirect variables"

From HSYCO
Jump to navigation Jump to search
Line 39: Line 39:
 
  uiSet("redirect", "mysid", "bmne500");
 
  uiSet("redirect", "mysid", "bmne500");
 
  uiSet("redirect", "myzone", param); // address: "temp."+ myzone
 
  uiSet("redirect", "myzone", param); // address: "temp."+ myzone
 +
        return "ok";
 
     }
 
     }
 
  }
 
  }

Revision as of 17:41, 19 March 2020

Redirect variables allow UI Objects to be linked dynamically to a source.

Redirect variables can be used in:

  • any object's id
  • I/O Server Objects, in server id and address parameters
  • Button objects, in the address parameter


Syntax

Variables are defined with the following syntax:

[<variable name>]

E.g.

[myaddr]

Setting Values

Server UISets (from events or java) are used to set a redirect variable's value. Each redirect variable is a property of the "redirect" object. For example, a redirect variable called "myaddr" can be set to "70" with a UISet command on events:

UISET redirect.myaddr=70

Example: Weather Object

In this example we will use a single TempMini object to display different sources. In hsyco.ini we have an ioServer with 3 zones.

ioServers = bmne500
ioServersType.bmne500 = MYHOME
ioServersOptions.bmne500 = tempzones=1;2;3

In a project we place a TempMini and three User buttons. On the TempMini parameters, we use two redirect variables: mysid and myzone.

Redirect vars 01.png

Each User button will have "changetemp" as name and "1", "2" or "3" respectively as param.

In events we declare:

function userCommand(session, userid, name, param) : {
   if (name == "changetemp") {
	uiSet("redirect", "mysid", "bmne500");
	uiSet("redirect", "myzone", param); // address: "temp."+ myzone
       return "ok";
   }
}

Clicking on a button in the interface will execute the above callback, which sets the redirect variables' values and changes the source of the TempMini object accordingly.

Example: Button object

Similarly to the previous example, in a project we place a Button object with a redirect variable called myaddr. We also place two User buttons with name "changeaddr" and param "light.1" and "autom.1"

Redirect vars 02.png

function userCommand(session, userid, name, param) : {
   if (name == "change") {
       uiSet("redirect", "myaddr", "dummy."+param); // dummy.light.1
   }
}

Once again clicking on a User button will cause the Button object to change its source, from a light to an autom.