Difference between revisions of "Notifier"

From HSYCO
Jump to navigation Jump to search
 
(72 intermediate revisions by 4 users not shown)
Line 9: Line 9:
 
The NOTIFIER SIB 600 Modbus interface is required. The default connection parameters are:
 
The NOTIFIER SIB 600 Modbus interface is required. The default connection parameters are:
  
Modbus address: 1 (can be set to 1-32)
+
Modbus address: 1 ... 32
  
 
RS-485 parameters:
 
RS-485 parameters:
Line 30: Line 30:
  
 
Refer to the Notifier manuals for installation, wiring and power supply requirements.
 
Refer to the Notifier manuals for installation, wiring and power supply requirements.
 +
 +
Here's a screenshot of the manual:
 +
 +
[[File:Notifier_Sib600.png]]
 +
 +
RS485 MODBUS port is on pin 5,6,7
 +
 +
It's mandatory to enable the SIB 600 module with UPLOAD PK 2000, PK4000 or PK6000. The MODBUS address must be assigned in the TCP/IP field.
  
 
== HSYCO Configuration ==
 
== HSYCO Configuration ==
 +
Add a NOTIFIER I/O Server in the [[Settings#I/O Servers|I/O Servers section of the Settings]] and set its parameters:
 +
 +
=== Communication ===
 +
*'''Comm ID''': select a MODBUSTCP I/O server if using a Modbus gateway, or the serial port id when using a direct RS-485 port with HSYCO acting as Modbus RTU master.
 +
 +
=== High Availability ===
 +
*'''Shutdown when inactive''': defaults to false.
 +
 
=== Options ===
 
=== Options ===
  
Line 68: Line 84:
 
|1
 
|1
 
|> 0
 
|> 0
|set to the highest zone number configured in the panel. Set to 0 to disable zone status polling and control commands
+
|the data acquisition interval, in seconds
 +
 
 
|-
 
|-
  
Line 81: Line 98:
 
|≥ 0
 
|≥ 0
 
|if GUI support is enabled, set to the maximum number of lines to show in the log text object. Set to 0 to disable the GUI log
 
|if GUI support is enabled, set to the maximum number of lines to show in the log text object. Set to 0 to disable the GUI log
 +
|-
 +
 +
|rowspan="2"|protocolversion
 +
|rowspan="2"|2
 +
|1
 +
|set this option to 1 only if the panel is using the old firmware
 +
|-
 +
|2
 +
|default protocol support for panels with new firmware (N models)
 
|-
 
|-
  
Line 86: Line 112:
  
 
== Datapoints ==
 
== Datapoints ==
 +
 +
{{tip|Data points marked with (N) are not available with older firmware versions. Data points marked with (O) are only available with older firmware versions.}}
  
 
{| class="wikitable"
 
{| class="wikitable"
Line 104: Line 132:
 
|-
 
|-
  
|rowspan="2" |annunciator.<n>.<m>.offline
+
|rowspan="2" |annunciator.<n>.<m>.offline (N)
|rowspan="2" |1
+
|1
 
|R
 
|R
 
|annunciator <n>.<m> offline
 
|annunciator <n>.<m> offline
 
|-
 
|-
|rowspan="2" |0
+
|0
 
|R
 
|R
 
|annunciator <n>.<m> online
 
|annunciator <n>.<m> online
 
|-
 
|-
 +
 +
|rowspan="2" |annunciator.<n>.<m>.fault (N)
 +
|1
 +
|R
 +
|annunciator <n>.<m>fault
 +
|-
 +
|0
 +
|R
 +
|annunciator <n>.<m> no fault
 +
|-
 +
 +
|rowspan="2" |annunciator.<n>.<m>.cfg.error (N)
 +
|1
 +
|R
 +
|annunciator <n>.<m> configuration error
 +
|-
 +
|0
 +
|R
 +
|annunciator <n>.<m> configured
 +
|-
 +
 +
|rowspan="2" |annunciator.<n>.offline (O)
 +
|1
 +
|R
 +
|annunciator <n> offline
 +
|-
 +
|0
 +
|R
 +
|annunciator <n> online
 +
|-
 +
 +
|rowspan="2" |annunciator.<n>.fault (O)
 +
|1
 +
|R
 +
|annunciator <n> fault
 +
|-
 +
|0
 +
|R
 +
|annunciator <n> no fault
 +
|-
 +
 +
|detected.annunciators
 +
|
 +
|R
 +
|space separated list of detected annunciators
 +
|-
 +
 +
|detected.lcds
 +
|
 +
|R
 +
|space separated list of detected LCDs
 +
|-
 +
 +
|detected.modules.<l>
 +
|
 +
|R
 +
|space separated list of detected modules on loop <l>
 +
|-
 +
 +
|detected.loops
 +
|
 +
|R
 +
|space separated list of detected loops
 +
|-
 +
 +
|detected.sensors.<l>
 +
|
 +
|R
 +
|space separated list of detected loops on loop <l>
 +
|-
 +
 +
|rowspan="2" |lcd.offline (O)
 +
|1
 +
|R
 +
|LCD/Terminal offline
 +
|-
 +
|0
 +
|R
 +
|LCD/Terminal offline
 +
|-
 +
 +
|rowspan="2" |lcd.<n>.offline (N)
 +
|1
 +
|R
 +
|LCD <n> offline
 +
|-
 +
|0
 +
|R
 +
|LCD <n> online
 +
|-
 +
 +
|rowspan="2" |lcd.<n>.fault (N)
 +
|1
 +
|R
 +
|LCD <n> fault
 +
|-
 +
|0
 +
|R
 +
|LCD <n> no fault
 +
|-
 +
 +
|rowspan="2" |lcd.<n>.cfg.error (N)
 +
|1
 +
|R
 +
|LCD <n> configuration error
 +
|-
 +
|0
 +
|R
 +
|LCD <n> configured
 +
|-
 +
 +
|rowspan="2" |loop.<n>.disabled (O)
 +
|1
 +
|R
 +
|loop <n> disabled
 +
|-
 +
|0
 +
|R
 +
|loop <n> not disabled
 +
|-
 +
 +
|rowspan="2" |loop.<n>.short
 +
|1
 +
|R
 +
|loop <n> short circuit
 +
|-
 +
|0
 +
|R
 +
|loop <n> no short circuit
 +
|-
 +
 +
|rowspan="2" |loop.<n>.open
 +
|1
 +
|R
 +
|loop <n> open fault
 +
|-
 +
|0
 +
|R
 +
|loop <n> no open fault
 +
|-
 +
 +
|rowspan="2" |loop.<n>.voltage
 +
|1
 +
|R
 +
|loop <n> low voltage fault
 +
|-
 +
|0
 +
|R
 +
|loop <n> no low voltage fault
 +
|-
 +
 +
|rowspan="2" |module.<l>.<n>.normal
 +
|1
 +
|R
 +
|module <n> on loop <l> normal state
 +
|-
 +
|0
 +
|R
 +
|module <n> on loop <l> error state
 +
|-
 +
 +
|rowspan="4" |module.<l>.<n>.disabled
 +
|rowspan="2"|1
 +
|R
 +
|module <n> on loop <l> disabled
 +
|-
 +
|W
 +
|disable module <n> on loop <l>
 +
|-
 +
|rowspan="2"|0
 +
|R
 +
|module <n> on loop <l> enabled
 +
|-
 +
|W
 +
|enable module <n> on loop <l>
 +
|-
 +
 +
|rowspan="4" |module.<l>.<n>.out
 +
|rowspan="2"|1
 +
|R
 +
|module <n> on loop <l> output active (ON)
 +
|-
 +
|W
 +
|turn ON out of module <n> on loop <l>
 +
|-
 +
|rowspan="2"|0
 +
|R
 +
|module <n> on loop <l> output not active (OFF)
 +
|-
 +
|W
 +
|turn OFF out of module <n> on loop <l>
 +
|-
 +
 +
|rowspan="2" | module.<l>.<n>.fault
 +
|v
 +
|R
 +
|module <n> on loop <l> fault  (see modules fault error table below)
 +
|-
 +
|0
 +
|R
 +
|module <n> on loop <l> no fault
 +
|-
 +
 +
|rowspan="2" |module.<l>.<n>.alarm
 +
|1
 +
|R
 +
|module <n> on loop <l> alarm
 +
|-
 +
|0
 +
|R
 +
|module <n> on loop <l> no alarm
 +
|-
 +
 +
|rowspan="2" |panel.fault.batt.disconn
 +
|1
 +
|R
 +
|batteries disconnected
 +
|-
 +
|0
 +
|R
 +
|batteries connected
 +
|-
 +
 +
|rowspan="2" |panel.fault.power
 +
|1
 +
|R
 +
|mains power failure
 +
|-
 +
|0
 +
|R
 +
|mains power ok
 +
|-
 +
 +
|rowspan="2" |panel.fault.supply.main (O)
 +
|1
 +
|R
 +
|main power supply failure
 +
|-
 +
|0
 +
|R
 +
|main power supply ok
 +
|-
 +
 +
|rowspan="2" |panel.fault.supply.aux (O)
 +
|1
 +
|R
 +
|aux power supply failure
 +
|-
 +
|0
 +
|R
 +
|aux power supply ok
 +
|-
 +
 +
|rowspan="2" |panel.fault.supply.aux.disc (O)
 +
|1
 +
|R
 +
|aux power supply disconnected
 +
|-
 +
|0
 +
|R
 +
|aux power supply not disconnected
 +
|-
 +
 +
|rowspan="2" |panel.fault.supply.aux.not.prg (O)
 +
|1
 +
|R
 +
|aux power supply not programmed
 +
|-
 +
|0
 +
|R
 +
|aux power supply programmed
 +
|-
 +
 +
|rowspan="2" |panel.fault.batt.unbal
 +
|1
 +
|R
 +
|battery charger unbalance detected
 +
|-
 +
|0
 +
|R
 +
|battery charger unbalance not detected
 +
|-
 +
 +
|rowspan="2" |panel.fault.batt.fail
 +
|1
 +
|R
 +
|battery failure detected
 +
|-
 +
|0
 +
|R
 +
|battery failure not detected
 +
|-
 +
 +
|rowspan="2" |panel.fault.batt.low (O)
 +
|1
 +
|R
 +
|battery low voltage detected
 +
|-
 +
|0
 +
|R
 +
|battery low voltage not detected
 +
|-
 +
 +
|rowspan="2" |panel.fault.bex
 +
|1
 +
|R
 +
|battery exhausted detected
 +
|-
 +
|0
 +
|R
 +
|battery exhausted not detected
 +
|-
 +
 +
|rowspan="2" |panel.fault.earth
 +
|1
 +
|R
 +
|ground connection fault
 +
|-
 +
|0
 +
|R
 +
|no ground connection fault
 +
|-
 +
 +
|rowspan="2" |panel.fault.undervoltage
 +
|1
 +
|R
 +
|AC power under-voltage fault
 +
|-
 +
|0
 +
|R
 +
|no AC power under-voltage fault
 +
|-
 +
 +
|rowspan="2" |panel.fault.overvoltage
 +
|1
 +
|R
 +
|AC power over-voltage fault
 +
|-
 +
|0
 +
|R
 +
|no AC power over-voltage fault
 +
|-
 +
 +
|rowspan="2" |panel.fault.siren.open
 +
|1
 +
|R
 +
|siren line wire cut detected
 +
|-
 +
|0
 +
|R
 +
|siren line wire cut not detected
 +
|-
 +
 +
|rowspan="2" |panel.fault.siren.short
 +
|1
 +
|R
 +
|siren line short circuit detected
 +
|-
 +
|0
 +
|R
 +
|siren line short circuit not detected
 +
|-
 +
 +
|rowspan="2" |panel.fault.fuse
 +
|1
 +
|R
 +
|fuse fault
 +
|-
 +
|0
 +
|R
 +
|fuse ok
 +
|-
 +
 +
|rowspan="2" style="white-space:nowrap"|panel.fault.batt.charger.undervoltage
 +
|1
 +
|R
 +
|battery charger under-voltage fault
 +
|-
 +
|0
 +
|R
 +
|no battery charger under-voltage fault
 +
|-
 +
 +
|rowspan="2" |panel.fault.batt.charger.overvoltage
 +
|1
 +
|R
 +
|battery charger over-voltage fault
 +
|-
 +
|0
 +
|R
 +
|no battery charger over-voltage fault
 +
|-
 +
 +
|rowspan="2" |panel.filesystem.clear.error (N)
 +
|1
 +
|R
 +
|memory delete error
 +
|-
 +
|0
 +
|R
 +
|no memory delete error
 +
|-
 +
 +
|rowspan="2" |panel.filesystem.init.error (N)
 +
|1
 +
|R
 +
|memory initialization error
 +
|-
 +
|0
 +
|R
 +
|no memory initialization error
 +
|-
 +
 +
|rowspan="2" |panel.reliab.par.mod
 +
|1
 +
|R
 +
|reliability parameters modified warning
 +
|-
 +
|0
 +
|R
 +
|no reliability parameters modified warning
 +
|-
 +
 +
|rowspan="2" |panel.hardkey.enabled
 +
|1
 +
|R
 +
|hardware programming key enabled
 +
|-
 +
|0
 +
|R
 +
|hardware programming key not enabled
 +
|-
 +
 +
|rowspan="2" |panel.power.on
 +
|1
 +
|R
 +
|power on phase
 +
|-
 +
|0
 +
|R
 +
|power on phase completed
 +
|-
 +
 +
|rowspan="2" |panel.wdt.reset
 +
|1
 +
|R
 +
|main CPU watchdog fault
 +
|-
 +
|0
 +
|R
 +
|main CPU watchdog ok
 +
|-
 +
 +
|rowspan="2" |panel.cfg.error (N)
 +
|1
 +
|R
 +
|configuration error
 +
|-
 +
|0
 +
|R
 +
|configuration ok
 +
|-
 +
 +
|rowspan="2" |panel.filesystem.error (N)
 +
|1
 +
|R
 +
|memory corruption
 +
|-
 +
|0
 +
|R
 +
|memory ok
 +
|-
 +
 +
|rowspan="2" |panel.hard.clock (N)
 +
|1
 +
|R
 +
|internal hardware clock fault
 +
|-
 +
|0
 +
|R
 +
|internal hardware clock ok
 +
|-
 +
 +
|rowspan="2" |panel.arch.full (N)
 +
|1
 +
|R
 +
|log archive full
 +
|-
 +
|0
 +
|R
 +
|log archive not full
 +
|-
 +
 +
|rowspan="2" |panel.arch.full.warning (N)
 +
|1
 +
|R
 +
|log archive warning (80% full)
 +
|-
 +
|0
 +
|R
 +
|no log archive warning
 +
|-
 +
 +
|rowspan="2" |panel.zone.default (N)
 +
|1
 +
|R
 +
|sensors/modules not yet assigned to zones
 +
|-
 +
|0
 +
|R
 +
|zones/modules assignment done
 +
|-
 +
 +
|rowspan="2" |panel.sib.offline (N)
 +
|1
 +
|R
 +
|SIB board offline
 +
|-
 +
|0
 +
|R
 +
|SIB board online
 +
|-
 +
 +
|rowspan="2" |panel.sib.not.prg (N)
 +
|1
 +
|R
 +
|SIB board not programmed
 +
|-
 +
|0
 +
|R
 +
|SIB board programmed
 +
|-
 +
 +
|rowspan="2" |panel.pc.invalid.cmd (N)
 +
|1
 +
|R
 +
|invalid command from PC
 +
|-
 +
|0
 +
|R
 +
|no invalid command from PC
 +
|-
 +
 +
|rowspan="2" |panel.arch.disabled
 +
|1
 +
|R
 +
|log archive disabled
 +
|-
 +
|0
 +
|R
 +
|log archive enabled
 +
|-
 +
 +
|rowspan="2" |panel.lib.<n>.offline
 +
|1
 +
|R
 +
|LIB board <n> offline
 +
|-
 +
|0
 +
|R
 +
|LIB board <n> online
 +
|-
 +
 +
|rowspan="2" |panel.lib.<n>.cfg.error
 +
|1
 +
|R
 +
|LIB board <n> configuration error
 +
|-
 +
|0
 +
|R
 +
|LIB board <n> configured
 +
|-
 +
 +
|rowspan="2" |panel.lib.<n>.not.prg
 +
|1
 +
|R
 +
|LIB board <n> not programmed
 +
|-
 +
|0
 +
|R
 +
|LIB board <n> programmed
 +
|-
 +
 +
|rowspan="4" |panel.fire
 +
|silence
 +
|W
 +
|fire alarm silence
 +
|-
 +
|reset
 +
|W
 +
|fire alarm reset
 +
|-
 +
|activate
 +
|W
 +
|output re-activation
 +
|-
 +
|ack
 +
|W
 +
|acknowledge
 +
|-
 +
 +
|rowspan="2" |panel.fire.normal
 +
|1
 +
|R
 +
|fire panel normal state
 +
|-
 +
|0
 +
|R
 +
|fire panel error state
 +
|-
 +
 +
|rowspan="2" |panel.fire.exclusions
 +
|1
 +
|R
 +
|fire panel has one or more disabled components
 +
|-
 +
|0
 +
|R
 +
|fire panel’s all components are enabled
 +
|-
 +
 +
|rowspan="2" |panel.fire.test
 +
|1
 +
|R
 +
|fire panel test
 +
|-
 +
|0
 +
|R
 +
|fire panel no test
 +
|-
 +
 +
 +
|rowspan="2" |panel.fire.fault
 +
|1
 +
|R
 +
|fire panel fault
 +
|-
 +
|0
 +
|R
 +
|fire panel no fault
 +
|-
 +
 +
|rowspan="2" |panel.fire.alarm
 +
|1
 +
|R
 +
|fire panel alarm
 +
|-
 +
|0
 +
|R
 +
|fire panel no alarm
 +
|-
 +
 +
|rowspan="2" |panel.fire.alarm.silent
 +
|1
 +
|R
 +
|fire panel alarm silenced
 +
|-
 +
|0
 +
|R
 +
|fire panel no alarm silenced
 +
|-
 +
 +
|rowspan="2" |panel.fire.ack
 +
|1
 +
|R
 +
|fire panel with events requing acknowledgement
 +
|-
 +
|0
 +
|R
 +
|fire panel with no events requing acknowledgement
 +
|-
 +
 +
|rowspan="4" |panel.tech (N)
 +
|silence
 +
|W
 +
|technical alarm silence
 +
|-
 +
|reset
 +
|W
 +
|technical alarm reset
 +
|-
 +
|activate
 +
|W
 +
|output re-activation
 +
|-
 +
|ack
 +
|W
 +
|acknowledge
 +
|-
 +
 +
|rowspan="2" |panel.tech.normal (N)
 +
|1
 +
|R
 +
|technical panel normal state
 +
|-
 +
|0
 +
|R
 +
|technical panel error state
 +
|-
 +
 +
|rowspan="2" |panel.tech.exclusions (N)
 +
|1
 +
|R
 +
|technical panel has one or more disabled components
 +
|-
 +
|0
 +
|R
 +
|technical panel’s all components are enabled
 +
|-
 +
 +
|rowspan="2" |panel.tech.test (N)
 +
|1
 +
|R
 +
|technical panel test
 +
|-
 +
|0
 +
|R
 +
|technical panel no test
 +
|-
 +
 +
|rowspan="2" |panel.tech.fault (N)
 +
|1
 +
|R
 +
|technical panel fault
 +
|-
 +
|0
 +
|R
 +
|technical panel no fault
 +
|-
 +
 +
|rowspan="2" |panel.tech.alarm (N)
 +
|1
 +
|R
 +
|technical panel alarm
 +
|-
 +
|0
 +
|R
 +
|technical panel no alarm
 +
|-
 +
 +
|rowspan="2" |panel.tech.ack (N)
 +
|1
 +
|R
 +
|technical panel with events requing acknowledgement
 +
|-
 +
|0
 +
|R
 +
|technical panel with no events requing acknowledgement
 +
|-
 +
 +
|rowspan="2" |sensor.<l>.<n>.normal
 +
|1
 +
|R
 +
|sensor <n> on loop <l> normal state
 +
|-
 +
|0
 +
|R
 +
|sensor <n> on loop <l> error state
 +
|-
 +
 +
|rowspan="4" |sensor.<l>.<n>.disabled
 +
|rowspan="2"|1
 +
|R
 +
|sensor <n> on loop <l> disabled
 +
|-
 +
|W
 +
|disable sensor <n> on loop <l>
 +
|-
 +
|rowspan="2"|0
 +
|R
 +
|sensor <n> on loop <l> enabled
 +
|-
 +
|W
 +
|enable sensor <n> on loop <l>
 +
|-
 +
 +
|rowspan="2" |sensor.<l>.<n>.prealarm.1
 +
|1
 +
|R
 +
|sensor <n> on loop <l> pre-alarm 1
 +
|-
 +
|0
 +
|R
 +
|sensor <n> on loop <l> pre-alarm 1 off
 +
|-
 +
 +
|rowspan="2" |sensor.<l>.<n>.prealarm.2
 +
|1
 +
|R
 +
|sensor <n> on loop <l> pre-alarm 2
 +
|-
 +
|0
 +
|R
 +
|sensor <n> on loop <l> pre-alarm 2 off
 +
|-
 +
 +
|rowspan="2" |sensor.<l>.<n>.fault
 +
|v
 +
|R
 +
|sensor <n> on loop <l> fault (see sensors fault error table below)
 +
|-
 +
|0
 +
|R
 +
|sensor <n> on loop <l> no fault
 +
|-
 +
 +
|rowspan="2" |sensor.<l>.<n>.alarm
 +
|1
 +
|R
 +
|sensor <n> on loop <l> alarm
 +
|-
 +
|0
 +
|R
 +
|sensor <n> on loop <l> no alarm
 +
|-
 +
 +
|sensor.<l>.<n>.analog
 +
|v
 +
|R
 +
|sensor <n> on loop <l> analog value
 +
|-
 +
 +
|rowspan="2" |zone.<n>.normal
 +
|1
 +
|R
 +
|zone <n> normal state
 +
|-
 +
|0
 +
|R
 +
|zone <n> error state
 +
|-
 +
 +
|rowspan="4" |zone.<n>.disabled
 +
|rowspan="2"|1
 +
|R
 +
|zone <n> disabled
 +
|-
 +
|W
 +
|disable zone <n>
 +
|-
 +
|rowspan="2"|0
 +
|R
 +
|zone <n> enabled
 +
|-
 +
|W
 +
|enable zone <n>
 +
|-
 +
 +
|rowspan="2" |zone.<n>.fault
 +
|1
 +
|R
 +
|zone <n> fault
 +
|-
 +
|0
 +
|R
 +
|zone <n> no fault
 +
|-
 +
 +
|rowspan="2" |zone.<n>.alarm
 +
|1
 +
|R
 +
|zone <n> alarm
 +
|-
 +
|0
 +
|R
 +
|zone <n> no alarm
 +
|-
 +
 +
|}
 +
 +
===Modules fault values for input modules===
 +
 +
The value v of the fault data point can be the combination (sum) of multiple error values.
 +
 +
{| class="wikitable"
 +
| '''Value'''
 +
| '''ID'''
 +
| '''Description'''
 +
|-
 +
| 1
 +
| EDEINST
 +
| not installed
 +
|-
 +
| 4
 +
| EINV
 +
| not responding
 +
|-
 +
| 8
 +
| EFAULTTYPEID
 +
| type id fault
 +
|-
 +
| 32
 +
| ESHORT or ECUT
 +
| short circuit or wire cut
 +
|-
 +
| 64
 +
| ETAMP
 +
| tamper alarm
 +
|}
 +
 +
===Modules fault values for output modules===
 +
 +
The value v of the fault data point can be the combination (sum) of multiple error values.
 +
 +
{| class="wikitable"
 +
| '''Value'''
 +
| '''ID'''
 +
| '''Description'''
 +
|-
 +
| 1
 +
| EDEINST
 +
| not installed
 +
|-
 +
| 4
 +
| EINV
 +
| not responding
 +
|-
 +
| 8
 +
| EFAULTTYPEID
 +
| type id fault
 +
|-
 +
| 32
 +
| ESHORT
 +
| short circuit
 +
|-
 +
| 64
 +
| ECUT
 +
| wire cut
 +
|}
 +
 +
===Sensors fault values for generic sensors===
 +
 +
The value v of the fault data point can be the combination (sum) of multiple error values.
 +
 +
{| class="wikitable"
 +
| '''Value'''
 +
| '''ID'''
 +
| '''Description'''
 +
|-
 +
| 1
 +
| EDEINST
 +
| not installed
 +
|-
 +
| 4
 +
| EINV
 +
| not responding
 +
|-
 +
| 8
 +
| EFAULTTYPEID
 +
| type id fault
 +
|-
 +
| 16
 +
| EDRIFT
 +
| drift warning (75% of alarm for >10 minute)
 +
|-
 +
| 32
 +
| EMAINT
 +
| dirt sensor warning (80% of alarm for >36 hours)
 +
|-
 +
| 64
 +
| ELOW
 +
| low chamber value fault (<20% of alarm)
 +
|}
 +
 +
===Sensors fault values for GASS or OXY sensors===
 +
 +
The value v of the fault data point can be the combination (sum) of multiple error values.
 +
 +
{| class="wikitable"
 +
| '''Value'''
 +
| '''ID'''
 +
| '''Description'''
 +
|-
 +
| 1
 +
| EDEINST
 +
| not installed
 +
|-
 +
| 4
 +
| EINV
 +
| not responding
 +
|-
 +
| 8
 +
| EFAULTTYPEID
 +
| type id fault
 +
|-
 +
| 64
 +
| ELOW
 +
| low chamber value fault
 
|}
 
|}
  
 
== User Interface ==
 
== User Interface ==
  
=== UISET Actions ===
+
===UISET===
 
You can use any object that accepts a text attribute, usually [[text]], but also [[marquee]] and others, to display the status of the system according to the following table:
 
You can use any object that accepts a text attribute, usually [[text]], but also [[marquee]] and others, to display the status of the system according to the following table:
  
Line 125: Line 1,141:
 
!colspan="2"|Set to
 
!colspan="2"|Set to
 
|-
 
|-
 +
 +
|log
 +
|value
 +
|colspan="2"|a textual log of all relevant events. The last event is at the top, with older events scrolled down, then removed from the log past the log lines limit
 +
|-
 +
 +
|log0
 +
|value
 +
|colspan="2"|latest line of the security log when a new entry is added, set back to blank after a short period
 +
|-
 +
 +
|offline.label
 +
|visible
 +
|true when HSYCO can’t connect to the Notifier panel, false otherwise
 +
|-
 +
 +
|annunciator.<n>.<m>.offline.label
 +
|visible
 +
|true when annunciator <n>.<m> is offline
 +
|-
 +
 +
|annunciator.<n>.<m>.fault.label
 +
|visible
 +
|true when annunciator <n>.<m> fault
 +
|-
 +
 +
|style="white-space:nowrap"|annunciator.<n>.<m>.cfg.error.label
 +
|visible
 +
|true when annunciator <n>.<m> has a configuration error
 +
|-
 +
 +
|lcd.offline.label
 +
|visible
 +
|true when LCD is offline (old protocol only)
 +
|-
 +
 +
|lcd.<n>.offline.label
 +
|visible
 +
|true when LCD <n> is offline
 +
|-
 +
 +
|lcd.<n>.fault.label
 +
|visible
 +
|true when LCD <n> is showing a fault condition
 +
|-
 +
 +
|lcd.<n>.cfg.error.label
 +
|visible
 +
|true when LCD <n> has a configuration error
 +
|-
 +
 +
|loop.<n>.short.label
 +
|visible
 +
|true when loop <n> short circuit
 +
|-
 +
 +
|loop.<n>.open.label
 +
|visible
 +
|true when loop <n> is open
 +
|-
 +
 +
|loop.<n>.voltage.label
 +
|visible
 +
|true when loop <n> voltage is too low
 +
|-
 +
 +
|module.<l>.<n>.normal.label
 +
|visible
 +
|true when module <n> on loop <l> normal state
 +
|-
 +
 +
 +
|module.<l>.<n>.disabled.label
 +
|visible
 +
|true when module <n> on loop <l> disabled
 +
|-
 +
 +
|module.<l>.<n>.out.label
 +
|visible
 +
|true when module <n> on loop <l> output is ON
 +
|-
 +
 +
|module.<l>.<n>.fault.label
 +
|visible
 +
|true when module <n> on loop <l> fault
 +
|-
 +
 +
|module.<l>.<n>.alarm.label
 +
|visible
 +
|true when module <n> on loop <l> alarm
 +
|-
 +
 +
|panel.fire.normal.label
 +
|visible
 +
|true when fire panel normal state
 +
|-
 +
 +
|panel.fire.exclusions.label
 +
|visible
 +
|true when fire panel has one or more disabled components
 +
|-
 +
 +
|panel.fire.test.label
 +
|visible
 +
|true when fire panel test mode
 +
|-
 +
 +
|panel.fire.fault.label
 +
|visible
 +
|true when fire panel fault
 +
|-
 +
 +
|panel.fire.alarm.label
 +
|visible
 +
|true when fire panel alarm
 +
|-
 +
 +
|panel.tech.normal.label
 +
|visible
 +
|true when technical panel normal state
 +
|-
 +
 +
|panel.tech.exclusions.label
 +
|visible
 +
|true when technical panel has disabled components
 +
|-
 +
 +
|panel.tech.test.label
 +
|visible
 +
|true when technical panel test mode
 +
|-
 +
 +
|panel.tech.fault.label
 +
|visible
 +
|true when technical panel fault
 +
|-
 +
 +
|panel.tech.alarm.label
 +
|visible
 +
|true when technical panel alarm
 +
|-
 +
 +
|sensor.<l>.<n>.normal.label
 +
|visible
 +
|true when sensor <n> on loop <l> normal state
 +
|-
 +
 +
|sensor.<l>.<n>.disabled.label
 +
|visible
 +
|true when sensor <n> on loop <l> disabled
 +
|-
 +
 +
|sensor.<l>.<n>.prealarm.1.label
 +
|visible
 +
|true when Sensor <n> on loop <l> pre-alarm 1
 +
|-
 +
 +
|sensor.<l>.<n>.prealarm.2.label
 +
|visible
 +
|true when Sensor <n> on loop <l> pre-alarm 2
 +
|-
 +
 +
|sensor.<l>.<n>.fault.label
 +
|visible
 +
|true when sensor <n> on loop <l> fault
 +
|-
 +
 +
|sensor.<l>.<n>.alarm.label
 +
|visible
 +
|true when sensor <n> on loop <l> alarm
 +
|-
 +
 +
|zone.<n>.normal.label
 +
|visible
 +
|true when zone <n> normal state
 +
|-
 +
 +
|zone.<n>.disabled.label
 +
|visible
 +
|true when zone <n> disabled
 +
|-
 +
 +
|zone.<n>.fault.label
 +
|visible
 +
|true when zone <n> fault
 +
|-
 +
 +
|zone.<n>.alarm.label
 +
|visible
 +
|true when zone <n> alarm
 +
|-
 +
 +
|}
  
 
=== USER Commands ===
 
=== USER Commands ===
Line 139: Line 1,348:
  
 
== Release Notes ==
 
== Release Notes ==
 +
=== 3.6.0 ===
 +
*adds support for old AM-x000 firmware versions
 +
*new data points: detected.loops, detected.sensors.<loop>, detected.modules.<loop>, detected.lcds, detected.annunciators
 +
*data point panel.fire.unknown renamed panel.fire.ack
 +
*data point panel.fault.loop.open renamed panel.fault.siren.open
 +
*data point panel.fault.loop.short renamed panel.fault.siren.short
 +
 +
=== 3.5.1 ===
 +
*minor changes to the sensor.<l>.<n>.fault data point
 +
*new "activate" and "ack" commands to the panel.fire data point
 +
 
=== 3.3.0 ===
 
=== 3.3.0 ===
 
*initial release
 
*initial release

Latest revision as of 08:21, 19 April 2019

The NOTIFIER AM-2000, AM-4000 and AM-6000 are multi-area fire panels. The integration with HSYCO can be accomplished via a standard Modbus RTU slave interface.

IO Server Notifier Panel.png

Communication

The NOTIFIER SIB 600 Modbus interface is required. The default connection parameters are:

Modbus address: 1 ... 32

RS-485 parameters:

Baud rate 9600
Data bits 8
Stop bit 1
Parity none
Flow control none

Refer to the Notifier manuals for installation, wiring and power supply requirements.

Here's a screenshot of the manual:

Notifier Sib600.png

RS485 MODBUS port is on pin 5,6,7

It's mandatory to enable the SIB 600 module with UPLOAD PK 2000, PK4000 or PK6000. The MODBUS address must be assigned in the TCP/IP field.

HSYCO Configuration

Add a NOTIFIER I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • Comm ID: select a MODBUSTCP I/O server if using a Modbus gateway, or the serial port id when using a direct RS-485 port with HSYCO acting as Modbus RTU master.

High Availability

  • Shutdown when inactive: defaults to false.

Options

ID Default Values Description
address 1 1 ... 32 the panel’s Modbus address
gui true true enable support for the UI object, UISET actions and USER commands
false disable UI support
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
pollinterval 1 > 0 the data acquisition interval, in seconds
lastzone 150 0 ... 150 set to the highest zone number configured in the panel. Set to 0 to disable zone status polling and control commands
loglines 100 ≥ 0 if GUI support is enabled, set to the maximum number of lines to show in the log text object. Set to 0 to disable the GUI log
protocolversion 2 1 set this option to 1 only if the panel is using the old firmware
2 default protocol support for panels with new firmware (N models)

Datapoints

Note Data points marked with (N) are not available with older firmware versions. Data points marked with (O) are only available with older firmware versions.

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
annunciator.<n>.<m>.offline (N) 1 R annunciator <n>.<m> offline
0 R annunciator <n>.<m> online
annunciator.<n>.<m>.fault (N) 1 R annunciator <n>.<m>fault
0 R annunciator <n>.<m> no fault
annunciator.<n>.<m>.cfg.error (N) 1 R annunciator <n>.<m> configuration error
0 R annunciator <n>.<m> configured
annunciator.<n>.offline (O) 1 R annunciator <n> offline
0 R annunciator <n> online
annunciator.<n>.fault (O) 1 R annunciator <n> fault
0 R annunciator <n> no fault
detected.annunciators R space separated list of detected annunciators
detected.lcds R space separated list of detected LCDs
detected.modules.<l> R space separated list of detected modules on loop <l>
detected.loops R space separated list of detected loops
detected.sensors.<l> R space separated list of detected loops on loop <l>
lcd.offline (O) 1 R LCD/Terminal offline
0 R LCD/Terminal offline
lcd.<n>.offline (N) 1 R LCD <n> offline
0 R LCD <n> online
lcd.<n>.fault (N) 1 R LCD <n> fault
0 R LCD <n> no fault
lcd.<n>.cfg.error (N) 1 R LCD <n> configuration error
0 R LCD <n> configured
loop.<n>.disabled (O) 1 R loop <n> disabled
0 R loop <n> not disabled
loop.<n>.short 1 R loop <n> short circuit
0 R loop <n> no short circuit
loop.<n>.open 1 R loop <n> open fault
0 R loop <n> no open fault
loop.<n>.voltage 1 R loop <n> low voltage fault
0 R loop <n> no low voltage fault
module.<l>.<n>.normal 1 R module <n> on loop <l> normal state
0 R module <n> on loop <l> error state
module.<l>.<n>.disabled 1 R module <n> on loop <l> disabled
W disable module <n> on loop <l>
0 R module <n> on loop <l> enabled
W enable module <n> on loop <l>
module.<l>.<n>.out 1 R module <n> on loop <l> output active (ON)
W turn ON out of module <n> on loop <l>
0 R module <n> on loop <l> output not active (OFF)
W turn OFF out of module <n> on loop <l>
module.<l>.<n>.fault v R module <n> on loop <l> fault (see modules fault error table below)
0 R module <n> on loop <l> no fault
module.<l>.<n>.alarm 1 R module <n> on loop <l> alarm
0 R module <n> on loop <l> no alarm
panel.fault.batt.disconn 1 R batteries disconnected
0 R batteries connected
panel.fault.power 1 R mains power failure
0 R mains power ok
panel.fault.supply.main (O) 1 R main power supply failure
0 R main power supply ok
panel.fault.supply.aux (O) 1 R aux power supply failure
0 R aux power supply ok
panel.fault.supply.aux.disc (O) 1 R aux power supply disconnected
0 R aux power supply not disconnected
panel.fault.supply.aux.not.prg (O) 1 R aux power supply not programmed
0 R aux power supply programmed
panel.fault.batt.unbal 1 R battery charger unbalance detected
0 R battery charger unbalance not detected
panel.fault.batt.fail 1 R battery failure detected
0 R battery failure not detected
panel.fault.batt.low (O) 1 R battery low voltage detected
0 R battery low voltage not detected
panel.fault.bex 1 R battery exhausted detected
0 R battery exhausted not detected
panel.fault.earth 1 R ground connection fault
0 R no ground connection fault
panel.fault.undervoltage 1 R AC power under-voltage fault
0 R no AC power under-voltage fault
panel.fault.overvoltage 1 R AC power over-voltage fault
0 R no AC power over-voltage fault
panel.fault.siren.open 1 R siren line wire cut detected
0 R siren line wire cut not detected
panel.fault.siren.short 1 R siren line short circuit detected
0 R siren line short circuit not detected
panel.fault.fuse 1 R fuse fault
0 R fuse ok
panel.fault.batt.charger.undervoltage 1 R battery charger under-voltage fault
0 R no battery charger under-voltage fault
panel.fault.batt.charger.overvoltage 1 R battery charger over-voltage fault
0 R no battery charger over-voltage fault
panel.filesystem.clear.error (N) 1 R memory delete error
0 R no memory delete error
panel.filesystem.init.error (N) 1 R memory initialization error
0 R no memory initialization error
panel.reliab.par.mod 1 R reliability parameters modified warning
0 R no reliability parameters modified warning
panel.hardkey.enabled 1 R hardware programming key enabled
0 R hardware programming key not enabled
panel.power.on 1 R power on phase
0 R power on phase completed
panel.wdt.reset 1 R main CPU watchdog fault
0 R main CPU watchdog ok
panel.cfg.error (N) 1 R configuration error
0 R configuration ok
panel.filesystem.error (N) 1 R memory corruption
0 R memory ok
panel.hard.clock (N) 1 R internal hardware clock fault
0 R internal hardware clock ok
panel.arch.full (N) 1 R log archive full
0 R log archive not full
panel.arch.full.warning (N) 1 R log archive warning (80% full)
0 R no log archive warning
panel.zone.default (N) 1 R sensors/modules not yet assigned to zones
0 R zones/modules assignment done
panel.sib.offline (N) 1 R SIB board offline
0 R SIB board online
panel.sib.not.prg (N) 1 R SIB board not programmed
0 R SIB board programmed
panel.pc.invalid.cmd (N) 1 R invalid command from PC
0 R no invalid command from PC
panel.arch.disabled 1 R log archive disabled
0 R log archive enabled
panel.lib.<n>.offline 1 R LIB board <n> offline
0 R LIB board <n> online
panel.lib.<n>.cfg.error 1 R LIB board <n> configuration error
0 R LIB board <n> configured
panel.lib.<n>.not.prg 1 R LIB board <n> not programmed
0 R LIB board <n> programmed
panel.fire silence W fire alarm silence
reset W fire alarm reset
activate W output re-activation
ack W acknowledge
panel.fire.normal 1 R fire panel normal state
0 R fire panel error state
panel.fire.exclusions 1 R fire panel has one or more disabled components
0 R fire panel’s all components are enabled
panel.fire.test 1 R fire panel test
0 R fire panel no test
panel.fire.fault 1 R fire panel fault
0 R fire panel no fault
panel.fire.alarm 1 R fire panel alarm
0 R fire panel no alarm
panel.fire.alarm.silent 1 R fire panel alarm silenced
0 R fire panel no alarm silenced
panel.fire.ack 1 R fire panel with events requing acknowledgement
0 R fire panel with no events requing acknowledgement
panel.tech (N) silence W technical alarm silence
reset W technical alarm reset
activate W output re-activation
ack W acknowledge
panel.tech.normal (N) 1 R technical panel normal state
0 R technical panel error state
panel.tech.exclusions (N) 1 R technical panel has one or more disabled components
0 R technical panel’s all components are enabled
panel.tech.test (N) 1 R technical panel test
0 R technical panel no test
panel.tech.fault (N) 1 R technical panel fault
0 R technical panel no fault
panel.tech.alarm (N) 1 R technical panel alarm
0 R technical panel no alarm
panel.tech.ack (N) 1 R technical panel with events requing acknowledgement
0 R technical panel with no events requing acknowledgement
sensor.<l>.<n>.normal 1 R sensor <n> on loop <l> normal state
0 R sensor <n> on loop <l> error state
sensor.<l>.<n>.disabled 1 R sensor <n> on loop <l> disabled
W disable sensor <n> on loop <l>
0 R sensor <n> on loop <l> enabled
W enable sensor <n> on loop <l>
sensor.<l>.<n>.prealarm.1 1 R sensor <n> on loop <l> pre-alarm 1
0 R sensor <n> on loop <l> pre-alarm 1 off
sensor.<l>.<n>.prealarm.2 1 R sensor <n> on loop <l> pre-alarm 2
0 R sensor <n> on loop <l> pre-alarm 2 off
sensor.<l>.<n>.fault v R sensor <n> on loop <l> fault (see sensors fault error table below)
0 R sensor <n> on loop <l> no fault
sensor.<l>.<n>.alarm 1 R sensor <n> on loop <l> alarm
0 R sensor <n> on loop <l> no alarm
sensor.<l>.<n>.analog v R sensor <n> on loop <l> analog value
zone.<n>.normal 1 R zone <n> normal state
0 R zone <n> error state
zone.<n>.disabled 1 R zone <n> disabled
W disable zone <n>
0 R zone <n> enabled
W enable zone <n>
zone.<n>.fault 1 R zone <n> fault
0 R zone <n> no fault
zone.<n>.alarm 1 R zone <n> alarm
0 R zone <n> no alarm

Modules fault values for input modules

The value v of the fault data point can be the combination (sum) of multiple error values.

Value ID Description
1 EDEINST not installed
4 EINV not responding
8 EFAULTTYPEID type id fault
32 ESHORT or ECUT short circuit or wire cut
64 ETAMP tamper alarm

Modules fault values for output modules

The value v of the fault data point can be the combination (sum) of multiple error values.

Value ID Description
1 EDEINST not installed
4 EINV not responding
8 EFAULTTYPEID type id fault
32 ESHORT short circuit
64 ECUT wire cut

Sensors fault values for generic sensors

The value v of the fault data point can be the combination (sum) of multiple error values.

Value ID Description
1 EDEINST not installed
4 EINV not responding
8 EFAULTTYPEID type id fault
16 EDRIFT drift warning (75% of alarm for >10 minute)
32 EMAINT dirt sensor warning (80% of alarm for >36 hours)
64 ELOW low chamber value fault (<20% of alarm)

Sensors fault values for GASS or OXY sensors

The value v of the fault data point can be the combination (sum) of multiple error values.

Value ID Description
1 EDEINST not installed
4 EINV not responding
8 EFAULTTYPEID type id fault
64 ELOW low chamber value fault

User Interface

UISET

You can use any object that accepts a text attribute, usually text, but also marquee and others, to display the status of the system according to the following table:

ID Attribute Set to
log value a textual log of all relevant events. The last event is at the top, with older events scrolled down, then removed from the log past the log lines limit
log0 value latest line of the security log when a new entry is added, set back to blank after a short period
offline.label visible true when HSYCO can’t connect to the Notifier panel, false otherwise
annunciator.<n>.<m>.offline.label visible true when annunciator <n>.<m> is offline
annunciator.<n>.<m>.fault.label visible true when annunciator <n>.<m> fault
annunciator.<n>.<m>.cfg.error.label visible true when annunciator <n>.<m> has a configuration error
lcd.offline.label visible true when LCD is offline (old protocol only)
lcd.<n>.offline.label visible true when LCD <n> is offline
lcd.<n>.fault.label visible true when LCD <n> is showing a fault condition
lcd.<n>.cfg.error.label visible true when LCD <n> has a configuration error
loop.<n>.short.label visible true when loop <n> short circuit
loop.<n>.open.label visible true when loop <n> is open
loop.<n>.voltage.label visible true when loop <n> voltage is too low
module.<l>.<n>.normal.label visible true when module <n> on loop <l> normal state
module.<l>.<n>.disabled.label visible true when module <n> on loop <l> disabled
module.<l>.<n>.out.label visible true when module <n> on loop <l> output is ON
module.<l>.<n>.fault.label visible true when module <n> on loop <l> fault
module.<l>.<n>.alarm.label visible true when module <n> on loop <l> alarm
panel.fire.normal.label visible true when fire panel normal state
panel.fire.exclusions.label visible true when fire panel has one or more disabled components
panel.fire.test.label visible true when fire panel test mode
panel.fire.fault.label visible true when fire panel fault
panel.fire.alarm.label visible true when fire panel alarm
panel.tech.normal.label visible true when technical panel normal state
panel.tech.exclusions.label visible true when technical panel has disabled components
panel.tech.test.label visible true when technical panel test mode
panel.tech.fault.label visible true when technical panel fault
panel.tech.alarm.label visible true when technical panel alarm
sensor.<l>.<n>.normal.label visible true when sensor <n> on loop <l> normal state
sensor.<l>.<n>.disabled.label visible true when sensor <n> on loop <l> disabled
sensor.<l>.<n>.prealarm.1.label visible true when Sensor <n> on loop <l> pre-alarm 1
sensor.<l>.<n>.prealarm.2.label visible true when Sensor <n> on loop <l> pre-alarm 2
sensor.<l>.<n>.fault.label visible true when sensor <n> on loop <l> fault
sensor.<l>.<n>.alarm.label visible true when sensor <n> on loop <l> alarm
zone.<n>.normal.label visible true when zone <n> normal state
zone.<n>.disabled.label visible true when zone <n> disabled
zone.<n>.fault.label visible true when zone <n> fault
zone.<n>.alarm.label visible true when zone <n> alarm

USER Commands

You can use the user object, or any other GUI object that generates user events, to execute any command that could be sent writing to a data point, as defined in the | Datapoints table. Set the user object’s name field to the datapoint (event) name, prefixed by the IO Server id, and its param field to the value that should be written to execute the command.

For example, to disable zone 1, use the following object:

(user fire.zone.1.disabled; 1; r4c2; gr; zone 1 off)

To enable zone 1:

(user fire.zone.1.disabled; 0; r4c3; gr; zone 1 on)

Release Notes

3.6.0

  • adds support for old AM-x000 firmware versions
  • new data points: detected.loops, detected.sensors.<loop>, detected.modules.<loop>, detected.lcds, detected.annunciators
  • data point panel.fire.unknown renamed panel.fire.ack
  • data point panel.fault.loop.open renamed panel.fault.siren.open
  • data point panel.fault.loop.short renamed panel.fault.siren.short

3.5.1

  • minor changes to the sensor.<l>.<n>.fault data point
  • new "activate" and "ack" commands to the panel.fire data point

3.3.0

  • initial release


Honeywell and Notifier are registered trademarks owned by Honeywell International Inc., or its subsidiaries or affiliates.