Protege is a server based architecture enabling you to securely manage, control and monitor a number of users, doors, areas, and other devices. The integration with HSYCO can be accomplished with a TCP/IP network connection.
ProtegeGXServer needs to be configured to accept a connection on a defined TCP/IP port with the ICT Automation and Control Service protocol. A PIN must be set (4 to 6 digits) Disable encryption and checksum Select Little Endian format Enable Login Block after PIN error
HSYCO Configuration
Add a PROTEGE I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- IP Address: the ICT Protege Server panel address
- IP Port: TCP/IP port enabled on the ICT Protege Server
High Availability
- Shutdown when inactive: defaults to true.
Options
ID | Default | Values | Description |
---|---|---|---|
pin | pin | the user PIN that the driver uses when sending commands to the Protege system. It must be a valid user code, able to engage and disengage the panel. | |
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
gui | true | true | enable support of the tecnoalarm Web interface object |
false | disable support of the tecnoalarm Web interface object | ||
debug | false | true | generates additional logs that can be viewed in verbose mode |
false | debug logging disabled | ||
areaslist | string | list of all the areas that are declared on the panel. Areas could not be consecutive and special characters "-" and ";" are used for intervals definition. E.G. 0-3;5-9 means areas from 0 to 3, from 5 to 9. E.G. 4;15 means area number 4 and number 15 | |
polltime | 1000 | n ≥ 0 | the data polling interval, in milliseconds. Shorter time improve the response of the system, but increase the load on the CPU of both HSYCO and the Tecnoalarm system |