Difference between revisions of "Dea Xensity"
Jump to navigation
Jump to search
(Created page with "DEA XENSITY is a Point ID intrusion detection system using special piezoelectric sensors for the protection of doors, windows, glass surfaces, security grilles and walls. [...") |
|||
Line 7: | Line 7: | ||
DEA XENSITY panels can be connected via ethernet. A valid IP address must be assigned to the controller using the configuration software. | DEA XENSITY panels can be connected via ethernet. A valid IP address must be assigned to the controller using the configuration software. | ||
+ | |||
{{tip| In case of multiple DEA XENSITY IO Servers running on the same HSYCO Server you must assign a different UDP port to each XENSITY driver.}} | {{tip| In case of multiple DEA XENSITY IO Servers running on the same HSYCO Server you must assign a different UDP port to each XENSITY driver.}} | ||
Revision as of 09:50, 23 March 2020
DEA XENSITY is a Point ID intrusion detection system using special piezoelectric sensors for the protection of doors, windows, glass surfaces, security grilles and walls.
Contents
Communication
DEA XENSITY panels can be connected via ethernet. A valid IP address must be assigned to the controller using the configuration software.
In case of multiple DEA XENSITY IO Servers running on the same HSYCO Server you must assign a different UDP port to each XENSITY driver.
HSYCO Configuration
Add a XENSITY I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- Address: IP address of the XENSITY controller (mandatory)
- Port: UDP port (mandatory)
High Availability
- Shutdown when inactive: defaults to false.
Options
ID | Default | Values | Description |
---|---|---|---|
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
unitid | 1 | > 0 | MODBUS unit ID of the KILSEN panel |
nodes | 1 | nodes list. Multiple nodes should be separated by semicolons | |
loopsnumber | 1 | > 0 | total number of loops |
sensorsnsumber | 1 | 0 ... 128 | set to the highest sensor number configured in the panel |
modulesnumber | 1 | 0 ... 128 | set to the highest module number configured in the panel |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
reset | 1 | W | panel reset |
reset | 1 | W | panel reset |
panel.silence | 1 | W | silence panel |
sounders.set | 0 | W | stop sounders |
1 | W | start sounders | |
global.alarm | 0 | R | no alarm |
1 | R | at lest one sensor of module on alarm | |
global.fault | 0 | R | no faults |
1 | R | at lest one sensor of module on fault status | |
global.disable | 0 | R | no sensors of modules disabled |
1 | R | at lest one sensor of module is disabled | |
global.test | 0 | R | panel in not in test mode |
1 | R | panel is in test mode | |
global.daynight | 0 | R | panel in day mode |
1 | R | panel is night mode | |
global.mcpalarm | 0 | R | mcp alarm off |
1 | R | mcp alarm on | |
global.sounder.delay.enabled | 0 | R | sounders delay disabled |
1 | R | sounders delay enabled | |
global.sounder.delay.in.progress | 0 | R | sounders delay not in progress |
1 | R | sounders delay in progress | |
global.sounder.outputs.activated | 0 | R | sounders outputs not active |
1 | R | sounders outputs active | |
global.sounder.outputs.silenced | 0 | R | sounders outputs not silenced |
1 | R | sounders outputs silenced | |
global.sounder.disabled | 0 | R | sounders are enabled |
1 | R | sounders are disabled | |
global.sounder.override.time.elapsed | 0 | R | override sounders time is not elapsed |
1 | R | ovveride sounders time elapsed | |
global.sounder.in.test | 0 | R | sounders not in test |
1 | R | sounders in test | |
global.fire.routing.delay.enabled | 0 | R | fire routing delay not enabled |
1 | R | fire routing delay enabled | |
global.fire.routing.delay.in.progress | 0 | R | fire routing delay not in progress |
1 | R | fire routing in progress | |
global.fire.routing.ouputs.activated | 0 | R | fire routing outputs not activated |
1 | R | fire routing outputs activated | |
global.fire.routing.ack | 0 | R | fire routing not in ack |
1 | R | fire routing ack | |
global.fire.routing.disabled | 0 | R | fire routing enabled |
1 | R | fire routing disabled | |
global.fire.routing.test.on | 0 | R | fire routing test is off |
1 | R | fire routing test on | |
global.fire.routing.ext.delay.in.progress | 0 | R | fire routing ext delay not in progress |
1 | R | fire routing ext delay in progress | |
node.<n>.loop.<l>.sensor.<s>.prealarm | 0 | R | not in prealarm |
1 | R | prealarm | |
node.<n>.loop.<l>.sensor.<s>.alarm | 0 | R | not in alarm |
1 | R | alarm | |
node.<n>.loop.<l>.sensor.<s>.fault | 0 | R | not in fault |
1 | R | fault | |
node.<n>.loop.<l>.sensor.<s>.test | 0 | R | not in test |
1 | R | in test | |
node.<n>.loop.<l>.sensor.<s>.dis | 0 | R | enabled |
1 | R | disabled | |
node.<n>.loop.<l>.module.<s>.prealarm | 0 | R | not in prealarm |
1 | R | prealarm | |
node.<n>.loop.<l>.module.<s>.alarm | 0 | R | not in alarm |
1 | R | alarm | |
node.<n>.loop.<l>.module.<s>.fault | 0 | R | not in fault |
1 | R | fault | |
node.<n>.loop.<l>.module.<s>.test | 0 | R | not in test |
1 | R | in test | |
node.<n>.loop.<l>.module.<s>.dis | 0 | R | enabled |
1 | R | disabled |
Release Notes
3.7.0
- initial release