Difference between revisions of "Dea Xensity"
Line 74: | Line 74: | ||
|0 | |0 | ||
|R | |R | ||
− | | | + | |no alarms |
|- | |- | ||
|1 | |1 | ||
|R | |R | ||
− | | | + | |at least one zone of this controller on alarm |
|- | |- | ||
− | |rowspan="2" | | + | |rowspan="2" |link.x16 |
|0 | |0 | ||
|R | |R | ||
− | | | + | |Connection with X16-ER16L is not stable |
|- | |- | ||
|1 | |1 | ||
|R | |R | ||
− | | | + | |Connection with X16-ER16L is stable |
|- | |- | ||
− | |rowspan="2" | | + | |rowspan="2" |link.sens |
|0 | |0 | ||
|R | |R | ||
− | | | + | |Connection with sensors is not stable |
|- | |- | ||
|1 | |1 | ||
|R | |R | ||
− | || | + | ||Connection with sensors is stable |
|- | |- | ||
− | |rowspan="2" | | + | |rowspan="2" |bus.power |
|0 | |0 | ||
|R | |R | ||
− | | | + | |Bus sensors power supply not ok |
|- | |- | ||
|1 | |1 | ||
|R | |R | ||
− | | | + | |Bus sensors power supply ok |
|- | |- | ||
− | |rowspan="2" | | + | |rowspan="2" |alarm.nf |
|0 | |0 | ||
|R | |R | ||
Line 119: | Line 119: | ||
|1 | |1 | ||
|R | |R | ||
− | | | + | |At least one alarm is active - not filtered- |
|- | |- | ||
Revision as of 11:31, 23 March 2020
DEA XENSITY is a Point ID intrusion detection system using special piezoelectric sensors for the protection of doors, windows, glass surfaces, security grilles and walls. This driver is compatible with the following controllers: Xensity128, Xensity64, Xensity32. Make sure to install the latest available firmware.
Contents
Communication
DEA XENSITY panels can be connected via ethernet. A valid IP address must be assigned to the controller using the configuration software.
In case of multiple DEA XENSITY IO Servers running on the same HSYCO Server you must assign a different UDP port to each XENSITY driver
HSYCO Configuration
Add a XENSITY I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- Address: IP address of the XENSITY controller (mandatory)
- Port: UDP port (mandatory)
High Availability
- Shutdown when inactive: defaults to false.
Options
ID | Default | Values | Description |
---|---|---|---|
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
pollinterval | 1000 | n ≥ 0 | the data polling interval, in milliseconds. Shorter time improve the response of the system, but increase the load on the CPU of both HSYCO and the Xensity system |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
alarm | 0 | R | no alarms |
1 | R | at least one zone of this controller on alarm | |
link.x16 | 0 | R | Connection with X16-ER16L is not stable |
1 | R | Connection with X16-ER16L is stable | |
link.sens | 0 | R | Connection with sensors is not stable |
1 | R | Connection with sensors is stable | |
bus.power | 0 | R | Bus sensors power supply not ok |
1 | R | Bus sensors power supply ok | |
alarm.nf | 0 | R | panel in not in test mode |
1 | R | At least one alarm is active - not filtered- | |
global.daynight | 0 | R | panel in day mode |
1 | R | panel is night mode | |
global.mcpalarm | 0 | R | mcp alarm off |
1 | R | mcp alarm on | |
global.sounder.delay.enabled | 0 | R | sounders delay disabled |
1 | R | sounders delay enabled | |
global.sounder.delay.in.progress | 0 | R | sounders delay not in progress |
1 | R | sounders delay in progress | |
global.sounder.outputs.activated | 0 | R | sounders outputs not active |
1 | R | sounders outputs active | |
global.sounder.outputs.silenced | 0 | R | sounders outputs not silenced |
1 | R | sounders outputs silenced | |
global.sounder.disabled | 0 | R | sounders are enabled |
1 | R | sounders are disabled | |
global.sounder.override.time.elapsed | 0 | R | override sounders time is not elapsed |
1 | R | ovveride sounders time elapsed | |
global.sounder.in.test | 0 | R | sounders not in test |
1 | R | sounders in test | |
global.fire.routing.delay.enabled | 0 | R | fire routing delay not enabled |
1 | R | fire routing delay enabled | |
global.fire.routing.delay.in.progress | 0 | R | fire routing delay not in progress |
1 | R | fire routing in progress | |
global.fire.routing.ouputs.activated | 0 | R | fire routing outputs not activated |
1 | R | fire routing outputs activated | |
global.fire.routing.ack | 0 | R | fire routing not in ack |
1 | R | fire routing ack | |
global.fire.routing.disabled | 0 | R | fire routing enabled |
1 | R | fire routing disabled | |
global.fire.routing.test.on | 0 | R | fire routing test is off |
1 | R | fire routing test on | |
global.fire.routing.ext.delay.in.progress | 0 | R | fire routing ext delay not in progress |
1 | R | fire routing ext delay in progress | |
node.<n>.loop.<l>.sensor.<s>.prealarm | 0 | R | not in prealarm |
1 | R | prealarm | |
node.<n>.loop.<l>.sensor.<s>.alarm | 0 | R | not in alarm |
1 | R | alarm | |
node.<n>.loop.<l>.sensor.<s>.fault | 0 | R | not in fault |
1 | R | fault | |
node.<n>.loop.<l>.sensor.<s>.test | 0 | R | not in test |
1 | R | in test | |
node.<n>.loop.<l>.sensor.<s>.dis | 0 | R | enabled |
1 | R | disabled | |
node.<n>.loop.<l>.module.<s>.prealarm | 0 | R | not in prealarm |
1 | R | prealarm | |
node.<n>.loop.<l>.module.<s>.alarm | 0 | R | not in alarm |
1 | R | alarm | |
node.<n>.loop.<l>.module.<s>.fault | 0 | R | not in fault |
1 | R | fault | |
node.<n>.loop.<l>.module.<s>.test | 0 | R | not in test |
1 | R | in test | |
node.<n>.loop.<l>.module.<s>.dis | 0 | R | enabled |
1 | R | disabled |