DETNOV are multi-area fire panels. The integration with HSYCO can be accomplished via a standard Modbus TCP/IP connection. This I/O server was developed following the MODBUS documentation MODBUS REGISTERS FOR DETNOV ADDRESSABLE SYSTEM VERSION 1.11 ENG
This driver has been tested on DETNOV CAD-150-2 panel.
Contents
Communication
DETNOV panels can be connected via ethernet. A valid IP address must be assigned to the panel. MODBUS PROTOCOL must be enabled. Please refer to the manual for detailed instruction about MODBUS protocol configuration.
HSYCO Configuration
Add a DETNOV I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- Address: IP address of the DETNOV panel
- Port: TCP/IP port for MODBUS communication (default 502)
High Availability
- Shutdown when inactive: defaults to false.
Options
ID | Default | Values | Description |
---|---|---|---|
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
unitid | 1 | > 0 | MODBUS unit ID of the DETNOV panel |
pollingtime | 3000 | n >= 3000 | the data polling interval, in milliseconds. |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
reset | 1 | W | panel reset |
mute | 1 | W | panel mute |
sounderson | 1 | W | enable sounders |
soundersoff | 1 | W | disable sounders |
info.modbus.status | 0 | R | modbus is disconnected |
1 | R | modbus slave is connected | |
global.fault | 0 | R | no faults |
1 | R | at lest one sensor of module on fault status | |
global.disable | 0 | R | no sensors of modules disabled |
1 | R | at lest one sensor of module is disabled | |
global.test | 0 | R | panel in not in test mode |
1 | R | panel is in test mode | |
global.daynight | 0 | R | panel in day mode |
1 | R | panel is night mode | |
global.mcpalarm | 0 | R | mcp alarm off |
1 | R | mcp alarm on | |
global.sounder.delay.enabled | 0 | R | sounders delay disabled |
1 | R | sounders delay enabled | |
global.sounder.delay.in.progress | 0 | R | sounders delay not in progress |
1 | R | sounders delay in progress | |
global.sounder.outputs.activated | 0 | R | sounders outputs not active |
1 | R | sounders outputs active |