The HID Edge Solo ESR40, ESRP40, ES400 are single-door IP access control solutions.

This I/O Server allows the integration of HID Edge Solo devices by using a TCP/IP connection.

More than one device can be controlled at the same time.

HID Edge Solo Configuration

The HID Edge Solo can be connected to a POE switch or to a normal ethernet switch. In this case the power supply must be provided with an external adapter. First of all, assign a static IP address to the Edge Solo, then it’s mandatory to disable the SSL/TLS encryption in the installer settings interface.

Hidedgesolo1.png

HSYCO Configuration

Add an HIDEDGESOLO I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • IP Address: IP address configured on the device
  • IP Port: TCP/IP port to use, leave blank for default port 80.

Authentication

  • User: username set in the installer settings
  • Password: password set in the installer settings.

High Availability

  • Shutdown when inactive: defaults to true.

Datapoints

If two readers are connected to the Edge Solo controller, the reader specific data points have a 0. or 1. prefix to identify each reader.

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
card.notfound <code> R badge <code> not found
pin.notfound <pin> R <pin> not found
access.granted <surname> R access granted to the user with surname <surname>
access.granted.extended <surname> R access granted extended to the user with surname <surname>
access.denied.schedule <surname> R access denied because badge/pin of the user <surname> was used outside scheduled time interval
access.denied.expired <surname> R access denied because badge/pin of the user <surname> is expired
card.notassigned <code> R access denied because the badge <code> is not assigned to an user.
access.denied.pin.expired <surname> R access denied because the pin assigned to the user <surname> is expired
alarm.acknowledged 0 R alarms reset
1 R normal conditions
door.lock.schedule false R normal conditions
true R door locked with a scheduled command
door.unlock.schedule false R normal conditions
true R door unlocked with a scheduled command
alarm.door.forced unset R normal conditions
set R door forced alarm
alarm.tamper unset R normal conditions
set R tamper alarm
access.granted.manual false R normal conditions
true R manual access granted
door.unlock false R normal conditions
true R door unlocked
state.alarm.tamper unset R normal conditions
set R tamper alarm
state.alarm.ac unset R normal conditions
set R power supply failure
state.alarm.battery unset R normal conditions
set R battery failure
state.alarm.door.held unset R normal conditions
set R door held
state.alarm.door.forced unset R normal conditions
set R door forced
state.name <name> R the door's name
state.relay unset R door relay closed
set R door relay open
state.relay.alert unset R alert relay not active
set R alert relay active
state.relay.aux unset R aux relay not active
set R aux relay active
command.access grant W grant the access
command.door lock W lock the door
unlock W unlock the door
command.alarm stop W alarms reset

Release Notes

3.6.0

  • added support for firmware version 2.0

3.4.0

  • added support for two readers door controller

3.0.0

  • initial release


HID is a registered trademark of HID Global.