Difference between revisions of "Boschmap"

From HSYCO
Jump to navigation Jump to search
Line 88: Line 88:
  
 
|-
 
|-
 +
 +
|<siid>.name
 +
|<name>
 +
|R
 +
|the name of the area/zone is set to <name>
 +
 +
|-
 +
 +
|rowspan="23" |<area_siid>.armed
 +
|rowspan="2" |0
 +
|R
 +
|area disarmed
 +
|-
 +
|W
 +
|disarm the area
 +
|-
 +
|rowspan="2" |1
 +
|R
 +
|area all armed, delayed
 +
|-
 +
|W
 +
|arm all the area, delayed
 +
|-
 +
|rowspan="2" |2
 +
|R
 +
|area all armed, delayed with bypass
 +
|-
 +
|W
 +
|arm all the area, instant
 +
|-
 +
|rowspan="2" |3
 +
|R
 +
|area all armed, instant
 +
|-
 +
|W
 +
|arm the area partially, delayed
 +
|-
 +
|rowspan="2" |4
 +
|R
 +
|area al armed, instant with bypass
 +
|-
 +
|W
 +
|arm the area partially, instant
 +
|-
 +
|rowspan="2" |5
 +
|R
 +
|area partially armed, delayed
 +
|-
 +
|W
 +
|custom-arm the area, delayed
 +
|-
 +
|rowspan="2" |6
 +
|R
 +
|area partially armed, delayed with bypass
 +
|-
 +
|W
 +
|custom-arm the area, instant
 +
|-
 +
|rowspan="2" |7
 +
|R
 +
|area partially armed, instant
 +
|-
 +
|W
 +
|arm all the area, delay zero
 +
|-
 +
|rowspan="2" |8
 +
|R
 +
|area partially armed, instant with bypass
 +
|-
 +
|W
 +
|arm the area partially, delay zero
 +
|-
 +
|rowspan="2" |9
 +
|R
 +
|area custom armed, delayed
 +
|-
 +
|W
 +
|custom-arm the area, delay zero
 +
|-
 +
|10
 +
|R
 +
|area custom armed, delayed with bypass
 +
|-
 +
|11
 +
|R
 +
|area custom armed, instant
 +
|-
 +
|12
 +
|R
 +
|area custom armed, instant with bypass
 +
 +
|-
 +
 +
|rowspan="2" |<area_siid>.ready.arm.instant
 +
|0
 +
|R
 +
|the area is not ready to be armed instantly
 +
|-
 +
|1
 +
|R
 +
|the area is ready to be armed instantly
 +
 +
|-
 +
 +
|rowspan="2" |<area_siid>.ready.arm.delay
 +
|0
 +
|R
 +
|the area is not ready to be armed with delay
 +
|-
 +
|1
 +
|R
 +
|the area is ready to be armed with delay
 +
 +
|-
 +
 +
|rowspan="2" |<area_siid>.ready.disarm
 +
|0
 +
|R
 +
|the area is not ready to be disarmed
 +
|-
 +
|1
 +
|R
 +
|the area is ready to be disarmed
 +
 +
|-
 +
 +
|rowspan="2" |<area_siid>.force.instant
 +
|0
 +
|R
 +
|the area is not ready to be force armed instantly
 +
|-
 +
|1
 +
|R
 +
|the area is ready to be force armed instantly
 +
 +
|-
 +
 +
|rowspan="2" |<area_siid>.force.delay
 +
|0
 +
|R
 +
|the area is not ready to be force armed with delay
 +
|-
 +
|1
 +
|R
 +
|the area is ready to be force armed with delay
  
 
|}
 
|}

Revision as of 09:52, 22 September 2014

The Bosch MPA panels are multi-area intrusion detection systems.

The integration with HSYCO can be accomplished via Ethernet connection.

HSYCO Configuration

Add a BOSCHMPA I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • IP Address: IP address of the panel
  • IP Port: TCP/IP port to use, leave blank to use default port 6793.

Authentication

  • Password: password set on for the BIS user. Leave blank to use the default password.

High Availability

  • Shutdown when inactive: defaults to true.

Options

ID Default Values Description
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system

galaxy.ini

The boschmpa.ini file is a specific configuration file located in the root directory. This file is required to specify which areas and zones are configured on the panel and to assign them a name.

Add a new line for each area followed by a new line for each zone belonging to that area, using the following format:

<io_server_id>.<area_siid> = <name>
<io_server_id>.<zone_siid> = <name>

where <area_siid>/<zone_siid> is the security identifier of the area/zone as specified in the configuration software of the panel.

For instance:

bsc.1.1.ControlPanelArea.1.1 = Control Panel

bsc.1.1.Area.2.4 = Internal area
	bsc.1.1.Point.01001.006 = Front door
	bsc.1.1.Point.01001.007 = Back door

bsc.1.1.Area.2.5 = External area
	bsc.1.1.Point.01001.008 = Gate

specifies three areas: the Control Panel area with no zones, an internal area with two zones and an external area with one zone.

Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
<siid>.name <name> R the name of the area/zone is set to <name>
<area_siid>.armed 0 R area disarmed
W disarm the area
1 R area all armed, delayed
W arm all the area, delayed
2 R area all armed, delayed with bypass
W arm all the area, instant
3 R area all armed, instant
W arm the area partially, delayed
4 R area al armed, instant with bypass
W arm the area partially, instant
5 R area partially armed, delayed
W custom-arm the area, delayed
6 R area partially armed, delayed with bypass
W custom-arm the area, instant
7 R area partially armed, instant
W arm all the area, delay zero
8 R area partially armed, instant with bypass
W arm the area partially, delay zero
9 R area custom armed, delayed
W custom-arm the area, delay zero
10 R area custom armed, delayed with bypass
11 R area custom armed, instant
12 R area custom armed, instant with bypass
<area_siid>.ready.arm.instant 0 R the area is not ready to be armed instantly
1 R the area is ready to be armed instantly
<area_siid>.ready.arm.delay 0 R the area is not ready to be armed with delay
1 R the area is ready to be armed with delay
<area_siid>.ready.disarm 0 R the area is not ready to be disarmed
1 R the area is ready to be disarmed
<area_siid>.force.instant 0 R the area is not ready to be force armed instantly
1 R the area is ready to be force armed instantly
<area_siid>.force.delay 0 R the area is not ready to be force armed with delay
1 R the area is ready to be force armed with delay