Difference between revisions of "Strato"
Jump to navigation
Jump to search
(→3.5.0) |
|||
Line 35: | Line 35: | ||
|rowspan="2"|false | |rowspan="2"|false | ||
|true | |true | ||
− | |enables the hardware watchdog and automatically generates the heartbeat signal | + | |enables the hardware watchdog and automatically generates the heartbeat signal (use this option only with the Strato UPS board) |
|- | |- | ||
|false | |false | ||
Line 48: | Line 48: | ||
|- | |- | ||
|int > 0 | |int > 0 | ||
− | |the driver will command the operating system shutdown and hardware power off after N minutes of back-up battery operations during a power failure. The Strato board will automatically power-up the Pi when power is restored | + | |the driver will command the operating system shutdown and hardware power off after N minutes of back-up battery operations during a power failure. The Strato board will automatically power-up the Pi when power is restored (use this option only with the Strato UPS board) |
|- | |- |
Revision as of 12:04, 10 June 2016
Strato Pi is an expansion board developed by Sfera Labs for the Raspberry Pi computer.
Strato Pi implements a number of hardware features to expand the Pi and allows its use in professional applications:
- 9-28 Vdc extended-range power supply
- integrated UPS with external NiCd rechargeable battery
- real-time clock with dedicated back-up battery
- opto-isolated RS-232 or RS-485 serial port
- configurable hardware watchdog
- buzzer for audible feedback.
Contents
HSYCO Configuration
Add a STRATO I/O Server in the I/O Servers section of the Settings and set its parameters.
Note that the Strato I/O Server doesn't count in the I/O servers license total, so you don't need an extra I/O Server license to use Strato with HSYCO.
High Availability
- Shutdown when inactive: defaults to false.
Options
ID | Default | Values | Description |
---|---|---|---|
watchdog | false | true | enables the hardware watchdog and automatically generates the heartbeat signal (use this option only with the Strato UPS board) |
false | disables the hardware watchdog | ||
shutdown_minutes | 0 | 0 | no automatic shutdown after power failure |
int > 0 | the driver will command the operating system shutdown and hardware power off after N minutes of back-up battery operations during a power failure. The Strato board will automatically power-up the Pi when power is restored (use this option only with the Strato UPS board) | ||
quiet | false | true | enables audible alarms on power failure |
false | disables audible alarms on power failure |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
battery | 0 | R | power supply is available |
1 | R | power supply failure, running on UPS battery | |
beep | 0 | R | buzzer is off |
1 | R | buzzer is on | |
off | W | turn buzzer off | |
on | W | turn buzzer on (continuous tone) | |
<duration> | W | turn buzzer on for <duration> seconds (decimals allowed) | |
<duration>;<pause> | W | turn buzzer on for <duration> seconds, then pause for <pause> seconds (decimals allowed) | |
heartbeat | 0 | R | heartbeat line is off |
W | set heartbeat line to off | ||
1 | R | heartbeat line is on | |
W | set heartbeat line to on | ||
shutdown | 0 | R | shutdown line is off |
1 | R | shutdown line is on | |
W | set shutdown line to on (Strato will wait approximately 60 seconds, then execute a power off-on cycle. Once the shutdown line is set to on, the power cycle procedure can't be reset | ||
timeout | 0 | R | hardware watchdog timeout line is off |
1 | R | hardware watchdog timeout line is on. Strato will set this line to on, then wait approximately 60 seconds and execute a power off-on cycle | |
watchdog | 0 | R | hardware watchdog is disabled |
W | disables the hardware watchdog | ||
1 | R | hardware watchdog is enabled | |
W | enables the hardware watchdog. When enabled, Strato should see an off-on transition on the hearbeat line at least every 60 seconds, otherwise a power cycle will be initiated, setting the timeout line on, then waiting 60 seconds, removing power to the Pi for 5 seconds, and finally restoring power |
Release Notes
3.5.0
- initial release
Strato is a registered trademark of Home Systems Consulting S.p.A.