(Created page with "Airzone is a control framework for ducted air conditioning systems which allows for the control of several zones independently. This I/O server provides support for this Airzo...")
 
Line 4: Line 4:
  
 
== Communication ==
 
== Communication ==
 +
 +
Airzone communicates with HSYCO through a modbus connection employing a RS-485 gateway.
 +
 +
RS-485 parameters:
 +
{| class="wikitable"
 +
| '''Baud rate'''
 +
| same as configured on panel (default 9600)
 +
|-
 +
| '''Data bits'''
 +
| 8
 +
|-
 +
| '''Stop bit'''
 +
| 1
 +
|-
 +
| '''Parity'''
 +
| none
 +
|-
 +
| '''Flow control'''
 +
| none
 +
|}
 +
 +
== HSYCO Configuration ==
 +
 +
=== Options ===
 +
 +
{| class="wikitable"
 +
!ID
 +
!Default
 +
!Values
 +
!Description
 +
|-
 +
 +
|pin
 +
|
 +
|<nowiki><code></nowiki>
 +
|4 or 6-digits code. Use the specified PIN code to perform operations that require user authentication. If this option is not specified it will be required to manually insert the pin every time such operations are performed
 +
 +
|-
 +
 +
|rowspan="2"|gui
 +
|rowspan="2"|true
 +
|true
 +
|enable support for the UI object, UISET actions and USER commands
 +
|-
 +
|false
 +
|disable UI support
 +
 +
|-
 +
 +
|rowspan="2"|startupevents
 +
|rowspan="2"|false
 +
|true
 +
|generate IO events also during the driver’s start-up phase
 +
|-
 +
|false
 +
|start generating events only after HSYCO is aligned with the current status of the system
 +
 +
|-
 +
 +
|pollinterval
 +
|3
 +
|n > 0
 +
|the data acquisition interval, in seconds
 +
 +
|-
 +
 +
|logsize
 +
|20
 +
|n &ge; 0
 +
|the number of log lines to display in the UI object
 +
 +
|}

Revision as of 11:33, 7 January 2014

Airzone is a control framework for ducted air conditioning systems which allows for the control of several zones independently. This I/O server provides support for this Airzone systems: INNOBUS, FLEXA, ANTREE and CEN.

Communication

Airzone communicates with HSYCO through a modbus connection employing a RS-485 gateway.

RS-485 parameters:

Baud rate same as configured on panel (default 9600)
Data bits 8
Stop bit 1
Parity none
Flow control none

HSYCO Configuration

Options

ID Default Values Description
pin <code> 4 or 6-digits code. Use the specified PIN code to perform operations that require user authentication. If this option is not specified it will be required to manually insert the pin every time such operations are performed
gui true true enable support for the UI object, UISET actions and USER commands
false disable UI support
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
pollinterval 3 n > 0 the data acquisition interval, in seconds
logsize 20 n ≥ 0 the number of log lines to display in the UI object