Difference between revisions of "Kilsen"

From HSYCO
Jump to navigation Jump to search
Line 114: Line 114:
 
|-
 
|-
  
|sounders.set
+
|rowspan="2" |sounders.set
|0,1
+
|0
 
|W
 
|W
|1=start sounders, 0=stop sounder
+
|stop sounders
 
|-
 
|-
 +
|1
 +
|W
 +
|start sounders
 +
|-
 +
 +
 +
|rowspan="2" |global.alarm
 +
|0
 +
|R
 +
|at lest one sensor of module on alarm
 +
|-
 +
|1
 +
|R
 +
|no alarm
 +
|-
 +
 +
|rowspan="2" |global.fault
 +
|0
 +
|R
 +
|at lest one sensor of module on fault status
 +
|-
 +
|1
 +
|R
 +
|no faults
 +
|-
 +
 +
|rowspan="2" |global.disable
 +
|0
 +
|R
 +
|at lest one sensor of module is disabled
 +
|-
 +
|1
 +
|R
 +
|no sensors or modules disabled
 +
|-
 +
 +
|rowspan="2" |global.test
 +
|0
 +
|R
 +
|panel in test mode
 +
|-
 +
|1
 +
|R
 +
|panel is not in test mode
 +
|-
 +
 +
|rowspan="2" |global.daynight
 +
|0
 +
|R
 +
|panel in night mode
 +
|-
 +
|1
 +
|R
 +
|panel is day mode
 +
|-
 +
  
 
|}
 
|}

Revision as of 09:32, 19 April 2019

KILSEN KFP-A are multi-area fire panels. The integration with HSYCO can be accomplished via a standard Modbus TCP/IP connection. This I/O server was developed following the MODBUS documentation P/N 00-3243-505-1603-01 • ISS 14DEC15

IO Server Kilsen Panel.jpg

Communication

KILSEN panels can be connected via ethernet. A valid IP address must be assigned to the panel. MODBUS PROTOCOL must be enabled. Please refer to the manual for detailed instruction about MODBUS protocol configuration.

HSYCO Configuration

Add a KILSEN I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • Address: IP address of the KILSEN panel
  • Port: TCP/IP port for MODBUS communication (default 502)

High Availability

  • Shutdown when inactive: defaults to false.

Options

ID Default Values Description
gui true true enable support for the UI object, UISET actions and USER commands
false disable UI support
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
unitid 1 > 0 MODBUS unit ID of the KILSEN panel
nodes 1 nodes list. Multiple nodes should be separated by semicolons
loopsnumber 1 > 0 total number of loops
sensorsnsumber 1 0 ... 128 set to the highest sensor number configured in the panel
modulesnumber 1 0 ... 128 set to the highest module number configured in the panel


Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
reset 1 W panel reset
panel.silence 1 W silence panel
sounders.set 0 W stop sounders
1 W start sounders
global.alarm 0 R at lest one sensor of module on alarm
1 R no alarm
global.fault 0 R at lest one sensor of module on fault status
1 R no faults
global.disable 0 R at lest one sensor of module is disabled
1 R no sensors or modules disabled
global.test 0 R panel in test mode
1 R panel is not in test mode
global.daynight 0 R panel in night mode
1 R panel is day mode