Line 124: Line 124:
 
|-
 
|-
  
|rowspan="2" |global.test
+
|info.panel.version
|0
+
|<n>
 
|R
 
|R
|panel in not in test mode
+
|n is the version of the panel
|-
 
|1
 
|R
 
|panel is in test mode
 
|-
 
 
 
|rowspan="2" |global.daynight
 
|0
 
|R
 
|panel in day mode
 
|-
 
|1
 
|R
 
|panel is night mode
 
 
|-
 
|-
  
|rowspan="2" |global.mcpalarm
+
|info.panel.network.version
|0
+
|<n>
|R
 
|mcp alarm off
 
|-
 
|1
 
 
|R
 
|R
|mcp alarm on
+
|n is the network version of the panel
 
|-
 
|-
  
|rowspan="2" |global.sounder.delay.enabled
+
|info.panel.modbus.version
|0
+
|<n>
|R
 
|sounders delay disabled
 
|-
 
|1
 
 
|R
 
|R
|sounders delay enabled
+
|n is the modbus version of the panel
 
|-
 
|-
  
 
|rowspan="2" |global.sounder.delay.in.progress
 
|0
 
|R
 
|sounders delay not in progress
 
|-
 
|1
 
|R
 
|sounders delay in progress
 
|-
 
  
 
|rowspan="2" |global.sounder.outputs.activated
 
|rowspan="2" |global.sounder.outputs.activated

Revision as of 14:54, 28 December 2020

DETNOV are multi-area fire panels. The integration with HSYCO can be accomplished via a standard Modbus TCP/IP connection. This I/O server was developed following the MODBUS documentation MODBUS REGISTERS FOR DETNOV ADDRESSABLE SYSTEM VERSION 1.11 ENG

This driver has been tested on DETNOV CAD-150-2 panel. (Should be compatible with CAD 150-1, CAD 150-2, CAD 150-8, CAD 150-8+, CAD 150-4)

IO Server Detnov Panel.jpg

Communication

DETNOV panels can be connected via ethernet. A valid IP address must be assigned to the panel. MODBUS PROTOCOL must be enabled. Please refer to the manual for detailed instruction about MODBUS protocol configuration.

HSYCO Configuration

Add a DETNOV I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • Address: IP address of the DETNOV panel
  • Port: TCP/IP port for MODBUS communication (default 502)

High Availability

  • Shutdown when inactive: defaults to false.

Options

ID Default Values Description
gui true true enable support for the UI object, UISET actions and USER commands
false disable UI support
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
unitid 1 > 0 MODBUS unit ID of the DETNOV panel
pollingtime 3000 n >= 3000 the data polling interval, in milliseconds.


Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
reset 1 W panel reset
mute 1 W panel mute
sounderson 1 W enable sounders
soundersoff 1 W disable sounders
info.modbus.status 0 R modbus is disconnected
1 R modbus slave is connected
info.panel.type <n> R n=1,2 > CAD 150-1, CAD 150-2 n=4,8 > CAD 150-8, CAD 150-8+, CAD 150-4
info.panel.version <n> R n is the version of the panel
info.panel.network.version <n> R n is the network version of the panel
info.panel.modbus.version <n> R n is the modbus version of the panel
global.sounder.outputs.activated 0 R sounders outputs not active
1 R sounders outputs active

Release Notes

3.8.0

  • initial release