INIM PREVIDIA are multi-zone fire panels. The integration with HSYCO can be accomplished via a standard Modbus TCP/IP connection. This I/O server was developed following the MODBUS documentation INIM Guida all'integrazione con sistemi di supervisione
This driver has been tested on INIM PREVIDIA Ultra, Max and Compact panels.
Communication
INIM PREVIDIA panels can be connected via ethernet. A valid IP address must be assigned to the panel. MODBUS PROTOCOL must be enabled. Please refer to the manual for detailed instruction about MODBUS protocol configuration.
HSYCO Configuration
Add a INIMPREVIDIA I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- Address: IP address of the INIM PREVIDIA panel
- Port: TCP/IP port for MODBUS communication (default 502)
High Availability
- Shutdown when inactive: defaults to false.
Options
ID | Default | Values | Description |
---|---|---|---|
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
unitid | 1 | > 0 | MODBUS unit ID of the INIM PREVIDIA panel |
pollingtime | 1000 | n >= 1000, n <= 30000 | the data polling interval, in milliseconds. |
loopsnumber | 16 | n = 1..16 | the number of configured loops |
groupsnumber | 240 | n = 1..240 | the number of configured groups |
zonesnumber | 1000 | n = 1..1000 | the number of configured zones |
INIM PREVIDIA Compact panel requires loopsnumber set to 2