Difference between revisions of "RayCONTROL"
Line 367: | Line 367: | ||
|z<n>.mode | |z<n>.mode | ||
+ | |value | ||
|zone <n> operating mode:<br/> | |zone <n> operating mode:<br/> | ||
OFF: zone is off<br/> | OFF: zone is off<br/> | ||
Line 373: | Line 374: | ||
MAN: manual mode; constantly follows the temperature set-point<br/> | MAN: manual mode; constantly follows the temperature set-point<br/> | ||
MAINT: zone in maintenance mode | MAINT: zone in maintenance mode | ||
+ | |- | ||
|z<n>.lock | |z<n>.lock |
Revision as of 14:30, 20 March 2014
RayCONTROL 30 is the control unit for the FCC Planterm temperature control system.
RayCONTROL 30 supports up to 30 individual zones.
Contents
Communication
RayNET is an interface module that provides a standard Modbus/RTU interface over RS485 for RayCONTROL 30. The default connection parameters are:
Modbus address: 1
RS-485 parameters:
Baud rate | 9600 |
Data bits | 8 |
Stop bit | 1 |
Parity | none |
Flow control | none |
Refer to the RayNET and RayCONTROL 30 technical documentation for installation, wiring and power supply requirements.
HSYCO connects to the Modbus bus through any standard Modbus/TCP gateway.
HSYCO Configuration
Options
ID | Default | Values | Description |
---|---|---|---|
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
pollinterval | 30 | 1 ... 45 | the data acquisition interval, in seconds |
address | 1 | > 0 | the Modbus address of the RayCONTROL device |
readinterval | 25 | 0 ... 1000 | minimum interval between consecutive Modbus commands |
systems | 1 | 1 ... 2 | set to 1 if using only system 1; set to 2 is system 2 is used |
zones | 15 | 1 ... 30 | set to the highest zone number used |
sensivity | 5 | >0 | measured temperatures’ changes are reported only if the difference from last reading is equal or greater than the sensivity option, in 10th of Celsius degrees |
language | en | en, fr, it | the language used for text messages. If undefined, the global language option is used. English is used if the global language is also undefined |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
s<n>.status | off | R | system <n> is off |
W | turn off system <n> | ||
on | R | system <n> is on | |
W | turn on system <n> | ||
maint | R | system <n> is in maintenance mode | |
s<n>.mode | winter | R | system <n> is in winter mode |
W | set system <n> to winter mode | ||
summer | R | system <n> is in winter mode | |
W | set system <n> to summer mode | ||
towinter | R | system <n> is in summer mode, transitioning to winter mode | |
tosummer | R | system <n> is in winter mode, transitioning to summer mode | |
s<n>.setpoint.winter.max | 160 .. 300 | R | system <n> current maximum winter temperature set-point |
W | set system <n> maximum winter temperature set-point | ||
s<n>.setpoint.winter.min | 150 .. 290 | R | system <n> current minimum winter temperature set-point |
W | set system <n> minimum winter temperature set-point | ||
s<n>.setpoint.summer.max | 160 .. 300 | R | system <n> current maximum summer temperature set-point |
W | set system <n> maximum summer temperature set-point | ||
s<n>.setpoint.summer.min | 150 .. 290 | R | system <n> current minimum summer temperature set-point |
W | set system <n> minimum summer temperature set-point | ||
s<n>.temp.out | -400 ... +800 | R | outdoor temperature, in 10th of Celsius degrees (e.g. 210 corresponds to 21.0 °C) |
s<n>.temp.inlet | -400 ... +800 | R | inlet temperature, in 10th of Celsius degrees (e.g. 210 corresponds to 21.0 °C) |
z<n>.mode | off | R | zone <n> is off |
W | turn off zone <n> | ||
maint | R | zone <n> is in maintenance mode | |
eco | R | zone <n> is in energy saving mode | |
W | set zone <n> to energy saving mode | ||
pgm | R | zone <n> is in program mode | |
W | set zone <n> to program mode | ||
man | R | zone <n> is in manual mode | |
W | set zone <n> to manual mode | ||
on | W | set zone <n> to the mode set before last off (ECO, PGM or MAN). If HSYCO starts with the zone already off, the on command sets the mode to ECO | |
z<n>.lock | 0 | R | zone <n> is not locked |
W | unlock zone <n> | ||
1 | R | zone <n> is locked | |
W | lock zone <n> | ||
z<n>.temp | -400 ... 800 | R | measured temperature, in 10th of Celsius degrees (e.g. 210 corresponds to 21.0 °C) |
z<n>.humidity | 1... 100 | R | measured relative umidity, from 0 to 100 |
z<n>.setpoint.temp | 150 ... 300 | R | zone <n> set-point temperature, in 10th of Celsius degrees (e.g. 210 corresponds to 21.0 °C) |
W | zone <n> set-point temperature, in 10th of Celsius degrees (e.g. 210 corresponds to 21.0 °C) | ||
up | W | increase zone temperature set-point by 0.5 °C | |
down | W | decrease zone temperature set-point by 0.5 °C | |
alarm.<c> | 0 | R | alarm code C (1-72) inactive |
1 | R | alarm code C (1-72) active | |
alarm | 0 | R | no active alarms |
1 | R | the system is reporting at least one active alarm |
User Interface
UISET Actions
ID | Attribute | Set to | |
---|---|---|---|
s<n>.status | value | system <n> (1 or 2) status
| |
s<n>.mode | value | system <n> (1 or 2) mode:
| |
s<n>.temp.out | value | the outdoor measured temperature for system <n> (1 or 2), in Celsius degrees with one decimal digit, followed by " °C" | |
s<n>.temp.inlet | value | the inlet measured temperature for system <n> (1 or 2), in Celsius degrees with one decimal digit, followed by " °C" | |
z<n>.mode | value | zone <n> operating mode: OFF: zone is off | |
z<n>.lock | value | zone lock mode: LOCKED: zone is locked | |
z<n>.temp | value | the current temperature in Celsius degrees with one decimal digit, followed by " °C" | |
z<n>.humidity | value | the current relative humidity, from 0 to 100, followed by “ %” | |
z<n>.setpoint.temp | value | the zone temperature set-point in Celsius degrees with one decimal digit, followed by " °C" | |
alarm.<n> | text line <n> (1-30) of the alarms register, with start/end date and time and error code: “CODE NN: YYYY-MM-DD HH:MM:SS - YYYY-MM-DD HH:MM:SS”" | ||
alarm.label | value | alarm flag. This object is normally invisible, and made visible when the rayCONTROL reports at least one active alarm |
USER Commands
Name | Param | Action |
---|
Release Notes
3.3.0
- new data points: s<n>.setpoint.winter.max s<n>.setpoint.winter.min s<n>.setpoint.summer.max s<n>.setpoint.summer.min z<n>.lock
- new readinterval option (defaults to 20 msec.)
- improved communication errors handling
3.0.0
- full integration in HSYCO 3.0.0
RayCONTROL is a registered trademark of Permasteelisa Impianti srl, FCC Planterm Division.