Difference between revisions of "Hidedgesolo"

From HSYCO
Jump to navigation Jump to search
Line 223: Line 223:
 
|alarms reset
 
|alarms reset
 
|}
 
|}
 
== Examples ==
 
 
A valid pin is digit on the Wiegand keyboard of the EDGE SOLO. Here’s the HSYCO log:
 
<pre>
 
IO MONITOR EVENT: hid1.state.relay = unset
 
IO MONITOR FORCED: hid1.access.granted = Gaffuri
 
IO MONITOR EVENT: hid1.state.relay = set
 
IO MONITOR EVENT: hid1.state.relay = unset
 
</pre>
 
 
The relay is set, the access is granted for the user. They relay is set for a time specified in the EDGE SOLO settings.
 
 
Access granted from a user button. Here’s the HSYCO log:
 
<pre>
 
WEB USER COMMAND [hid1]: grant [OK]
 
IO MONITOR EVENT: command.access = grant
 
IO MONITOR EVENT: hid1.state.relay = set
 
IO MONITOR FORCED: hid1.access.granted.manual = true
 
IO MONITOR EVENT: hid1.state.relay = unset
 
</pre>
 
 
After the button is pressed the relay is set. The manuale access granted is reported in the log.
 
 
Door forced. Here’s the HSYCO log:
 
<pre>
 
IO MONITOR FORCED: hid1.alarm.door.forced = 1
 
IO MONITOR EVENT: hid1.state.alarm.door.forced = set
 
IO MONITOR EVENT: hid1.state.relay.aux = set
 
IO MONITOR EVENT: hid1.state.relay.alert = set
 
</pre>
 
 
To grant an access using a user button, open the Project Editor and create a new user button. Specify the following parameters:
 
 
[[File:hidedgesolo2.png]]
 
 
 
Name e param are used to call a spacific line in the events.txt file:
 
 
<pre>
 
io hid1.state.relay = set : UISET hid1.color = g
 
io hid1.state.relay = unset : UISET hid1.color = gr
 
user hid1=grant : io hid1.command.access=grant
 
</pre>
 
 
where hid1 is the id of the I/O server. The button color changes according to the relay state.
 

Revision as of 11:11, 7 January 2014

The HID Edge solo ESR40, ESRP40, ES400 are single-door IP access control solution. This driver allows the integration of HID Edge Solo devices by using a TCP/IP connection. More than one device can be controlled at the same time.

HID Edge Solo configuration

The HID Edge Solo can be connected to a POE switch or to a normal ethernet switch. In this case the power supply must be provided with an external adapter. First of all, assign an IP address to the Edge Solo, then it’s mandatory to disable the SSL/TLS encryption in the installer settings interface.

Hidedgesolo1.png

Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
card.notfound <code> R badge <code> not found
pin.notfound <pin> R <pin> not found
access.granted <surname> R access granted to the user with surname <surname>
access.granted.extended <surname> R access granted extended to the user with surname <surname>
access.denied.schedule <surname> R access denied because badge/pin of the user <surname> was used outside scheduled time interval
access.denied.expired <surname> R access denied because badge/pin of the user <surname> is expired
card.notassigned <code> R access denied because the badge <code> is not assigned to an user.
access.denied.pin.expired <surname> R access denied because the pin assigned to the user <surname> is expired
alarm.acknowledged 0 R alarms reset
1 R normal conditions
door.lock.schedule false R normal conditions
true R door locked with a scheduled command
door.unlock.schedule false R normal conditions
true R door unlocked with a scheduled command
alarm.door.forced unset R normal conditions
set R door forced alarm
alarm.tamper unset R normal conditions
set R tamper alarm
access.granted.manual false R normal conditions
true R manual access granted
door.unlock false R normal conditions
true R door unlocked
state.alarm.tamper unset R normal conditions
set R tamper alarm
state.alarm.ac unset R normal conditions
set R power supply failure
state.alarm.battery unset R normal conditions
set R battery failure
state.alarm.door.held unset R normal conditions
set R door held
state.alarm.door.held unset R normal conditions
set R door held
state.alarm.door.forced unset R normal conditions
set R door forced
state.relay unset R door relay closed
set R door relay open
state.relay.aux unset R the device is not in alarm state
set R the device is in alarm state
command.access grant W grant the access
command.door lock W lock the door
unlock W unlock the door
command.alarm stop W alarms reset