The Satel INTEGRA series comprises a variety of multi-area security systems. The integration with HSYCO can be accomplished via direct control through Ethernet connection. The I/O Server complies with the protocol INT-RS v2.13 2015-03-19 and has been tested on firmware version 1.14 2015-12-15.
Contents
Satel Configuration
TODO
HSYCO Configuration
Add a SATEL I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- IP Address: host name or IP address of the panel
- IP Port: TCP/IP port to use (as configured on the panel)
High Availability
- Shutdown when inactive: defaults to true.
Options
ID | Default | Values | Description |
---|---|---|---|
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
logsize | 20 | n ≥ 0 | the number of log lines to display in the UI object |
usercode | <user_code> | default user code to be used to send commands | |
maxzone | 1 ≤ n ≤ 256 | highest zone number configured on the panel | |
maxpartition | 1 ≤ n ≤ 32 | highest partition number configured on the panel | |
maxoutput | 1 ≤ n ≤ 256 | highest output number configured on the panel | |
maxdoor | 1 ≤ n ≤ 64 | highest door number configured on the panel |
Datapoints
ID | Value | R/W | Description |
---|---|---|---|
connection | online | R | connection established |
offline | R | HSYCO can't connect to the panel | |
armed | 0 | R | all groups are disarmed |
W | disarm all groups | ||
1 | R | the system is (partially) armed | |
W | arm all groups | ||
alarm | 0 | R | the system is not in a alarm state |
1 | R | the system is in a alarm state | |
tamper | 0 | R | the system is not in a tamper state |
1 | R | the system is in a tamper state | |
panel.tamper | 0 | R | the panel is not tampered |
1 | R | the panel is tampered | |
bell.tamper | 0 | R | the bell is not tampered |
1 | R | the bell is tampered | |
low.volts | 0 | R | voltage ok |
1 | R | low voltage detected | |
sounder | 0 | R | the sounder is inactive |
1 | R | the sounder is active | |
audio | 0 | R | the audio signal of the panel is inactive |
1 | R | the audio signal of the panel is active | |
strobe | 0 | R | the strobe is inactive |
1 | R | the strobe is active | |
mains.fail | 0 | R | no mains fail |
1 | R | mains fail | |
power.fail | 0 | R | no power fail |
1 | R | power fail | |
battery.fail | 0 | R | no battery fail |
1 | R | battery fail | |
fuse.1.fault | 0 | R | fuse 1 is working |
1 | R | fuse 1 in fault | |
fuse.2.fault | 0 | R | fuse 2 is working |
1 | R | fuse 2 in fault | |
fuse.3.fault | 0 | R | fuse 3 is working |
1 | R | fuse 3 in fault | |
line.fault | 0 | R | communication line is working |
1 | R | communication line in fault | |
c<n>.name | <text> | R | the name of circuit <n> is set to <text> |
g<n>.name | <text> | R | the name of group <n> is set to <text> |
g<n>.armed | 0 | R | group <n> is disarmed |
W | disarm group <n> | ||
1 | R | group <n> is armed | |
W | arm group <n> | ||
c<n>.alarm | 0 | R | circuit <n> is not in alarm state |
1 | R | circuit <n> is in alarm state | |
c<n>.tamper.alarm | 0 | R | circuit <n> is not in tamper alarm |
1 | R | circuit <n> is in tamper alarm | |
c<n>.open | 0 | R | circuit <n> is closed |
1 | R | circuit <n> is open | |
c<n>.tamper | 0 | R | circuit <n> is not tampered |
1 | R | circuit <n> is tampered | |
c<n>.fault | 0 | R | circuit <n> is working properly |
1 | R | circuit <n> is faulty | |
c<n>.bypassed | 0 | R | circuit <n> is not bypassed |
W | unbypass circuit <n> | ||
1 | R | circuit <n> is bypassed | |
W | bypass circuit <n> | ||
c<n>.isolated | 0 | R | circuit <n> is not isolated |
W | un-isolate circuit <n> | ||
1 | R | circuit <n> is isolated | |
W | isolate circuit <n> | ||
c<n>.soaked | 0 | R | circuit <n> is not soaked |
W | un-soak circuit <n> | ||
1 | R | circuit <n> is soaked | |
W | soak circuit <n> | ||
c<n>.status[Note 1] | <status_values> | R | the status of circuit <n> is set to the reported values |
c<n>.attributes[Note 1] | <attributes_values> | R | the attributes of circuit <n> are set to the reported values |
c<n>.resistance[Note 1] | <value> | R | the measured resistance on circuit <n> is <value> ohm |
>20k | R | the measured resistance on circuit <n> is greater than 20 K-ohm | |
k<n>.tamper | 0 | R | keypad <n> is not tampered |
1 | R | keypad <n> is tampered | |
k<n>.fault | 0 | R | keypad <n> is working properly |
1 | R | keypad <n> is faulty | |
logon.<n> | <user_num> | R | user with number <user_num> logged in from keypad <n> |
error | R | wrong pin entered in keypad <n> | |
system | reset | W | reset alarms |