{| class="wikitable"
 +
!ID
 +
!Attribute
 +
!colspan="2"|Set to
 +
|-
 +
|log
 +
|value
 +
|colspan="2"|latest security log lines (as many as specified by the 'logsize' option)
 +
|-
 +
|log0
 +
|value
 +
|colspan="2"|latest line of the security log when a new entry is added, set back to blank after a short period
 +
|-
 +
|z<n>.name
 +
|value
 +
|colspan="2"|name assigned to zone <n>
 +
|-
 +
|p<n>.name
 +
|value
 +
|colspan="2"|name assigned to partition <n>
 +
|-
 +
|rowspan="2"|connection.offline
 +
|rowspan="2"|visible
 +
|true
 +
|when datapoint connection = offline
 +
|-
 +
|false
 +
|when datapoint connection = online
 +
|-
 +
|rowspan="2"|connection.online
 +
|rowspan="2"|visible
 +
|true
 +
|when datapoint connection = online
 +
|-
 +
|false
 +
|when datapoint connection = offline
 +
|-
 +
|rowspan="2"|<datapoint_id>.1
 +
|rowspan="2"|visible
 +
|true
 +
|when datapoint with ID <datapoint_id> has value '1'
 +
|-
 +
|false
 +
|when datapoint with ID <datapoint_id> has value '0'
 +
|-
 +
|rowspan="2"|<datapoint_id>.0
 +
|rowspan="2"|visible
 +
|true
 +
|when datapoint with ID <datapoint_id> has value '0'
 +
|-
 +
|false
 +
|when datapoint with ID <datapoint_id> has value '1'
 +
|}
 +
 +
=== USER Commands ===
 +
 +
{| class="wikitable"
 +
!Name
 +
!Param
 +
!Action
 +
 +
|-
 +
 +
|rowspan="2" |armed
 +
|0
 +
|disarm all groups
 +
|-
 +
|1
 +
|arm all groups
 +
 +
|-
 +
 +
|rowspan="2" |g<n>.armed
 +
|0
 +
|disarm group <n>
 +
|-
 +
|1
 +
|arm group <n>
 +
 +
|-
 +
 +
|rowspan="2" |c<n>.bypassed
 +
|0
 +
|unbypass zone <n>
 +
|-
 +
|1
 +
|bypass zone <n>
 +
 +
|-
 +
 +
|rowspan="2" |c<n>.isolated
 +
|0
 +
|un-isolate zone <n>
 +
|-
 +
|1
 +
|isolate zone <n>
 +
 +
|-
 +
 +
|rowspan="2" |c<n>.soaked
 +
|0
 +
|un-soak zone <n>
 +
|-
 +
|1
 +
|soak zone <n>
 +
 +
|-
 +
 +
|system
 +
|reset
 +
|reset alarms
 +
|-
 +
 +
|rowspan="2" |input.bypassed
 +
|0
 +
|unbypass circuit
 +
|-
 +
|1
 +
|bypass circuit
 +
|-
 +
 +
|rowspan="2" |input.isolated
 +
|0
 +
|un-isolate circuit
 +
|-
 +
|1
 +
|isolate circuit
 +
|-
 +
 +
|rowspan="2" |input.soaked
 +
|0
 +
|un-soak circuit
 +
|-
 +
|1
 +
|soak circuit
 +
|-
 +
 +
|}
  
 
== Release Notes ==
 
== Release Notes ==

Revision as of 10:16, 10 May 2016

The Satel INTEGRA series comprises a variety of multi-area security systems. The integration with HSYCO can be accomplished via direct control through Ethernet connection. The I/O Server complies with the protocol INT-RS v2.13 2015-03-19 and has been tested on firmware version 1.14 2015-12-15.

Satel Configuration

TODO

HSYCO Configuration

Add a SATEL I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • IP Address: host name or IP address of the panel
  • IP Port: TCP/IP port to use (as configured on the panel)

High Availability

  • Shutdown when inactive: defaults to true.

Options

ID Default Values Description
startupevents false true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
logsize 20 n ≥ 0 the number of log lines to display in the UI object
usercode <user_code> default user code to be used to send commands
maxzone 1 ≤ n ≤ 256 highest zone number configured on the panel
maxpartition 1 ≤ n ≤ 32 highest partition number configured on the panel
maxoutput 1 ≤ n ≤ 256 highest output number configured on the panel
maxdoor 1 ≤ n ≤ 64 highest door number configured on the panel

Datapoints

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the panel
armed 0 R all partitions are disarmed
1 R the system is (partially) armed
alarm 0 R the system is not in a alarm state
1 R the system is in a alarm state
alarm.mem 0 R no active alarm memory
1 R the system has an active alarm memory
alarm.fire.mem 0 R no active fire alarm memory
1 R the system has an active fire alarm memory
alarm.fire 0 R no fire alarm
1 R fire alarm active
alarm.tamper 0 R none of the zone are in tamper alarm
1 R at least one zone is in tamper alarm
alarm.tamper.mem 0 R none of the zone have an active tamper alarm memory
1 R at least one zone has an active tamper alarm memory
trouble 0 R no trouble
1 R active system troubles
trouble.mem 0 R no trouble memory active
W clear trouble memory
1 R active system trouble memory
service 0 R service mode not active
1 R service mode active
time YYYY-MM-DD hh:mm:ss R the date/time set on the panel is the reported one (this datapoint is updated every few minutes unless requested with "read")
W set the specified date/time on the panel
read W requests the reading of the panel date/time
p<n>.name <text> R the name of partition <n> is set to <text>
z<n>.name <text> R the name of zone <n> is set to <text>
z<n>.open 0 R zone <n> is closed
1 R zone <n> is open
z<n>.tamper 0 R zone <n> is not tampered
1 R zone <n> is tampered
z<n>.alarm 0 R zone <n> is not in alarm
1 R zone <n> is in alarm
z<n>.alarm.tamper 0 R zone <n> is not in tamper alarm
1 R zone <n> is in tamper alarm
z<n>.alarm.tamper 0 R zone <n> is not in tamper alarm
1 R zone <n> is in tamper alarm
z<n>.alarm.mem 0 R zone <n> does not have an active alarm memory
1 R zone <n> has an active alarm memory
z<n>.alarm.tamper.mem 0 R zone <n> does not have an active tamper alarm memory
1 R zone <n> has an active tamper alarm memory
z<n>.bypassed 0 R zone <n> is not bypassed
W un-bypass zone <n>
1 R zone <n> is bypassed
W bypass zone <n>
z<n>.trouble 0 R 'no violation' trouble not active on zone <n>
1 R 'no violation' trouble active on zone <n>
z<n>.trouble.long 0 R 'long violation' trouble not active on zone <n>
1 R 'long violation' trouble active on zone <n>
z<n>.isolated 0 R zone <n> not isolated
1 R zone <n> isolated
W isolate zone <n>
z<n>.masked 0 R zone <n> not masked
1 R zone <n> masked
z<n>.masked.mem 0 R zone <n> does not have an active masked memory
1 R zone <n> has an active masked memory
p<n>.armed 0 R partition <n> is not armed
W disarm partition <n> using the default user code if specified in the options
1 R partition <n> is armed
W arm partition <n> using the default user code if specified in the options
1f W force arm partition <n> using the default user code if specified in the options
p<n>.armed.<code> 0 W disarm partition <n> using the specified user code
1 W arm partition <n> using the specified user code
1f W force arm partition <n> using the specified user code
p<n>.armed.suppressed 0 R partition <n> is not armed (suppressed)
1 R partition <n> is armed (suppressed)
p<n>.armed1 0 R partition <n> is not armed in mode 1
W disarm partition <n> in mode 1 using the default user code if specified in the options
1 R partition <n> is armed in mode 1
W arm partition <n> in mode 1 using the default user code if specified in the options
1f W force arm in mode 1 partition <n> using the default user code if specified in the options
p<n>.armed1.<code> 0 W disarm partition <n> in mode 1 using the specified user code
1 W arm partition <n> in mode 1 using the specified user code
1f W force arm partition <n> in mode 1 using the specified user code
p<n>.armed2 0 R partition <n> is not armed in mode 2
W disarm partition <n> in mode 2 using the default user code if specified in the options
1 R partition <n> is armed in mode 2
W arm partition <n> in mode 2 using the default user code if specified in the options
1f W force arm in mode 2 partition <n> using the default user code if specified in the options
p<n>.armed2.<code> 0 W disarm partition <n> in mode 2 using the specified user code
1 W arm partition <n> in mode 2 using the specified user code
1f W force arm partition <n> in mode 2 using the specified user code
p<n>.armed3 0 R partition <n> is not armed in mode 3
W disarm partition <n> in mode 3 using the default user code if specified in the options
1 R partition <n> is armed in mode 3
W arm partition <n> in mode 3 using the default user code if specified in the options
1f W force arm in mode 3 partition <n> using the default user code if specified in the options
p<n>.armed3.<code> 0 W disarm partition <n> in mode 3 using the specified user code
1 W arm partition <n> in mode 3 using the specified user code
1f W force arm partition <n> in mode 3 using the specified user code
p<n>.open 0 R partition <n> has no open zone
1 R partition <n> has open zones
p<n>.alarm.verified 0 R partition <n> has no verified alarm
1 R partition <n> has verified alarms
p<n>.warning 0 R partition <n> has no warnings
1 R partition <n> has warnings
p<n>.code 0 R partition <n> has 1st code not entered
1 R partition <n> has 1st code entered
p<n>.entry 0 R entry time not active on partition <n>
1 R entry time active on partition <n>
p<n>.exit.gt10 0 R exit time on partition <n> not active or not greater than 10 seconds
1 R exit time on partition <n> is active and greater than 10 seconds
p<n>.exit.lt10 0 R exit time on partition <n> not active or not less than 10 seconds
1 R exit time on partition <n> is active and less than 10 seconds
p<n>.blocked.temp 0 R partition <n> not temporary blocked
1 R partition <n> temporary blocked
p<n>.blocked.guard 0 R partition <n> not blocked for guard round
1 R partition <n> blocked for guard round
p<n>.alarm 0 R partition <n> not alarmed
1 R partition <n> alarmed
clear W clear alarms on partition <n> using the default user code if specified in the options
p<n>.alarm.<code> clear W clear alarms on partition <n> using the specified user code
p<n>.alarm.fire 0 R no fire alarm on partition <n>
1 R fire alarm on partition <n>
p<n>.alarm.mem 0 R partition <n> does not have an active alarm memory
1 R partition <n> has an active alarm memory
p<n>.alarm.fire.mem 0 R partition <n> does not have an active fire alarm memory
1 R partition <n> has an active fire alarm memory
o<n>.on 0 R output <n> is off
W switch off output <n> using the default user code if specified in the options
1 R output <n> is on
W switch on output <n> using the default user code if specified in the options
<any_other_val> W invert output <n>'s state using the default user code if specified in the options
o<n>.on.<code> 0 W switch off output <n> using the specified user code
1 W switch on output <n> using the specified user code
<any_other_val> W invert output <n>'s state using the specified user code
d<n>.open 0 R door <n> is closed
1 R door <n> is open
W open door <n> using the default user code if specified in the options
d<n>.open.<code> 1 W open door <n> using the specified user code
d<n>.open.long 0 R door <n> has not been open for a long time
1 R door <n> has been open for a long time


User Interface

Satel Object

The user interface for the Satel multi-area intrusion detection system:

Satel UI Object 1.png Satel UI Object 2.png Satel UI Object 3.png

The Satel object is listed in the Project Editor’s new object list only when at least one Satel I/O Server is defined.


Parameters

  • server id: the server ID
  • position: the object's position. Use the pixels or rows and columns coordinates format

Syntax

(satel <server id>; <position>)

E.g.

(satel serverid; x10y20)

UISET Actions

ID Attribute Set to
log value latest security log lines (as many as specified by the 'logsize' option)
log0 value latest line of the security log when a new entry is added, set back to blank after a short period
z<n>.name value name assigned to zone <n>
p<n>.name value name assigned to partition <n>
connection.offline visible true when datapoint connection = offline
false when datapoint connection = online
connection.online visible true when datapoint connection = online
false when datapoint connection = offline
<datapoint_id>.1 visible true when datapoint with ID <datapoint_id> has value '1'
false when datapoint with ID <datapoint_id> has value '0'
<datapoint_id>.0 visible true when datapoint with ID <datapoint_id> has value '0'
false when datapoint with ID <datapoint_id> has value '1'

USER Commands

Name Param Action
armed 0 disarm all groups
1 arm all groups
g<n>.armed 0 disarm group <n>
1 arm group <n>
c<n>.bypassed 0 unbypass zone <n>
1 bypass zone <n>
c<n>.isolated 0 un-isolate zone <n>
1 isolate zone <n>
c<n>.soaked 0 un-soak zone <n>
1 soak zone <n>
system reset reset alarms
input.bypassed 0 unbypass circuit
1 bypass circuit
input.isolated 0 un-isolate circuit
1 isolate circuit
input.soaked 0 un-soak circuit
1 soak circuit

Release Notes

3.6.0

  • initial version release


Satel is a registered trademark of Satel Italia srl.