Difference between revisions of "IonoPi"

From HSYCO
Jump to navigation Jump to search
Line 9: Line 9:
  
 
== HSYCO Configuration ==
 
== HSYCO Configuration ==
Add a IONO I/O Server in the [[Settings#I/O Servers|I/O Servers section of the Settings]] and set its parameters:
+
Add a IONO Pi I/O Server in the [[Settings#I/O Servers|I/O Servers section of the Settings]] and set its parameters:
  
 
=== Communication ===
 
=== Communication ===

Revision as of 11:35, 2 May 2017

Iono Pi is a versatile I/O module that combines several digital and analog input lines, power relay outputs and support for standard interfaces, typical of modern PLCs, with the powerful computing core of the Raspberry Pi.

iono Pi

This driver provides support for iono Pi pre-installed with the Sfera Framework and the Sfera Driver for Iono Pi.

HSYCO Configuration

Add a IONO Pi I/O Server in the I/O Servers section of the Settings and set its parameters:

Communication

  • IP Address: the IP address assigned to iono;

High Availability

  • Shutdown when inactive: defaults to true.

Options

ID Default Values Description
startupevents true true generate IO events also during the driver’s start-up phase
false start generating events only after HSYCO is aligned with the current status of the system
pollinterval 0 0 the driver will use the push notifications sent by iono to monitor its changes
int > 0 the driver will poll iono's state with the specified time interval (in seconds). Push notifications won't be enabled
input1 digital digital the specified multi-mode input will be read as digital signal (DI<n>)
input2
input3 voltage the specified multi-mode input will be read as analog voltage (AV<n>)
input4 current the specified multi-mode input will be read as analog current (AI<n>)
stabletime 100 int > 0 number of milliseconds an input must be stable before a push notification is sent by iono to HSYCO
minvariation 0.1 float > 0 minimun value variation (for analog inputs) to trigger a push notification
subscribehost <host_name> hostname or IP address to be used by iono to send push notifications. Leave blank to let the driver discover the local address

Datapoints

For inputs 1 to 4, depending on the 'input1' ... 'input4' options, only the corresponding datapoint will be created, i.e. di<n> (if digital), av<n> (if voltage) or ai<n> (if curent).

ID Value R/W Description
connection online R connection established
offline R HSYCO can't connect to the device
do<n> 0 R relay <n> (digital output) is off
W switch off relay <n>
1 R relay <n> (digital output) is on
W switch on relay <n>
di<n> 0 R digital input <n> is low
1 R digital input <n> is high
av<n> <val> R analog input <n> is reading a voltage equal to <val> (in Volts)
ai<n> <val> R analog input <n> is reading a current equal to <val> (in mA)
ao1 <val> W set the analog output to <val> Volts

User Interface

To control a digital output (DO1 ... DO6), add a button or a buttonicon object to your project page and set its address field to the corresponding datapoint:

Iono UI Buttonicon.png

Release Notes

3.5.0

  • initial release


iono is a registered trademark of Sfera Labs Srl