Revision as of 08:32, 19 April 2019
KILSEN KFP-A are multi-area fire panels. The integration with HSYCO can be accomplished via a standard Modbus TCP/IP connection. This I/O server was developed following the MODBUS documentation P/N 00-3243-505-1603-01 • ISS 14DEC15
Communication
KILSEN panels can be connected via ethernet. A valid IP address must be assigned to the panel. MODBUS PROTOCOL must be enabled. Please refer to the manual for detailed instruction about MODBUS protocol configuration.
HSYCO Configuration
Add a KILSEN I/O Server in the I/O Servers section of the Settings and set its parameters:
Communication
- Address: IP address of the KILSEN panel
- Port: TCP/IP port for MODBUS communication (default 502)
High Availability
- Shutdown when inactive: defaults to false.
Options
ID | Default | Values | Description |
---|---|---|---|
gui | true | true | enable support for the UI object, UISET actions and USER commands |
false | disable UI support | ||
startupevents | false | true | generate IO events also during the driver’s start-up phase |
false | start generating events only after HSYCO is aligned with the current status of the system | ||
loopsnumber | 1 | > 0 | total number of loops |
sensorsnsumber | 1 | 0 ... 128 | set to the highest sensor number configured in the panel |
modulesnumber | 1 | 0 ... 128 | set to the highest module number configured in the panel |